Carrier 48EW, 48AW Unit Size, 80.5 79.5 48EJ,EK,EW,EY024-054, 120.5 119.5 48EJ,EK,EW,EY058-068

Page 55

Install Motormaster® III Controls — Only one Motormaster III control is required per unit.

Motor — One outdoor-fan motor (OFM) must be changed out in the field to accommodate the Motormaster III accessory. The replacement motor part no. is HD52AK652.

For 48AJ,AK,AW,AY020-030 and 48EJ,EK,EW,EY024- 034 units, the Motormaster controlled OFM is the no. 2 OFM and is located at the left side of the unit looking from the com- pressor end. The no. 1 OFM is controlled to shut off at 55 F and on at 65 F outdoor-air temperature and does NOT need to be changed out.

For 48AJ,AK,AW,AY035-050 and 48EJ,EK,EW,EY038- 054 units, the Motormaster controlled OFM is no. 1 OFM and is located at the left side of the unit looking from the compres- sor end and the second motor back. The no. 3 and 4 OFM are controlled to shut off at 55 F and on at 65 F outdoor-air temper- ature and do NOT need to be changed out. The no. 2 OFM is intended to run at all ambient temperatures.

For 48AJ,AK,AW,AY060 and 48EJ,EK,EW,EY058-068 units, the Motormaster controlled OFM is no. 3 OFM and is lo- cated at the left side of the unit looking from the compressor end and the second motor back.

The no. 4, 5, and 6 OFMs are controlled to shut off at 55 F and on at 65 F outdoor-air temperature and do NOT need to be changed out. The no. 1 and 2 OFMs are intended to run at all ambient temperatures.

Sensor — Install the sensor for thermistor input control in the location shown in Fig. 53A-53E. Connect sensor leads to the violet and gray control signal leads on the Motormaster III control.

Signal Selection Switch — Remove the cover of the Motor- master III control. Set the switch to accept the thermistor sensor input signal. Set the frequency to match the unit power supply (60 Hz).

Motormaster III Control — The recommended mounting loca- tion is in the indoor fan section, mounted on the panel that sep- arates the indoor and outdoor sections. On VAV units, this location is next to the VFD (variable frequency drive).

Do not route the Motormaster III control wiring next to the VFD on VAV units. Use a separate connector through the parti- tion when wiring to the OFM.

Electrical Connections

To avoid possibility of electrical shock and personal injury, turn off all power to unit before making electrical connections.

When replacing the OFM, reconnect the black, yellow, and blue wires form the outdoor fan contactor to the black, yellow, and blue wires of the Motormaster III control. Run new wires from the red, orange, and brown wires to the leads of the new OFM. Connect the green wire from the control to ground.

NOTE: On all 575-v units, 2 transformers (part no. HT01AH851) must be used for each Motormaster III control to lower the supply voltage to the control to 460-v. Transform- ers can be mounted anywhere outside the control box.

1 BOTH SIDES

18

B

0.312 DIA HOLES

61

17.167

 

BETWEEN

 

HOLES

 

(TYPICAL)

CROSS-BREAK

A

0.5

4.62

 

UNIT SIZE

A

B

48AJ,AK,AW,AY020-050 and

80.5

79.5

48EJ,EK,EW,EY024-054

 

 

48AJ,AK,AW,AY060 and

120.5

119.5

48EJ,EK,EW,EY058-068

 

 

NOTE: All dimensions are in inches. Material: 20 gage galvanized steel or other non-corrosive material.

Fig. 52 — Motormaster III Control Baffle Details

Fig. 53A — Motormaster III Sensor Location

(48AJ,AK,AW,AY020-030 and

48EJ,EK,EW,EY024-034)

