Carrier 50XJ064-104 specifications Controller Set Points, OMNIZONESETPT02

Page 14

Table 7 — Controller Set Points

 

DESCRIPTION

 

 

 

 

 

 

DISPLAY

VALUE

UNITS

STATUS

FORCE

NAME

 

SCREENS

 

 

 

 

 

OMNIZONE::SETPT01:

 

 

 

 

 

Supply fan Status

 

 

 

 

 

Occupied Lo Setpoint

0.3

in H2O

 

 

OccLow

Occupied Hi Setpoint

0.4

in H2O

 

 

OccHgh

Unoccupied Lo Setpoint

0.3

in H2O

 

 

UnOccLow

Unoccupied Hi Setpoint

0.4

in H2O

 

 

UnOccHgh

OMNIZONE::SETPT02:

 

 

 

 

 

VAVRESETbaseline

 

 

 

 

 

Occupied Lo Setpoint

0

dF

 

 

OccLow

Occupied Hi Setpoint

0

dF

 

 

OccHgh

Unoccupied Lo Setpoint

0

dF

 

 

UnOccLow

Unoccupied Hi Setpoint

0

dF

 

 

UnOccHgh

OMNIZONE::SETPT03:

 

 

 

 

 

Heat\Cool Mode & Reset

 

 

 

 

 

Occupied Lo Setpoint

70

dF

 

 

OccLow

Occupied Hi Setpoint

74

dF

 

 

OccHgh

Unoccupied Lo Setpoint

55

dF

 

 

UnOccLow

Unoccupied Hi Setpoint

85

dF

 

 

UnOccHgh

OMNIZONE::SETPT04:

 

 

 

 

 

Head Pressure Control

 

 

 

 

 

Occupied Lo Setpoint

225

PSIG

 

 

OccLow

Occupied Hi Setpoint

225

PSIG

 

 

OccHgh

Unoccupied Lo Setpoint

225

PSIG

 

 

UnOccLow

Unoccupied Hi Setpoint

225

PSIG

 

 

UnOccHgh

OMNIZONE::SETPT05:

 

 

 

 

 

Supply Static Pressure

 

 

 

 

 

Occupied Lo Setpoint

1.5

in H2O

 

 

OccLow

Occupied Hi Setpoint

1.5

in H2O

 

 

OccHgh

Unoccupied Lo Setpoint

1.5

in H2O

 

 

UnOccLow

Unoccupied Hi Setpoint

1.5

in H2O

 

 

UnOccHgh

OMNIZONE::SETPT06:

 

 

 

 

 

Supply Air Temperature

 

 

 

 

 

Occupied Lo Setpoint

55

dF

 

 

OccLow

Occupied Hi Setpoint

55

dF

 

 

OccHgh

Unoccupied Lo Setpoint

55

dF

 

 

UnOccLow

Unoccupied Hi Setpoint

55

dF

 

 

UnOccHgh

OMNIZONE::SETPT07:

 

 

 

 

 

Building Static Pressure

 

 

 

 

 

Occupied Lo Setpoint

0.02

in H2O

 

 

OccLow

Occupied Hi Setpoint

0.02

in H2O

 

 

OccHgh

Unoccupied Lo Setpoint

0.02

in H2O

 

 

UnOccLow

Unoccupied Hi Setpoint

0.02

in H2O

 

 

UnOccHgh

OMNIZONE::SETPT08:

 

 

 

 

 

BSP raw control

 

 

 

 

 

Occupied Lo Setpoint

12.32

ma

 

 

OccLow

Occupied Hi Setpoint

12.32

ma

 

 

OccHgh

Unoccupied Lo Setpoint

12.32

ma

 

 

UnOccLow

Unoccupied Hi Setpoint

12.32

ma

 

 

UnOccHgh

OMNIZONE::SETPT09:

 

 

 

 

 

Humidity Control

 

 

 

 

 

Occupied Lo Setpoint

0

%RH

 

 

OccLow

Occupied Hi Setpoint

99

%RH

 

 

OccHgh

Unoccupied Lo Setpoint

0

%RH

 

 

UnOccLow

Unoccupied Hi Setpoint

99

%RH

 

 

UnOccHgh

 

LEGEND

 

 

 

 

 

BSP

Building Static Pressure

 

 

 

 

RH

Relative Humidity

 

 

 

 

Check System Parameters — To check system parameters, press the STAT button. The LID display will show: “Hardware Points Table 1.” Press ENTER to view the hardware points. The user can navigate up and down through the points with the up and down arrows.

Press 2 and STAT to display the software points. The user can navigate up and down through the points with the up and down arrows.

Refer to Tables 8 and 9 for hardware and software points.

Display Alarm History — If the controller is indicating there are alarms, the user can view the alarm history by

pressing the HIST button. The LID display will show “Alarm

History.” Press ENTER . The LID display will show the date

and type of alarm.

