Chicago Pneumatic CPVS 40, CPVS 60, CPVS 50, CPVS 75 Electric cabling, Voltage, Safety Regulations

Page 9

F - Electric cabling

Each CPVS is wired for a pre-determined voltage, i.e. 460 V.

NEVER OPERATE THE CPVS ON A VOLTAGE OTHER THAN THAT SHOWN ON THE ELECTRIC CABINET.

The electric current supply to the CPVS must comply with the following table :

Type of cable to be used :

Power cable size

(for a maximum 32.8 ft length)

CPVS Model

VOLTAGE

 

460 V

 

 

 

40

AWG4

50

AWG3

60

AGW1

75

AWG0

SAFETY REGULATIONS

It should be remembered that safety regulations require :

An earth socket to be used.

A manual isolating switch, cutting all three phases ; this switch must be clearly visible near the CPVS unit.

The electric current must be cut whenever maintenance work is carried out on the machine (except for pressurized oil change)

 

Fuses to be used for

CPVS Model

the isolating switch (RK5 type)

 

 

460 V

 

 

40

80

50

100

60

125

75

150

 

 

Chicago Pneumatic Compressors

01/2008

62 305 258 65

Page 9

Image 9
Contents Cpvs Model Cpvs 40 50 60Cpvs Model Mini + 36 F frost free Maxi + 104 FPSI NPTMain Voltage 460 Volt / 3 / 60 Hz AWGConnection of the electric plate to an external control box Contents AIR Delivery Power SupplyGeneral Information DescriptionRespect of the environment and prevention of pollution Standard equipmentElectronic board Definition of the pictogramsInstallation Safety Regulations Electric cablingVoltage Parallel compressor assembly Discharge pressure adjustmentSafety Preparation for start-upAir and oil circuits OperationKey fig Air circuits see FigOptions Level detection bleed valve FigAdvanced filtration to the compression air inlet a and 7b Pre-filtration panels Support gridFilter Medium Features Rotation direction indicator Phase controllerAutomatic restarting Remote starting and stoppingDescription of the option Centrifugal separator See B SectionSafety instructions InstallationSafety Rules Description cf SectionCommissioning Setting of pressure machinePreparation for start-up See Section Control of rotation direction on start upPressure regulation for low rates of flow Energy saving Principle of the pressure regulation by variable speedMain incidents Operating incidentsMaintenance Operations to be carried out PartsObservations Air filter Oil level and change see figTurbine OillevelOil and air cooler Temperature safety testsOil separator see B Section Oil return pipe see figSee -E Main incidentsSupport@CPcompressor.com