Table 20 — Alarms Displayed at Unit LID

FUNCTION

ALARM MESSAGE (Actual Text)

CAUSE

UNIT RESPONSE (See Notes)

RESET

SAT

SAT xx.x dF outside

SAT reads out of prescribed range

Unit shuts down and

Automatic

limit of xxx.x dF

for 5 sec. during operation

indicates alarm

 

 

 

 

 

DSP_ALM

Duct Static Sensor Failure

Duct Pressure Sensor reading is out of

Unit shuts down,

indicates alarm

Automatic

 

range (i.e., likely faulty sensor or circuit).

 

 

 

 

 

 

 

 

FSD

Fire Shutdown

External Fire Alarm input opens for 5 sec.

Unit shuts down,

indicates alarm

Automatic

 

Duct High Static Pressure

Pressure rises above 3.0 in.H2O during

Unit shuts down,

indicates alarm

Automatic

DHS

 

operation. Set point adjustable on the switch.

 

 

 

 

Used for Off position of switch on smaller

 

 

 

 

 

 

 

 

 

 

units with one controller

 

 

 

CSMUX

CSMUX x.xx Volts outside

Compressor safety circuit Resistor Board

Unit shuts down and indicates

Automatic

limit of x.xx Volts

reads out of prescribed range for 5 sec.

alarm

 

 

 

 

during operation

 

 

 

CDWF

Check Condenser Water Flow

Waterflow Switch contacts are open at startup,

Compressor Cooling shuts down,

Automatic

 

or go open for 5 sec. during operation.

locks out and indicates warning

 

 

 

 

FLTS

Change Filters

Filter pressure drop exceeds Filter Pressure

Unit operates normally,

Automatic

 

Switch setting (and contacts open) for 5 sec.

but still indicates Warning

 

 

 

 

 

Economizer Freeze Condition

Economizer Freeze Switch contacts for 5 sec.

Warning indicated for 15 minutes

Automatic

FREEZ

 

open during operation.

turns off ventilation request, then

 

 

 

unit shuts down and Econo valve

 

 

 

 

opens, pump request stays on,

 

 

 

 

and Alarm indicated

 

C1_ALM

Compressor 1 Fault

Compressor safety circuit opens for 2 sec.

Unit shuts that compressor down,

Automatic

C2_ALM

Compressor 2 Fault

 

and indicates Warning, but retries

 

C3_ALM

Compressor 3 Fault

 

2 more times before locking it out.

 

C4_ALM

Compressor 4 Fault

 

 

 

 

 

Check Supply Fan

Duct Pressure Sensor reading is below .3 in.

If on but indicates off cooling,

Automatic

SFS

 

H2O at 10 sec. after starting fan, or during

and heating will be disabled

 

 

operation, or reads above .3when fan is

warning light will be on

 

 

 

 

 

 

supposed to be Off.

 

 

 

EWT

EWT xx.x dF outside

EWT reads out of prescribed range for 5 sec.

Indicates warning

Automatic

limit of xxx.x dF

or more

 

 

 

 

 

 

 

MA_RA

MA_RA xx.x dF outside

ma_ra reads out of prescribed range for 5 sec.

Indicates warning

Automatic

limit of xxx.x dF

or more

 

 

 

 

 

 

 

PHASE

Phase Loss

Phase monitor activates (see “Phase

Unit shuts down,

indicates alarm

Automatic

 

Loss/Reversal Protection Switch” on page 5)

 

 

 

 

 

for 5 sec. during operation.

 

 

 

BYPAS

 

BYPAS switch in Bypass position or Off,

 

 

 

 

local remote in Off position

 

 

 

 

 

 

 

 

NOTES:

1.Unit display will indicate alarm by displaying “There is 1 Alarm” or “There are X alarms”, for the active alarms in the controller.

2.Red light on, indicating alarm.

3.Yellow light is on, indicating a warning.

Standard Diagnostic Features, Alarm and Warning Lights

SUPPLY AIR TEMPERATURE SENSOR FAILURE — If the supply air temperature sensor fails and indicates either 245 F from a short or -40.0 F from and open sensor the control- ler outputs will be forced to off with safety forces, the alarm output will close and the red Alarm light will be lit. A system alarm will be generated and displayed on the unit keypad. Unit reset is automatic when the supply air sensor has a valid reading again.

DUCT STATIC PRESSURE SENSOR FAILURE — If the duct static pressure sensor fails and indicates either 5.0 inches from a short or 0.0 inches from and open sensor the controller outputs will be forced to off with safety forces, the alarm output will close and the red Alarm light will be lit. A system alarm will be generated and displayed on the unit keypad. Unit reset is automatic when the supply air sensor has a valid reading again.

