Carrier Understanding csmux and Its Configuration for Air Conditioners

Page 12

22.The control forces CMP4 (compressor 4) on, if config- ured, then waits 5 seconds.

The LID display shows: Factory/Field Test Stop

The yellow LED will go off, and the red LED will go off.

23.The control forces CMP4 off.

24.The run test is complete.

Power Up the LID Display — After completing the automatic run test, perform the following procedures to change the controller password, set the controller clock, configure schedules, set parameters, view settings, and view alarm history.

1.Set the Remote/Local/Off switch on the front of the unit to the OFF position. This prevents operation of the fan and compressors while still providing power to the unit controls.

NOTE: When the switch is in the OFF position, the red alarm LED will be lit; this is normal. The bypass point will also indicate OK.

2.If the unit access panel (for power and controls) is still on the unit, remove it in order to view the control modules during start-up.

3.Switch the main unit power disconnect to ON.

When power is applied to the OMNIZONE™ System Control panel, the red LED on the top front of the processor module will flash at a rapid pace (about twice a second) for the first 30 to 60 seconds. This rapid flash will then be replaced by a slower paced flash (about once per second).

The green LED below the red LED will start flashing. This LED indicates input/output communications for accessory input output modules and the LID display.

The yellow LED will flash when the controller is broadcast- ing CCN messages to a laptop or other computer.

The third LED from the bottom of the controller (PCB1) will light.

The LID display will show the controller identification, time and date as shown below.

OMNIZONE VPAC hh:mm mm-dd-yy

Log On to the LID Display — To Log On to the LID display, perform the following procedure:

1.Press 3 and then SET . The LID display will show: Controller Password

2.Press ENTER . The LID display will show: Log in to Controller

Enter Password

NOTE: The LID display has two modes: Edit mode and Status/Maintenance mode. Edit mode allows the user to change settings on the configurations screens. Status/ Maintenance mode only allows the user to look at the settings.

If the LID display is in Edit mode, then the display will only show the word “password.” Press the EXPN/EDIT key to toggle to the Status mode. Make sure the LID display shows:

Log in to Controller Enter Password

3.Key in the password and press ENTER . NOTE: The default password is 1111.

4.The LID display will show: Log in to Controller Logged In

NOTE: The user will be automatically logged off after 15 min. of non-use.

Change the Default Password — To change the default password, perform the following procedure:

NOTE: The password must have already been entered to perform this procedure.

1.Press 3 and then SET . The LID display will show: Controller Password

2.Press ENTER . The LID display will show: Log in to Controller

Logged in

3.Press EXPN/EDIT . The LID display will show: Password

1111 (default password, or previous password entered)

4.Enter the new password (up to 6 digits) and press ENTER . The LID display will show:

Password

(password just entered)

NOTE: Remember this password; write it down.

5.Press CLEAR twice to leave the password screen and re- turn to the default display screen.

Set the Clock — The user must be logged in to set the clock. To set the clock, perform the following procedure:

1.Press 1 and then SET . The LID display will show: Set Clock

2.Press ENTER . The LID display will show: No Maintenance

NOTE: There is no maintenance information regarding setting the clock.

3.Press EXPN/EDIT . The LID display will show: Time

00:00

4.Enter the time. The time is entered in military time (for example 14.59 for 2.59 pm). Press ENTER then press

the button. The LID display will show: Day of Week

1

5.Enter the day of week. The numbers 1 through 7 corre- spond to the days of the week (1 = MON, 2 = TUE,

3 = WED, 4 = THUR, 5 = FRI, 6 = SAT, 7 = SUN). Press

ENTER then press . The LID display will show: Month

1

6.Enter the number of the corresponding month (1 through

12). Press ENTER then press . The LID display will show:

