Carrier 48EJ, 48EW, 48AW, 48EK CCN Connection Approved Shielded Cables, Color Code Recommendations

Page 47

Fig. 32 — Field Control Thermostat Wiring

NOTE: Sensor part numbers are as follows:

T-55CEC0121448-01

T-56CEC0121448-01

Fig. 33 — Field Control Temperature Sensor

Wiring (CV or VAV Units)

Conductors and drain wire must be 20 AWG minimum stranded, tinned copper. Individual conductors must be insulat- ed with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum op- erating temperature range of -20 C to 60 C (-4 F to 140 F) is re- quired. Table 9 lists cables that meet the requirements.

Table 9 — CCN Connection Approved

Shielded Cables

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

IMPORTANT: When connecting the CCN communica- tion bus to a system element, use a color coding system for the entire network to simplify installation and checkout. See Table 10.

Table 10 — Color Code Recommendations

SIGNAL

CCN BUS CONDUCTOR

CCN PLUG

TYPE

INSULATION COLOR

PIN NO.

Positive (+)

RED

1

Ground

WHITE

2

Negative (-)

BLACK

3

NOTE: If a cable with a different color scheme is selected, a similar color code should be adopted for the entire network.

At each system element, the shields of the communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the com- munication bus cable exits from one building and enters anoth- er, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only).

To connect the unit to the network:

1.Turn off power to the control box.

2.Cut the CCN wire and strip the ends of the red (+), white (ground), and black (-) conductors. (If a different network color scheme is used, substitute appropriate colors.)

3.Remove the 3-pin male plug from the base control board in the main control box, and connect the wires as follows:

a.Insert and secure the red (+) wire to terminal 1 of the 3-pin plug.

b.Insert and secure the white (ground) wire to termi- nal 2 of the 3-pin plug.

c.Insert and secure the black (-) wire to terminal 3 of the 3-pin plug.

4.Insert the plug into the existing 3-pin mating connector on the base module in the main control box.

