CPVS Model

40

50

60

75

 

 

 

 

 

 

Motor power

(hp)

40

50

60

75

 

 

 

 

 

 

 

 

Main Voltage 460 Volt / 3 / 60 Hz

 

 

 

 

 

 

 

 

Nominal current

(A)

69

81

89

125

Power supply cable

 

AWG 4

AWG 3

AWG 1

AWG 0

Fuse protection

(Type RK5)

80

100

125

150

 

 

 

 

 

 

 

 

 

 

 

 

Connection of the electric plate to an external control box

Install an RC filter on the KM1 coil.

Install an RC filter on the KM2 coil.

All connections between external parts and the compressor must be carried out using a shielded cable, which must be grounded at one of its ends.

WARNING: the operation connection cables between the different elements must never follow the same path as the existing power cords. A separate installation from the power cords must be carried out.

Install an RC filter on all the relay coils of the external operation units.

Chicago Pneumatic Compressors

01/2008

62 305 258 65

Page 3

Image 3
Contents Cpvs Model Cpvs 40 50 60NPT Mini + 36 F frost free Maxi + 104 FCpvs Model PSIMain Voltage 460 Volt / 3 / 60 Hz AWGConnection of the electric plate to an external control box Contents AIR Delivery Power SupplyStandard equipment DescriptionGeneral Information Respect of the environment and prevention of pollutionElectronic board Definition of the pictogramsInstallation Safety Regulations Electric cablingVoltage Preparation for start-up Discharge pressure adjustmentParallel compressor assembly SafetyAir circuits see Fig OperationAir and oil circuits Key figOptions Level detection bleed valve FigAdvanced filtration to the compression air inlet a and 7b Pre-filtration panels Support gridFilter Medium Remote starting and stopping Rotation direction indicator Phase controllerFeatures Automatic restartingDescription of the option Centrifugal separator See B SectionDescription cf Section InstallationSafety instructions Safety RulesControl of rotation direction on start up Setting of pressure machineCommissioning Preparation for start-up See SectionPressure regulation for low rates of flow Energy saving Principle of the pressure regulation by variable speedMain incidents Operating incidentsMaintenance Operations to be carried out PartsObservations Oillevel Oil level and change see figAir filter TurbineOil return pipe see fig Temperature safety testsOil and air cooler Oil separator see B SectionSee -E Main incidentsSupport@CPcompressor.com