Carrier 50XJ064-104 Keys and Functions for 50XJ VFD, VFD Non-Trip Messages for 50XJ Unit

Page 20

STATUS MONITOR MODE — In Status Monitor mode, it is possible to monitor the VFD status (frequency command, output voltage, current, terminal information, etc.). Status monitor mode is entered by pressing the Setup/Program/Monitor key, then selecting MON at the mode selection menu and pressing the Read/Write key. Table 11 details the procedure for entering status monitor mode (from standard monitor mode) and viewing all the monitored status variables. The present output frequency (which, just after power is applied, is 0.0) is displayed. (If the ST- CC terminals are not shorted, OFF will be displayed).

If either or is pressed continuously, every 0.5 sec

the next/previous item will be displayed. As optional points, RUN, STOP, displaying the frequency status, and switching to local/remote and manual/auto modes can be performed.

MANUAL MODE — To override the automatic unit controls and manually operate the fan from the VFD display, press keys for “MANUAL” run mode, “LOCAL” speed control, and press the Up or Down arrow keys to increase or decrease output frequency.

 

 

 

 

 

 

 

 

Table 11 — Keys and Functions for 50XJ VFD

 

 

 

 

 

 

 

 

 

 

 

 

KEY

FUNCTION

 

 

 

 

 

 

 

 

Local/Remote Key

 

LOCAL/REMOTE

 

 

 

Switches the source of frequency command information from panel/terminal

 

 

SPEED CTRL

 

 

 

 

block. The appropriate LED is lit to indicate local or remote frequency command.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual/Auto Key

 

MANUAL/AUTO

 

 

 

Switches the source of run/stop command information from panel/terminal block.

 

 

RUN MODE

 

 

 

 

The appropriate LED is lit to indicate manual or auto run/stop command.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETUP

 

Setup/Program/Monitor Key

 

 

 

PROGRAM

 

Toggles between Setup, Program, Monitor, and Frequency Mode.

 

 

 

MONITOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Read/Write Key

 

 

 

READ

 

 

 

 

 

 

Mode, group, parameter, data, and frequency selection key. This key is used to

 

 

 

 

 

 

 

 

 

 

 

WRITE

 

 

 

 

 

 

select or enter a parameter value, a frequency command, or a group name.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up Key

 

 

 

 

 

 

 

 

Scrolls up the setting of the currently displayed parameter. If the key is held

 

 

 

 

 

 

 

 

down, the scrolling speed gradually increases. Only RAM values are changed.

 

 

 

 

 

 

 

 

Also toggles to other function group entries. Pushing Read/Write key saves the setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Down Key

 

 

 

 

 

 

 

 

Scrolls down the setting of the currently displayed parameter. If the key is held

 

 

 

 

 

 

 

 

down, the scrolling speed gradually increases. Only RAM values are changed.

 

 

 

 

 

 

 

 

Also toggles to other function group entries. Pushing Read/Write key saves the setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

Run Key

 

 

 

RUN

 

 

 

 

 

 

 

 

 

This key is used to start a RUN command (only valid when in manual control mode).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop/Reset Key

 

 

 

STOP

 

Functions as the STOP key and emergency stop key during local operation.

 

 

 

RESET

 

 

Functions as the RESET key when an inverter trip occurs. In all other modes,

 

 

 

 

 

 

 

 

emergency off is engaged when this key is pressed twice.

 

 

 

 

 

 

 

 

 

Table 12 — VFD Non-Trip Messages for 50XJ Unit

 

 

LED MESSAGE

EXPLANATION

OFF

Displayed whenever the ST-CC connection is open.

pOFF

Displayed when the VFD control power supply voltage is too low.

nOFF

Displayed when the VFD’s main DC bus voltage is low.

rtrY

Auto-restart message: alternately displayed with the output frequency whenever the

 

VFD tries to automatically restart after a non-critical trip.

Err1

Displayed when 2 frequency points (F-P1,F-P2,etc.) are set too close to each other.

CLr

Displayed during a pending clear command (after the STOP/RESET key has been

 

pressed ONCE after a trip).

EOFF

Displayed during a pending emergency off command (after the STOP/RESET key has

 

been pressed ONCE when in terminal control mode).

