Table 16 — Trip Messages for 50BV VFD (cont)

ERROR

COMMUNICATION

PROBLEM

POSSIBLE CAUSES

REMEDIES

CODE

NO.

 

 

 

OP3

C

Overvoltage during

• The input voltage fluctuates abnormally.

• Insert a suitable input reactor.

 

 

constant-speed

(1) The power supply has a capacity of

 

 

 

operation

200kVA or more.

 

 

 

 

(2) A power factor improvement capacitor is

 

 

 

 

opened or closed.

 

 

 

 

(3) A system using a thyristor is connected

 

 

 

 

to the same power distribution line.

• Install a dynamic braking resistor.

 

 

 

• The motor is in a regenerative state

 

 

 

because the load causes the motor to run at

 

 

 

 

a frequency higher than the inverter

 

 

 

 

output frequency.

 

OL1

D

Inverter overload

• The acceleration ACC time is too short.

• Increase the acceleration time ACC.

 

 

 

• The DC braking amount is too large.

• Reduce the DC braking amount F251

 

 

 

• The V/F setting is improper.

and the DC braking time F252.

 

 

 

• A restart signal is input to the rotating

• Check the V/F parameter setting.

 

 

 

motor after a momentary stop, etc.

• Use F301 (auto-restart) and F302

 

 

 

• The load is too large.

(ride-through control).

 

 

 

 

• Use an inverter with a larger rating.

OL2

E

Motor overload

• The V/F setting is improper.

• Check the V/F parameter setting.

 

 

 

• The motor is locked up.

• Check the load (operated machine).

 

 

 

Low-speed operation is performed

• Adjust OLN to the overload that the

 

 

 

continuously.

motor can withstand during operation in a

 

 

 

• An excessive load is applied to the motor

low speed range.

 

 

 

during operation.

 

*EPHO

9

Output phase failure

• A phase failure occurred in the output line

• Check the main circuit output line, motor,

 

 

 

of the main circuit.

etc., for phase failure.

 

 

 

 

• Enable F605 (Output phase failure

 

 

 

 

detection).

*EPH1

8

Input phase failure

• A phase failure occurred in the input line

• Check the main circuit input line for phase

 

 

 

of the main circuit.

failure.

 

 

 

 

• Enable F608 (input phase failure

 

 

 

 

detection).

OH2

2Eh

External thermal trip

• A thermal trip command is entered from

• Check the external input device.

 

 

 

an external input device.

 

*Ot

20h

Over-torque trip

• The load torque rises up to the over-torque

• Enable F615 (Over-torque trip selection)

 

 

 

detection level during operation

• Check whether the system is in a normal

 

 

 

 

condition.

OLr

F

Dynamic braking

• The deceleration time is too short.

• Increase the deceleration time dEC.

 

 

resistor overload trip

• The dynamic braking amount is too large.

• Use a dynamic resistor with a larger

 

 

 

 

capacity (W) and adjust F308 (PBR

 

 

 

 

capacity parameter) accordingly.

OH

10h

Overheat

• The cooling fan does not rotate.

• Restart the operation by resetting the

 

 

 

• The ambient temperature is too high.

inverter after it has cooled down enough.

 

 

 

• The vent is blocked up.

• The fan requires replacement if it does

 

 

 

• A heat generating device is installed close

not rotate during operation.

 

 

 

to the inverter.

• Secure sufficient space around the

 

 

 

• The thermistor in the unit is broken.

inverter.

 

 

 

 

• Do not place any heat-generating device

 

 

 

 

near the inverter.

 

 

 

 

• Make a service call.

*UP1

1E

Undervoltage trip

• The input voltage (in the main circuit) is

• Check the input voltage.

 

 

(main circuit)

too low.

• Enable F627 (undervoltage trip

 

 

 

 

selection).

 

 

 

 

• To cope with a momentary stop due to

 

 

 

 

undervoltage, enable F302 (ride-through

 

 

 

 

control) and F301 (auto-restart).

25

Image 25
Contents Controls Operation Troubleshooting Page SW2 SW3 SW1 Control Inputs and OutputsManufacturer Part Number Communication Cable RecommendationsWhen the unit is off, both valves are closed Field Terminal Blocks for 50XJ Unit Space Temperature Sensor Typical Wiring 33ZCT55SPT Operative Keys LID Function KeysNumeric Keys Operative USE KeysOmnizone Vpac KEY Algo Stat Hist Srvc Alrm SET Quick Access ChartOmnizone Page SETPT01 OMNIZONESETPT02 Controller Set PointsController Hardware Points Configuration ParametersSoftware Points Operation Page Page RUN VFD Non-Trip Messages for 50XJ Unit Keys and Functions for 50XJ VFDVFD Trip Messages for 50XJ Unit KEY Operaton LED Message Explanation VFD Mode Summary for 50XJ UnitDown 50BV VFD Display Trip Messages for 50BV VFD Non-Trip Messages for the 50BV VFDOL2 OL1Epho EPH1Error Communication Problem Possible Causes Remedies Code Forcing an Input or Output Run Test TroubleshootingClearing a Forced Input or Output Alarms Displayed at Unit LID Comp Volts Range Compressor MUX Board VoltagesUnit Wiring 50BVJ,K Low Voltage Schematic50BVJ,K High Voltage Schematic TRANS-3 24VAC BLU 50BVW,X Low Voltage Schematic50BVW,X High Voltage Schematic PCB2 J1 50BVJ,K,W,X Field-Installed Low Voltage Schematic3 4 5 6 7 50BVJ,K Field-Installed Low Voltage SchemticField Wiring 50BVW,X Field-installed Low Voltage SchematicAqua RoccSPT BpssLOW Voltage Control Wiring 50XJ Low Voltage Control WiringBLK VIO Switch Settings 50XJ 115V Control WiringPower Wiring 50XJ Power WiringPCB3 50BV,XJ Accessory Control Module PCB3 SchematicCdwfs HeatHRN IFMDescription Value Units Status Force Name Rsetrto NumcmpCdwf 0=NO,1=YES Cdfwswt Econ 0=NO,1=YES Ewtsns EwtrstDescription Value Units Name SETPT09 PntnameSENSDI00 SETPT00High Conversion Endpoint 309.77 Comparison Point OMNIZONEDSALM02 Phase Protection Monitored Input Point OMNIZONEDSALM05 Fire alarm Monitored Input Point OMNIZONEDSALM08 Compressor 1 Alarm Monitored Input Point DISCRO00 LINK09 OMNIZONEINTLK02 Ok to Cool Discrete Output Point SETPT03 VOLTI00NTFC00 HCVAV01OMNIZONELMALM02 Entering WaterTemp Monitored Input Point DOW2 DOW1DOW3 DOW4Maintenance Screens Ccvvrf FalseADAPT03 LMALM03ADAPT01 ADAPT02Eeprom RAMDodxrf Description Value Units Status Force Name CCVAV01 ANCTL01Resched Taskstat LMALM02Tasktimr Exetime

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.