FIRE/SHUTDOWN INPUT (FSD) — This is a normally closed input, which when opened, deenergizes an isolation relay in the unit, opening the input to the controller. When this input turns opens, all control outputs are immediately turned off, including the fan. Fire forces will be displayed on the outputs. Unit reset is automatic when the FSD input is closed

again. A system alarm will be generated and displayed at the keypad.

DUCT HIGH STATIC INPUT (DHS) — This air switch provides over pressurization protection for the ductwork. It is factory installed in the unit. The switch is a normally open switch, with adjustable manual setting (range is 1 to 5 in. wg default setting is 3.0 in. wg). Upon switch closure, the control- ler outputs will be forced to off with safety forces, the alarm output will close and the red Alarm light will be lit. A system alarm will be generated and displayed on the unit keypad. Unit reset is automatic when the duct pressure is again below the switch setting minus the device hysteresis.

COMPRESSOR MULTIPLEX (MUX) BOARD — A re- sistance board is used to generate a variable voltage input to the controller to determine compressor status. If the voltage output from this board gets out of the acceptable range the controller outputs will be forced to off with safety forces, the alarm output will close and the red Alarm light will be lit. A system alarm will be generated and displayed on the unit keypad. Unit reset is automatic when the Mux board has a valid reading again. The valid range is between 1.5 and 10 vdc. The table below indicates what voltages correspond to the compressor status indicated in the controller.

28

Image 28
Contents Controls Operation Troubleshooting Page Control Inputs and Outputs SW2 SW3 SW1Communication Cable Recommendations Manufacturer Part NumberWhen the unit is off, both valves are closed Field Terminal Blocks for 50XJ Unit Space Temperature Sensor Typical Wiring 33ZCT55SPT LID Function Keys Operative KeysNumeric Keys Operative USE KeysOmnizone Vpac Quick Access Chart KEY Algo Stat Hist Srvc Alrm SETOmnizone Page SETPT01 Controller Set Points OMNIZONESETPT02Controller Hardware Points Configuration ParametersSoftware Points Operation Page Page RUN Keys and Functions for 50XJ VFD VFD Non-Trip Messages for 50XJ UnitVFD Trip Messages for 50XJ Unit KEY Operaton LED Message Explanation VFD Mode Summary for 50XJ UnitDown 50BV VFD Display Non-Trip Messages for the 50BV VFD Trip Messages for 50BV VFDOL1 OL2Epho EPH1Error Communication Problem Possible Causes Remedies Code Forcing an Input or Output Run Test TroubleshootingClearing a Forced Input or Output Alarms Displayed at Unit LID Compressor MUX Board Voltages Comp Volts Range50BVJ,K Low Voltage Schematic Unit Wiring50BVJ,K High Voltage Schematic 50BVW,X Low Voltage Schematic TRANS-3 24VAC BLU50BVW,X High Voltage Schematic 50BVJ,K,W,X Field-Installed Low Voltage Schematic PCB2 J150BVJ,K Field-Installed Low Voltage Schemtic 3 4 5 6 750BVW,X Field-installed Low Voltage Schematic Field WiringRocc AquaSPT Bpss50XJ Low Voltage Control Wiring LOW Voltage Control Wiring50XJ 115V Control Wiring BLK VIO Switch Settings50XJ Power Wiring Power Wiring50BV,XJ Accessory Control Module PCB3 Schematic PCB3Heat CdwfsHRN IFMDescription Value Units Status Force Name Numcmp RsetrtoCdwf 0=NO,1=YES Cdfwswt Econ 0=NO,1=YES Ewtsns EwtrstDescription Value Units Name Pntname SETPT09SENSDI00 SETPT00High Conversion Endpoint 309.77 Comparison Point OMNIZONEDSALM02 Phase Protection Monitored Input Point OMNIZONEDSALM05 Fire alarm Monitored Input Point OMNIZONEDSALM08 Compressor 1 Alarm Monitored Input Point DISCRO00 LINK09 OMNIZONEINTLK02 Ok to Cool Discrete Output Point VOLTI00 SETPT03NTFC00 HCVAV01OMNIZONELMALM02 Entering WaterTemp Monitored Input Point DOW1 DOW2DOW3 DOW4Maintenance Screens False CcvvrfADAPT03 LMALM03ADAPT02 ADAPT01Eeprom RAMDodxrf Description Value Units Status Force Name ANCTL01 CCVAV01LMALM02 Resched TaskstatTasktimr Exetime

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.