Chapter 8 PROTECTION FUNCTION

8.1 Action selection in case of option error

To ignore or make inverter trip can be selected in case of option error.

Item

Function code

Data

Contents

Action selection in

P001 / P002

00

TRP: Inverter trips and outputs alarm signal.

 

RUN: Inverter ignores the option error and continues

case of option error

01

 

the operation.

 

 

 

(Note) : Inverter trips anyway in case of encoder line break error (E60, E70), SJ-FB abnormal connection (E69,E79) occurs, although action selection is set to 01 (RUN). Please refer to "Chapter 5.2 FEED-BACK BOARD INITIAL SETTINGS".

8.2 Cause and countermeasure of the option error

When any of the following alarms occurs, the inverter displays the alarm cause and stops.

Display

Item

 

Contents

 

Processing

 

 

 

Detect the line break or disconnection of the

Check the encoder signal line and

E60

 

encoder line.

 

 

connection.

 

Encoder line

Detect when there is an encoder failure.

Replace it to a suitable one.

(E70)

break

Detect when the specification of the encoder is

(Note 1)

not line driver output type.

 

 

 

 

 

 

 

 

 

Detect when there is no Z pulse.

 

Turn SWENC-2 OFF on the option

 

 

 

board.

 

 

 

 

 

 

 

 

E61

 

Detect when the motor rotation speed exceeds

Adjust the Kp and J constants related

(E71)

Over speed

(maximum frequency (note 2))×(over speed

to the speed control system to reduce

(Note 1)

 

error detection level (P026).

 

overshoot.

 

 

(Note 3),(Note 4)

 

 

 

 

 

 

 

 

 

E62

Positioning

Detect

when the

deviation of

the current

Increase the position loop gain.

(E72)

position and command value becomes more than

Decrease the numbers

of the pulse

error

(Note 1)

1,000,000 pulses during position controlling.

train input per second.

 

 

 

E69

connection

Detect

abnormal

connection

between the

Check the connection

between the

(E79)

error

inverter main body and SJ-FB.

 

inverter main body and SJ-FB.

(Note 1)

 

 

 

 

 

 

 

 

(Note 1): ( ) shows when the option card is connected to option slot 2.

(Note 2): Frequency upper limit value (A061/A261) is reflected when it is set.

(Note 3): It depends on what type of main body combines with the SJ-FB, the setting value conversion is different.

Please refer to the (Note 3) of the “5.3 Items regarding the feed back board of the inverter main body“.

(Note 4): When the over speed error occurred . There is a possibility the over speed error occur again. Even though the trip is cleared during the motor free run. In this case stop the motor, then clear the trip please.

8.3 Warning display (Feed back option relation)

(Refer to the operation manual of the main body about the warning other than the following,)

The 009 is displayed in the case that it became orientation speed setting (P015) > the highest frequency setting (A004). Please confirm the case, orientation speed setting (P015) and highest frequency setting (A004).

31

Image 31
Contents SJ-FB Feed-Back Board Definitions and Symbols SafetyRevision History Table Page Page Contents Request upon inquiry Inquiry and Warranty of the UnitWarranty of the unit Inspection upon packingOutline of SJ-FB How to Mount the option Board Outlook of SJ-FB Terminal assignment of the Option BoardSAP Function Explanation of the TerminalDSE Terminal connection diagramIf they Feed-back board initial setting Position of the setting switchMotor Setting 21 position of specification Switch setting flowchart Setting flowchart of the switch on the boardOperation Set Motor constant J bigger and bigger H024/H034 Function outline Orientation functionFunctions Data setting related to speed control Data settingWhen the motor is unstable Decrease position loop gain Position control APR Electronic gear function Control mode settingData setting of the input-output terminal Speed control ASRData setting related to position control Wiring for Synchronized OperationPositioning completion Set ‘23’ to one Control block diagram of the electron gear function Forward/Reverse command + pulse train mode Pulse train mode selectionForward pulse train + Reversion pulse train mode Speed control mode is normally controlled by proportional Speed control P/PI switching functionResistor vs. Temperature Curves Cause and countermeasure of the option error Action selection in case of option errorProduct specification