47

Image 47
Contents Installation, Start-Up Service Instructions Instructions on Make Unit Duct ConnectionsRoof Curb 48AJ,AK020-030 and 48EJ,EK024-034 Units Roof Curb 48AJ,AK034-050 and 48EJ,EK038-048 Units Roof Curb 48AJ,AK060 and 48EJ,EK054-068 Units Page Base Unit Dimensions 48AJ,AK020-030 Base Unit Dimensions 48AJ,AK035-050 Base Unit Dimensions 48AJ,AK060 Base Unit Dimensions 48AW,AY020-030 Base Unit Dimensions 48AW,AY035-050 Base Unit Dimensions 48W,AY060 Base Unit Dimensions 48EJ,EK024-034 Base Unit Dimensions 48EJ,EK038-048 Base Unit Dimensions 48EJ,EK054-068 Base Unit Dimensions 48EW,EY024-034 Base Unit Dimensions 48EW,EY038-048 Base Unit Dimensions 48EW,EY054-068 AT Each Corner % 48EJ,EW,EK,EYD030 Rigging Weights 48AJ,AK,AW,AY UnitsAT Each Corner % 48EJ,EW,EK,EYD024 48EJ,EW,EK,EYD028Unit 48AJ,AK,AW,AY Physical Data 48AJ,AK,AW,AY UnitsQuantity Rows...Fins/in Unit 48EJ,EK,EW,EY Physical Data 48EJ,EK,EW,EY Units06D537 06EA250 06EA265 Quantity...Type Ckt 1, Ckt Operating Weights Air Distribution Thru-the-Bottom Evaporator Fan Motor DataCombustion Fan Housing Location Install Flue HoodStages 48A,E Series Staged Gas ImplementationNumber of Stages Model Number Position Heat Size Htstgtyp Thermistor Designations Supply-Air Thermistor Connections Indoor Air Quality Sensor Configuration Make Electrical Connections DIP CCNCOM SIORLA LRA Unbalanced 3-Phase Supply VoltageElectrical Data 48AJ,AK,AW,AY Units Min MaxQty 30.8/28.0 180.5/177.7 225/225 236.3/230.9 MCA Mocp EW,EY Electrical Data 48EJ,EK,EW,EY UnitsRange Exhaust FAN Motor FLA LRAFLA LRA MCA Mocp EW,EY 54.0 23.6 41.6 RLA FLANEC GND Ground Field Power Wiring ConnectionsIFC CCBEquip GNDOFC Indoor-Fan Relay Terminal Block Carrier Comfort Network Indoor-Fan CircuitCCN IFC Pesc Color Code Recommendations CCN Connection Approved Shielded CablesSpace Temperature Averaging Wiring Make Outdoor-Air Inlet AdjustmentsAdding Seal Strip to Top of Hood Sides Adding Seal Strip to Sides of Hood Top Mounting Flange Mounting Angle With Tabs Attached to Filter Track Assembly Differential Enthalpy Control and Sensor Control Control Point Curve APPROX. DEG Psychrometric Chart for Enthalpy ControlBarometric Relief Damper and Power Exhaust Mounting Details 120.5 119.5 48EJ,EK,EW,EY058-068 Unit Size80.5 79.5 48EJ,EK,EW,EY024-054 Motormaster III Sensor Location 48EJ,EK,EW,EY054-064 Side Return Air Conversion Field ModificationsSTART-UP In. wg Pressure Control Signal VFD SET PointParameter Group Default Value Carrier Default Program Parameter ValuesMotor Standard Efficiency High Efficiency Typical Factory Wiring Optional Field Wiring Building Pressure Signal Level Closed DIP Switch ConfigurationSetting OpenAirflow DIP Switch Factory SettingsFan Performance, 48AJ,AK020-030 Vertical Discharge Units 18,000 Fan Performance, 48AJ,AK035 Vertical Discharge Units16,000 17,00017,000 18,000 19,000 20,000 Fan Performance, 48AJ,AK040,050 Vertical Discharge Units19,000 20,000Fan Performance, 48AJ,AK060 Vertical Discharge Units 11,000 12,000 13,000 14,000 15,000 Fan Performance, 48AW,AY020-030 Horizontal Discharge Units13,000 14,000 15,000 16,000 17,000 18,000 Fan Performance, 48AW,AY035 Horizontal Discharge Units17,000 18,000 16,000 17,000 18,000 19,000 20,000 Fan Performance, 48AW,AY040,050 Horizontal Discharge Units19,000 20,000 26,000 27,000 Fan Performance, 48AW,AY060 Horizontal Discharge UnitsFan Performance, 48EJ,EK024,034 Vertical Discharge Units 15,000 16,000 17,000 18,000 19,000 20,000 Fan Performance, 48EJ,EK038,044 Vertical Discharge Units19,000 20,000 Available External Static Pressure in. wg Rpm Bhp 000 1066 1096 1125000 1086 11.10 1114 11.61 1141 12.14 Fan Performance, 48EJ,EK048 Vertical Discharge UnitsRpm Bhp 10,000 949 13.81 970 14.54 990 15.26 Fan Performance, 48EJ,EK054-068 Vertical Discharge Units20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 Fan Performance, 48EW,EY054-068 Horizontal Discharge Units26,000 27,000 Available External Static Pressure in. wg 10,000 956 12.99 976 13.66 996 14.32ESP Airflow LOW Speed Medium Speed High SpeedAir Quality Limits Motor LimitationsSequence of Operation Software Control Link Points User Defined Set PointsPage COM Common Heat Interlock Relay WiringInput Description Staged Gas System ComponentsStage Gas System Inputs/Outputs Function LocationNavigator Display Menu Structure Navigator DisplayCondition Occupied Morning Temperature Software HeatVersion Enabled DEG. F ResetField-Supplied Smoke Detector Wiring Stages Smoke Control ModesCooling Capacity Staging Table, CV Units with 2 Compressors Device Pressurization Smoke Purge Evacuation Fire ShutdownService Typical Gas Heating Section Manufacturer Lubricant LubricationCondenser-Fan Adjustment Evaporator Fan Service and ReplacementBelt Tension Adjustment To adjust belt tension Evaporator-Fan Motor ReplacementCooling Charging Chart 48EJ,EK,EW,EY024-034 Gas Valve AdjustmentCooling Charging Chart 48EJ,EK,EW,EY054-068 Protective Devices 20 HP 208/230-3-60 Voltage WireIndoor Voltage Wire 06D-537 208/230-3-60 Following fan motors have twoTypical 48EK VAV 24-V Control Circuit Typical CV 24-V Control Circuit Typical 48EK VAV 115-V Control Circuit Typical 48EJ CV 115-V Control Circuit 101 102 Troubleshooting Typical Refrigerant Circuiting 48AJ,AK,AW,AY027,030 Typical Refrigerant Circuiting 48AJ,AK,AW,AY035 Typical Refrigerant Circuiting 48EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 48AJ,AK,AW,AY040,050 Typical Refrigerant Circuiting 48EJ,EK,EW,EY048 Typical Refrigerant Circuiting 48EJ,EK,EW,EY054 Typical Refrigerant Circuiting 48AJ,AK,AW,AY060 Typical Refrigerant Circuiting 48EJ,EK,EW,EY064 Typical Refrigerant Circuiting 48EJ,EK,EW,EY068 IGC Control Heating and Cooling Control Board LED Alarms IGC Control Board LED AlarmsIAQ O Channel Designations Base Module CVO Channel Designations Base Module VAV Terminal no AssignmentService Training START-UP Checklist General
Related manuals
Manual 64 pages 39.75 Kb Manual 36 pages 38.76 Kb

48EJ, 48AJ, 48AK, 48EK, 48AY020-060 specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.