Carrier 50XJ064-104 specifications Omnizone

Page 11

2.Press 3 and then SET . The LID display will show: Controller Password

3.Press ENTER . The LID display will show: Log in to Controller

Enter Password

NOTE: The LID display has two modes: Edit mode and Status/Maintenance mode. If the LID display is in Edit mode, then the display will only show the word “pass- word.” Press the EXPN/EDIT key to toggle to the Status mode.

Press the EXPN/EDIT to display: Log in to Controller

Enter Password

4.Key in the password and press ENTER . NOTE: The default password is 1111.

5.The LID display will show: Log in to Controller Logged In

NOTE: At this point, for the 50BV unit only, the run test will follow these steps:

a.Press 37 ALGO . The display will show: Custom Program

b.Press ENTER . The display will show: 2.0 Global Dictionary

OMNIZONE

c.Press EXPN/EDIT (NOTE: Display will flash, indicating that the device is now in edit mode.) The display will show:

2.0Global Dictionary

OMNIZONE

d.Press ENTER . The display will show: Compressor Stages

NOTE: A 50BV unit with only 2 compressors will display 2.00. Skip to Step 6.

e.Input 2.00 and Press ENTER . The display will show: Compressor Stages

6.Press STAT . The LID display will show: Hardware Points

7.Press STAT again. The LID display will show: Software Points

8.Press ENTER . The LID display will show: Compressor 1 Status

9.Press 6 times. The LID display will show: Factory/Field Test

Stop

10.Press 1 then ENTER , The LID display will show: Factory/Field Test

Start

NOTE: At this point, the yellow warning light on the display panel will be lit and will stay on throughout the run test. After each successful step, the red alarm light will blink once.

11.The control module will now check if there is input from BYPAS (50XJ), DHS, FSD, SAT, DSP, and CSMUX.

If the control does not receive open/open/closed/ in range/in range/in range, the red alarm LED will go on and the test will stop.

If the inputs are OK, the red alarm LED blinks once and the test continues.

12.Next, the control forces the Supply Fan (SF) and all of the Compressors (COMP) off, and waits 15 seconds.

For the 50XJ unit, if the REMOTE LED and AUTO LED on the VFD display are on, the red LED blinks once and the test continues.

NOTE: For the 50XJ unit, if the controller is config- ured with a water Economizer, the delay is 2 min. and both valves are commanded to 0%. Both water valves will close.

13.The control forces SF on and SPEED to 20 percent and then waits 30 seconds.

If the VFD display shows “10.6 Hz,” the Remote and Auto LEDs blink, and the fan goes on, then the red LED on the control module blinks once and the test continues.

NOTE: For the 50XJ unit, if the controller is config- ured with a water Economizer the delay is 2 min. and Econo valve is commanded to 100%. The economizer valve will open and the RVS/HD (reverse/head pressure) valve will remain closed.

14.The control forces SF on and SPEED to 35 percent and then waits 30 seconds.

If the VFD display shows “20.0 Hz,” the Remote and Auto LEDs blink, and the fan goes on, then the red LED on the control module blinks once and the test continues.

NOTE: For the 50XJ unit, if the controller is configured with a water Economizer the delay is 2 min. and RVS/ HD valve is commanded to 100%. The economizer valve is commanded to 0% and the RVS/HD valve will open.

15.The control forces SF off then waits 15 seconds.

If the VFD display shows “Off,” the Remote and Auto LEDs are off, and the fan goes off, then the red LED on the control module blinks once and the test continues.

NOTE: For the 50XJ unit, if the controller is configured with a water Economizer both valves are commanded to 0%. The economizer valve and RVS/HD will close.

NOTE: For the 50BV unit, the steps below (16-24) will be completed for the number of compressors configured.

16.The control forces CMP1 (compressor 1) on then waits 5 seconds.

If CSMUX is not in range the red LED will go on and the test will stop.

If CSMUX is in range, the red LED blinks once and the test continues.

17.The control forces CMP1 off.

18.The control forces CMP2 (compressor 2) on then waits 5 seconds.

If CSMUX is not in range the red LED will go on and the test will stop.

If CSMUX is in range, the red LED blinks once and the test continues.

19.The control forces CMP2 off.

20.The control forces CMP3 (compressor 3) on, if config- ured, then waits 5 seconds.

If CSMUX is not in range the red LED will go on and the test will stop.

If CSMUX is in range, the red LED blinks once and the test continues.

21.The control forces CMP3 off.

11

Image 11
Contents Controls Operation Troubleshooting Page SW2 SW3 SW1 Control Inputs and OutputsManufacturer Part Number Communication Cable RecommendationsWhen the unit is off, both valves are closed Field Terminal Blocks for 50XJ Unit Space Temperature Sensor Typical Wiring 33ZCT55SPT Operative USE Keys LID Function KeysOperative Keys Numeric KeysOmnizone Vpac KEY Algo Stat Hist Srvc Alrm SET Quick Access ChartOmnizone Page SETPT01 OMNIZONESETPT02 Controller Set PointsSoftware Points Configuration ParametersController Hardware Points Operation Page Page RUN VFD Non-Trip Messages for 50XJ Unit Keys and Functions for 50XJ VFDVFD Trip Messages for 50XJ Unit Down VFD Mode Summary for 50XJ UnitKEY Operaton LED Message Explanation 50BV VFD Display Trip Messages for 50BV VFD Non-Trip Messages for the 50BV VFDEPH1 OL1OL2 EphoError Communication Problem Possible Causes Remedies Code Clearing a Forced Input or Output Run Test TroubleshootingForcing an Input or Output Alarms Displayed at Unit LID Comp Volts Range Compressor MUX Board VoltagesUnit Wiring 50BVJ,K Low Voltage Schematic50BVJ,K High Voltage Schematic TRANS-3 24VAC BLU 50BVW,X Low Voltage Schematic50BVW,X High Voltage Schematic PCB2 J1 50BVJ,K,W,X Field-Installed Low Voltage Schematic3 4 5 6 7 50BVJ,K Field-Installed Low Voltage SchemticField Wiring 50BVW,X Field-installed Low Voltage SchematicBpss RoccAqua SPTLOW Voltage Control Wiring 50XJ Low Voltage Control WiringBLK VIO Switch Settings 50XJ 115V Control WiringPower Wiring 50XJ Power WiringPCB3 50BV,XJ Accessory Control Module PCB3 SchematicIFM HeatCdwfs HRNDescription Value Units Status Force Name Ewtrst NumcmpRsetrto Cdwf 0=NO,1=YES Cdfwswt Econ 0=NO,1=YES EwtsnsDescription Value Units Name SETPT00 PntnameSETPT09 SENSDI00High Conversion Endpoint 309.77 Comparison Point OMNIZONEDSALM02 Phase Protection Monitored Input Point OMNIZONEDSALM05 Fire alarm Monitored Input Point OMNIZONEDSALM08 Compressor 1 Alarm Monitored Input Point DISCRO00 LINK09 OMNIZONEINTLK02 Ok to Cool Discrete Output Point HCVAV01 VOLTI00SETPT03 NTFC00OMNIZONELMALM02 Entering WaterTemp Monitored Input Point DOW4 DOW1DOW2 DOW3Maintenance Screens LMALM03 FalseCcvvrf ADAPT03RAM ADAPT02ADAPT01 EepromDodxrf Description Value Units Status Force Name CCVAV01 ANCTL01Exetime LMALM02Resched Taskstat Tasktimr

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.