Carrier 50XJ064-104 specifications OMNIZONEDSALM05 Fire alarm Monitored Input Point

Page 50

Configuration Screens (cont)

DESCRIPTION

VALUE*

UNITS

NAME

OMNIZONE::DSALM05: Fire alarm

 

 

 

Monitored Input Point

FSD

 

Name

Comparison Point

SENSDI00

 

Name

Alarm Inhibit Point

SENSDI00

 

Name

Discrete Check

 

 

 

Alarm Logic

Invert

 

AlmLogic

Enable Delay Time

10

sec

DlyTim

Persistence Time

10

sec

Persist

Alarm Processor

 

 

 

Alarm Processing

Enable

 

AlmProc

Re-Alarm Interval

0

min

ReAlmTim

Alarm=1 or Alert=0

1

 

Type

Alarm Level

0

 

AlmLevel

Alarm Source

5

 

AlmSrc

Alarm Routing

11010000

 

AlmRtg

Alarm Description Index

0

 

AlmDesc

Alarm Message - Part 1

Fire Shutdown

 

Message

Alarm Message - Part 2

 

 

Message

Alarm Message - Part 3

 

 

Message

Alarm Message - Part 4

 

 

Message

Power on Delay

0

sec

PowerUp

OMNIZONE::DSALM06: Condenser Water Flow

 

 

 

Monitored Input Point

CDWF

 

Name

Comparison Point

COOLOK

 

Name

Alarm Inhibit Point

CDWF_ST

 

Name

Discrete Check

 

 

 

Alarm Logic

Normal

 

AlmLogic

Enable Delay Time

120

sec

DlyTim

Persistence Time

120

sec

Persist

Alarm Processor

 

 

 

Alarm Processing

Enable

 

AlmProc

Re-Alarm Interval

0

min

ReAlmTim

Alarm=1 or Alert=0

1

 

Type

Alarm Level

2

 

AlmLevel

Alarm Source

5

 

AlmSrc

Alarm Routing

11010000

 

AlmRtg

Alarm Description Index

0

 

AlmDesc

Alarm Message - Part 1

Check Condenser

 

Message

Alarm Message - Part 2

Water Flow

 

Message

Alarm Message - Part 3

 

 

Message

Alarm Message - Part 4

 

 

Message

Power on Delay

0

sec

PowerUp

OMNIZONE::DSALM07: Filter Alarm

 

 

 

Monitored Input Point

FLTS

 

Name

Comparison Point

SENSDI00

 

Name

Alarm Inhibit Point

SENSDI00

 

Name

Discrete Check

 

 

 

Alarm Logic

Normal

 

AlmLogic

Enable Delay Time

10

sec

DlyTim

Persistence Time

20

sec

Persist

Alarm Processor

 

 

 

Alarm Processing

Enable

 

AlmProc

Re-Alarm Interval

0

min

ReAlmTim

Alarm=1 or Alert=0

1

 

Type

Alarm Level

2

 

AlmLevel

Alarm Source

5

 

AlmSrc

Alarm Routing

11010000

 

AlmRtg

Alarm Description Index

0

 

AlmDesc

Alarm Message - Part 1

Change Filters

 

Message

Alarm Message - Part 2

 

 

Message

Alarm Message - Part 3

 

 

Message

Alarm Message - Part 4

 

 

Message

Power on Delay

0

sec

PowerUp

*Default values from factory.

NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.

50

Image 50
Contents Controls Operation Troubleshooting Page Control Inputs and Outputs SW2 SW3 SW1Communication Cable Recommendations Manufacturer Part NumberWhen the unit is off, both valves are closed Field Terminal Blocks for 50XJ Unit Space Temperature Sensor Typical Wiring 33ZCT55SPT Numeric Keys LID Function KeysOperative Keys Operative USE KeysOmnizone Vpac Quick Access Chart KEY Algo Stat Hist Srvc Alrm SETOmnizone Page SETPT01 Controller Set Points OMNIZONESETPT02Software Points Configuration ParametersController Hardware Points Operation Page Page RUN Keys and Functions for 50XJ VFD VFD Non-Trip Messages for 50XJ UnitVFD Trip Messages for 50XJ Unit Down VFD Mode Summary for 50XJ UnitKEY Operaton LED Message Explanation 50BV VFD Display Non-Trip Messages for the 50BV VFD Trip Messages for 50BV VFDEpho OL1OL2 EPH1Error Communication Problem Possible Causes Remedies Code Clearing a Forced Input or Output Run Test TroubleshootingForcing an Input or Output Alarms Displayed at Unit LID Compressor MUX Board Voltages Comp Volts Range50BVJ,K Low Voltage Schematic Unit Wiring50BVJ,K High Voltage Schematic 50BVW,X Low Voltage Schematic TRANS-3 24VAC BLU50BVW,X High Voltage Schematic 50BVJ,K,W,X Field-Installed Low Voltage Schematic PCB2 J150BVJ,K Field-Installed Low Voltage Schemtic 3 4 5 6 750BVW,X Field-installed Low Voltage Schematic Field WiringSPT RoccAqua Bpss50XJ Low Voltage Control Wiring LOW Voltage Control Wiring50XJ 115V Control Wiring BLK VIO Switch Settings50XJ Power Wiring Power Wiring50BV,XJ Accessory Control Module PCB3 Schematic PCB3HRN HeatCdwfs IFMDescription Value Units Status Force Name Cdwf 0=NO,1=YES Cdfwswt Econ 0=NO,1=YES Ewtsns NumcmpRsetrto EwtrstDescription Value Units Name SENSDI00 PntnameSETPT09 SETPT00High Conversion Endpoint 309.77 Comparison Point OMNIZONEDSALM02 Phase Protection Monitored Input Point OMNIZONEDSALM05 Fire alarm Monitored Input Point OMNIZONEDSALM08 Compressor 1 Alarm Monitored Input Point DISCRO00 LINK09 OMNIZONEINTLK02 Ok to Cool Discrete Output Point NTFC00 VOLTI00SETPT03 HCVAV01OMNIZONELMALM02 Entering WaterTemp Monitored Input Point DOW3 DOW1DOW2 DOW4Maintenance Screens ADAPT03 FalseCcvvrf LMALM03Eeprom ADAPT02ADAPT01 RAMDodxrf Description Value Units Status Force Name ANCTL01 CCVAV01Tasktimr LMALM02Resched Taskstat Exetime

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.