55

Image 55
Contents Installation, Start-Up Service Instructions Instructions on Make Unit Duct ConnectionsRoof Curb 48AJ,AK020-030 and 48EJ,EK024-034 Units Roof Curb 48AJ,AK034-050 and 48EJ,EK038-048 Units Roof Curb 48AJ,AK060 and 48EJ,EK054-068 Units Page Base Unit Dimensions 48AJ,AK020-030 Base Unit Dimensions 48AJ,AK035-050 Base Unit Dimensions 48AJ,AK060 Base Unit Dimensions 48AW,AY020-030 Base Unit Dimensions 48AW,AY035-050 Base Unit Dimensions 48W,AY060 Base Unit Dimensions 48EJ,EK024-034 Base Unit Dimensions 48EJ,EK038-048 Base Unit Dimensions 48EJ,EK054-068 Base Unit Dimensions 48EW,EY024-034 Base Unit Dimensions 48EW,EY038-048 Base Unit Dimensions 48EW,EY054-068 AT Each Corner % 48EJ,EW,EK,EYD030 Rigging Weights 48AJ,AK,AW,AY UnitsAT Each Corner % 48EJ,EW,EK,EYD024 48EJ,EW,EK,EYD028Unit 48AJ,AK,AW,AY Physical Data 48AJ,AK,AW,AY UnitsQuantity Rows...Fins/in Unit 48EJ,EK,EW,EY Physical Data 48EJ,EK,EW,EY Units06D537 06EA250 06EA265 Quantity...Type Ckt 1, Ckt Operating Weights Air Distribution Thru-the-Bottom Evaporator Fan Motor DataCombustion Fan Housing Location Install Flue HoodNumber of Stages Model Number Position Heat Size Htstgtyp 48A,E Series Staged Gas ImplementationStages Thermistor Designations Supply-Air Thermistor Connections Indoor Air Quality Sensor Configuration Make Electrical Connections DIP CCNCOM SIORLA LRA Unbalanced 3-Phase Supply VoltageElectrical Data 48AJ,AK,AW,AY Units Min MaxQty 30.8/28.0 180.5/177.7 225/225 236.3/230.9 MCA Mocp EW,EY Electrical Data 48EJ,EK,EW,EY UnitsRange Exhaust FAN Motor FLA LRAFLA LRA MCA Mocp EW,EY 54.0 23.6 41.6 NEC FLARLA GND Ground Field Power Wiring ConnectionsIFC CCBEquip GNDOFC CCN IFC Pesc Carrier Comfort Network Indoor-Fan CircuitIndoor-Fan Relay Terminal Block Color Code Recommendations CCN Connection Approved Shielded CablesSpace Temperature Averaging Wiring Make Outdoor-Air Inlet AdjustmentsAdding Seal Strip to Top of Hood Sides Adding Seal Strip to Sides of Hood Top Mounting Flange Mounting Angle With Tabs Attached to Filter Track Assembly Differential Enthalpy Control and Sensor Control Control Point Curve APPROX. DEG Psychrometric Chart for Enthalpy ControlBarometric Relief Damper and Power Exhaust Mounting Details 80.5 79.5 48EJ,EK,EW,EY024-054 Unit Size120.5 119.5 48EJ,EK,EW,EY058-068 Motormaster III Sensor Location 48EJ,EK,EW,EY054-064 Side Return Air Conversion Field ModificationsSTART-UP In. wg Pressure Control Signal VFD SET PointParameter Group Default Value Carrier Default Program Parameter ValuesMotor Standard Efficiency High Efficiency Typical Factory Wiring Optional Field Wiring Building Pressure Signal Level Closed DIP Switch ConfigurationSetting OpenFan Performance, 48AJ,AK020-030 Vertical Discharge Units DIP Switch Factory SettingsAirflow 18,000 Fan Performance, 48AJ,AK035 Vertical Discharge Units16,000 17,00017,000 18,000 19,000 20,000 Fan Performance, 48AJ,AK040,050 Vertical Discharge Units19,000 20,000Fan Performance, 48AJ,AK060 Vertical Discharge Units 11,000 12,000 13,000 14,000 15,000 Fan Performance, 48AW,AY020-030 Horizontal Discharge Units17,000 18,000 Fan Performance, 48AW,AY035 Horizontal Discharge Units13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 Fan Performance, 48AW,AY040,050 Horizontal Discharge Units16,000 17,000 18,000 19,000 20,000 26,000 27,000 Fan Performance, 48AW,AY060 Horizontal Discharge UnitsFan Performance, 48EJ,EK024,034 Vertical Discharge Units 15,000 16,000 17,000 18,000 19,000 20,000 Fan Performance, 48EJ,EK038,044 Vertical Discharge Units19,000 20,000 Available External Static Pressure in. wg Rpm Bhp 000 1066 1096 1125Rpm Bhp Fan Performance, 48EJ,EK048 Vertical Discharge Units000 1086 11.10 1114 11.61 1141 12.14 10,000 949 13.81 970 14.54 990 15.26 Fan Performance, 48EJ,EK054-068 Vertical Discharge Units20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 Fan Performance, 48EW,EY054-068 Horizontal Discharge Units26,000 27,000 Available External Static Pressure in. wg 10,000 956 12.99 976 13.66 996 14.32ESP Airflow LOW Speed Medium Speed High SpeedAir Quality Limits Motor LimitationsSequence of Operation Software Control Link Points User Defined Set PointsPage COM Common Heat Interlock Relay WiringInput Description Staged Gas System ComponentsStage Gas System Inputs/Outputs Function LocationNavigator Display Menu Structure Navigator DisplayCondition Occupied Morning Temperature Software HeatVersion Enabled DEG. F ResetField-Supplied Smoke Detector Wiring Stages Smoke Control ModesCooling Capacity Staging Table, CV Units with 2 Compressors Device Pressurization Smoke Purge Evacuation Fire ShutdownService Typical Gas Heating Section Manufacturer Lubricant LubricationCondenser-Fan Adjustment Evaporator Fan Service and ReplacementBelt Tension Adjustment To adjust belt tension Evaporator-Fan Motor ReplacementCooling Charging Chart 48EJ,EK,EW,EY024-034 Gas Valve AdjustmentCooling Charging Chart 48EJ,EK,EW,EY054-068 Protective Devices 20 HP 208/230-3-60 Voltage WireIndoor Voltage Wire 06D-537 208/230-3-60 Following fan motors have twoTypical 48EK VAV 24-V Control Circuit Typical CV 24-V Control Circuit Typical 48EK VAV 115-V Control Circuit Typical 48EJ CV 115-V Control Circuit 101 102 Troubleshooting Typical Refrigerant Circuiting 48AJ,AK,AW,AY027,030 Typical Refrigerant Circuiting 48AJ,AK,AW,AY035 Typical Refrigerant Circuiting 48EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 48AJ,AK,AW,AY040,050 Typical Refrigerant Circuiting 48EJ,EK,EW,EY048 Typical Refrigerant Circuiting 48EJ,EK,EW,EY054 Typical Refrigerant Circuiting 48AJ,AK,AW,AY060 Typical Refrigerant Circuiting 48EJ,EK,EW,EY064 Typical Refrigerant Circuiting 48EJ,EK,EW,EY068 IGC Control Heating and Cooling Control Board LED Alarms IGC Control Board LED AlarmsIAQ O Channel Designations Base Module CVO Channel Designations Base Module VAV Terminal no AssignmentService Training START-UP Checklist General
Related manuals
Manual 64 pages 39.75 Kb Manual 36 pages 38.76 Kb

48EJ, 48AJ, 48AK, 48EK, 48AY020-060 specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.