Day 1

7. Enter the day of the month. Press ENTER then press

. The LID display will show: Year

95

12

Image 12
Contents Controls Operation Troubleshooting Page Control Inputs and Outputs SW2 SW3 SW1Communication Cable Recommendations Manufacturer Part NumberWhen the unit is off, both valves are closed Field Terminal Blocks for 50XJ Unit Space Temperature Sensor Typical Wiring 33ZCT55SPT LID Function Keys Operative KeysNumeric Keys Operative USE KeysOmnizone Vpac Quick Access Chart KEY Algo Stat Hist Srvc Alrm SETOmnizone Page SETPT01 Controller Set Points OMNIZONESETPT02Configuration Parameters Controller Hardware PointsSoftware Points Operation Page Page RUN Keys and Functions for 50XJ VFD VFD Non-Trip Messages for 50XJ UnitVFD Trip Messages for 50XJ Unit VFD Mode Summary for 50XJ Unit KEY Operaton LED Message ExplanationDown 50BV VFD Display Non-Trip Messages for the 50BV VFD Trip Messages for 50BV VFDOL1 OL2Epho EPH1Error Communication Problem Possible Causes Remedies Code Run Test Troubleshooting Forcing an Input or OutputClearing a Forced Input or Output Alarms Displayed at Unit LID Compressor MUX Board Voltages Comp Volts Range50BVJ,K Low Voltage Schematic Unit Wiring50BVJ,K High Voltage Schematic 50BVW,X Low Voltage Schematic TRANS-3 24VAC BLU50BVW,X High Voltage Schematic 50BVJ,K,W,X Field-Installed Low Voltage Schematic PCB2 J150BVJ,K Field-Installed Low Voltage Schemtic 3 4 5 6 750BVW,X Field-installed Low Voltage Schematic Field WiringRocc AquaSPT Bpss50XJ Low Voltage Control Wiring LOW Voltage Control Wiring50XJ 115V Control Wiring BLK VIO Switch Settings50XJ Power Wiring Power Wiring50BV,XJ Accessory Control Module PCB3 Schematic PCB3Heat CdwfsHRN IFMDescription Value Units Status Force Name Numcmp RsetrtoCdwf 0=NO,1=YES Cdfwswt Econ 0=NO,1=YES Ewtsns EwtrstDescription Value Units Name Pntname SETPT09SENSDI00 SETPT00High Conversion Endpoint 309.77 Comparison Point OMNIZONEDSALM02 Phase Protection Monitored Input Point OMNIZONEDSALM05 Fire alarm Monitored Input Point OMNIZONEDSALM08 Compressor 1 Alarm Monitored Input Point DISCRO00 LINK09 OMNIZONEINTLK02 Ok to Cool Discrete Output Point VOLTI00 SETPT03NTFC00 HCVAV01OMNIZONELMALM02 Entering WaterTemp Monitored Input Point DOW1 DOW2DOW3 DOW4Maintenance Screens False CcvvrfADAPT03 LMALM03ADAPT02 ADAPT01Eeprom RAMDodxrf Description Value Units Status Force Name ANCTL01 CCVAV01LMALM02 Resched TaskstatTasktimr Exetime

50XJ064-104 specifications

The Carrier 50XJ064-104 is a high-efficiency rooftop air conditioning system designed to deliver exceptional cooling and heating capabilities for diverse commercial applications. One of the standout features of this model is its robust cooling capacity of 64,000 BTUs, making it suitable for mid to large-sized spaces. The 50XJ064-104 is engineered using advanced technologies to ensure energy efficiency and reliable performance, contributing to reduced operational costs and environmental sustainability.

One of the primary technologies employed in the Carrier 50XJ064-104 is the high-efficiency scroll compressor. This component plays a pivotal role in optimizing energy usage while delivering consistent cooling output. The system also incorporates an economizer that allows for enhanced energy savings by utilizing outdoor air for cooling when conditions are favorable. This not only decreases reliance on the compressor but also improves indoor air quality.

The microprocessor-based controls in the 50XJ064-104 provide precise temperature regulation, ensuring optimal comfort levels in various applications. These controls allow for easy programming and can be integrated into building management systems for centralized oversight. Additionally, the unit features a built-in fault detection and diagnostic system that aids in identifying potential issues before they escalate, minimizing downtime and maintenance costs.

The Carrier 50XJ064-104 is designed with durability in mind. It features a weather-resistant cabinet, designed to withstand harsh outdoor conditions and prolong service life. The high-quality insulation within the unit not only enhances energy efficiency but also minimizes noise levels, making it an ideal choice for urban environments where sound control is critical.

Another important characteristic is its environmentally friendly R-410A refrigerant, which has a lower impact on ozone depletion compared to older refrigerants. This aligns with Carrier's commitment to creating sustainable HVAC solutions that comply with current environmental regulations.

Overall, the Carrier 50XJ064-104 stands out for its combination of efficiency, advanced technologies, and durable construction. Whether for commercial buildings, retail spaces, or industrial applications, this rooftop air conditioning unit is designed to provide reliable performance and comfort year-round.