As an example, if the LID display shows: ALARM — 10:55 11-27-02

SFS

That display indicates that on 11/27/02 at 10:55 A.M. the system Supply Fan was either on when it had not been commanded on or was off when it was commanded on.

The user can view other stored alarms by pressing the up and down arrows. The twenty-four most recent alarms are stored.

Configure Custom Programming Selections —

To configure the custom programming selections, perform the following procedure:

1.Press 37 ALGO . The LID display will show: Custom Program

2.Press ENTER . The LID display will show: 2.0 Global Dictionary

OMNIZONE

3.Press ENTER . The display indicates “No Data.” Press CLEAR then press EXPN/EDIT . Press ENTER again. The LID display should now show:

Compressor Stages 4.00

4.Press 4 and then ENTER to indicate that 4 compressors are installed.

5.Use the down and up arrows to select the other configura- tion parameters as required. See Table 10 for a list of con- figuration parameters.

6.A field-supplied 0 to 10 vdc signal to the 50XJ unit may be used to reset the supply-air temperature.

The reset will be taken off the supply air set point configured in the controller. The reset range can be changed by adjusting the High Conversion Endpoint value of the custom voltage input to a value other than 20. For example for 10 degrees of reset change the Hi input value to 10. This may be found by pressing 7 STAT from the Keypad. RESET will be the second custom voltage input point in the controller. The first will be CSMUX, which is the compressor status multi-

plexed input. Press to see the following in the LID display:

Ext. Supply Air Reset

RESET

Press ENTER . If the LID display shows:

System Value

Press EXPN/EDIT . The LID display will show:

Low Input Endpoint 2.0 Volts

Press three times to get to the High Conversion Endpoint. The user must be logged in to be able to change this otherwise you can only view it. See the start up section for how to log into the controller.

Configuration parameters are shown in Table 10.

14

Image 14
Contents Controls Operation Troubleshooting Page Control Inputs and Outputs SW2 SW3 SW1Communication Cable Recommendations Manufacturer Part NumberWhen the unit is off, both valves are closed Field Terminal Blocks for 50XJ Unit Space Temperature Sensor Typical Wiring 33ZCT55SPT Numeric Keys LID Function KeysOperative Keys Operative USE KeysOmnizone Vpac Quick Access Chart KEY Algo Stat Hist Srvc Alrm SETOmnizone Page SETPT01 Controller Set Points OMNIZONESETPT02Software Points Configuration ParametersController Hardware Points Operation Page Page RUN Keys and Functions for 50XJ VFD VFD Non-Trip Messages for 50XJ UnitVFD Trip Messages for 50XJ Unit Down VFD Mode Summary for 50XJ UnitKEY Operaton LED Message Explanation 50BV VFD Display Non-Trip Messages for the 50BV VFD Trip Messages for 50BV VFDEpho OL1OL2 EPH1Error Communication Problem Possible Causes Remedies Code Clearing a Forced Input or Output Run Test TroubleshootingForcing an Input or Output Alarms Displayed at Unit LID Compressor MUX Board Voltages Comp Volts Range50BVJ,K Low Voltage Schematic Unit Wiring50BVJ,K High Voltage Schematic 50BVW,X Low Voltage Schematic TRANS-3 24VAC BLU50BVW,X High Voltage Schematic 50BVJ,K,W,X Field-Installed Low Voltage Schematic PCB2 J150BVJ,K Field-Installed Low Voltage Schemtic 3 4 5 6 750BVW,X Field-installed Low Voltage Schematic Field WiringSPT RoccAqua Bpss50XJ Low Voltage Control Wiring LOW Voltage Control Wiring50XJ 115V Control Wiring BLK VIO Switch Settings50XJ Power Wiring Power Wiring50BV,XJ Accessory Control Module PCB3 Schematic PCB3HRN HeatCdwfs IFMDescription Value Units Status Force Name Cdwf 0=NO,1=YES Cdfwswt Econ 0=NO,1=YES Ewtsns NumcmpRsetrto EwtrstDescription Value Units Name SENSDI00 PntnameSETPT09 SETPT00High Conversion Endpoint 309.77 Comparison Point OMNIZONEDSALM02 Phase Protection Monitored Input Point OMNIZONEDSALM05 Fire alarm Monitored Input Point OMNIZONEDSALM08 Compressor 1 Alarm Monitored Input Point DISCRO00 LINK09 OMNIZONEINTLK02 Ok to Cool Discrete Output Point NTFC00 VOLTI00SETPT03 HCVAV01OMNIZONELMALM02 Entering WaterTemp Monitored Input Point DOW3 DOW1DOW2 DOW4Maintenance Screens ADAPT03 FalseCcvvrf LMALM03Eeprom ADAPT02ADAPT01 RAMDodxrf Description Value Units Status Force Name ANCTL01 CCVAV01Tasktimr LMALM02Resched Taskstat Exetime

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.