CtrL

Displayed during a pending coast stop command (after the Local/Remote key has

 

been pressed once when in local control mode while the VFD is running).

HI

This maximum value warning message “HI” will be alternately displayed in the data

 

field of a parameter when an attempt is made to increase the setting value greater than

 

the parameter’s maximum value.

LO

This minimum value warning message “LO” will be alternately displayed in the data

 

field of a parameter when an attempt is made to decrease the setting value less than

 

the parameter’s minimum value.

PASS

Displayed if the correct password is entered at the password prompt.

Err

Displayed if an incorrect password is entered at the password prompt.

E1

Displayed when the VFD attempts to display a number that exceeds four

 

numerical digits.

db

Displayed when DC injection braking is being executed.

dbon

Displayed when motor shaft stationary control is being executed.

FJOG

Displayed when in forward JOG mode.

rJOG

Displayed when in reverse JOG mode.

L

VFD/motor overload pre-alarm display.

C

Overcurrent pre-alarm display.

P

Overvoltage pre-alarm display.

H

Overheat pre-alarm display.

t

Option board communication alarm display.

InIt

Displayed when the VFD is initializing values during resetting/power-up.

20

Image 20
Contents Controls Operation Troubleshooting Page Control Inputs and Outputs SW2 SW3 SW1Communication Cable Recommendations Manufacturer Part NumberWhen the unit is off, both valves are closed Field Terminal Blocks for 50XJ Unit Space Temperature Sensor Typical Wiring 33ZCT55SPT LID Function Keys Operative KeysNumeric Keys Operative USE KeysOmnizone Vpac Quick Access Chart KEY Algo Stat Hist Srvc Alrm SETOmnizone Page SETPT01 Controller Set Points OMNIZONESETPT02Software Points Configuration ParametersController Hardware Points Operation Page Page RUN Keys and Functions for 50XJ VFD VFD Non-Trip Messages for 50XJ UnitVFD Trip Messages for 50XJ Unit Down VFD Mode Summary for 50XJ UnitKEY Operaton LED Message Explanation 50BV VFD Display Non-Trip Messages for the 50BV VFD Trip Messages for 50BV VFDOL1 OL2Epho EPH1Error Communication Problem Possible Causes Remedies Code Clearing a Forced Input or Output Run Test TroubleshootingForcing an Input or Output Alarms Displayed at Unit LID Compressor MUX Board Voltages Comp Volts Range50BVJ,K Low Voltage Schematic Unit Wiring50BVJ,K High Voltage Schematic 50BVW,X Low Voltage Schematic TRANS-3 24VAC BLU50BVW,X High Voltage Schematic 50BVJ,K,W,X Field-Installed Low Voltage Schematic PCB2 J150BVJ,K Field-Installed Low Voltage Schemtic 3 4 5 6 750BVW,X Field-installed Low Voltage Schematic Field WiringRocc AquaSPT Bpss50XJ Low Voltage Control Wiring LOW Voltage Control Wiring50XJ 115V Control Wiring BLK VIO Switch Settings50XJ Power Wiring Power Wiring50BV,XJ Accessory Control Module PCB3 Schematic PCB3Heat CdwfsHRN IFMDescription Value Units Status Force Name Numcmp RsetrtoCdwf 0=NO,1=YES Cdfwswt Econ 0=NO,1=YES Ewtsns EwtrstDescription Value Units Name Pntname SETPT09SENSDI00 SETPT00High Conversion Endpoint 309.77 Comparison Point OMNIZONEDSALM02 Phase Protection Monitored Input Point OMNIZONEDSALM05 Fire alarm Monitored Input Point OMNIZONEDSALM08 Compressor 1 Alarm Monitored Input Point DISCRO00 LINK09 OMNIZONEINTLK02 Ok to Cool Discrete Output Point VOLTI00 SETPT03NTFC00 HCVAV01OMNIZONELMALM02 Entering WaterTemp Monitored Input Point DOW1 DOW2DOW3 DOW4Maintenance Screens False CcvvrfADAPT03 LMALM03ADAPT02 ADAPT01Eeprom RAMDodxrf Description Value Units Status Force Name ANCTL01 CCVAV01LMALM02 Resched TaskstatTasktimr Exetime

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.