8-3. Optional Generator Power Receptacles

European Receptacle

5

6

Australian Receptacle

5

6

South African Receptacle

5

6

1

2

1

3

1

4

 

 

 

 

 

 

1120 V 20 A AC GFCI Receptacle GFCI1

2240 V 16 A AC European Receptacle RC1

3240 V 15 A AC Australian Receptacle RC1

4240 V 15 A AC South African Receptacle RC1

Receptacles supply 60 Hz single- phase power at weld/power speed.

If a ground fault is detected, the GFCI Reset button pops out and the receptacle does not work. Check for faulty tools plugged in receptacle. Press button to reset GFCI1.

.At least once a month, run en- gine at weld/power speed and press test button to verify GFCI is working properly.

5Circuit Breaker CB2

6Circuit Breaker CB3

CB2 protects GFCI1 from overload. If CB2 opens, GFCI1 does not work. Press button to reset breaker.

CB3 protects RC1 from overload. If CB3 opens, RC1 does not work. Press button to reset breaker.

.If a circuit breaker continues to open, contact Factory Autho- rized Service Agent.

.Generator power is not af- fected by weld output.

Maximum output is 2.4 kVA/kW from GFCI1 and 4 kVA/kW from RC1. Maximum output from all re- ceptacles is 4 kVA/kW.

EXAMPLE: If 13 A is drawn from RC1, only 7 A is available at GFCI1:

(240 V x 13 A) + (120 V x 7 A) = 4.0 kVA/kW

191 624

OM-496 Page 40

Return To Table Of Contents

Image 46
Contents Processes OM-496Description From Miller to You Table of Contents 11-2 11-111-3 Standards DirectivesDeccon1 11/02 Sound Level Information Deccon1 5/98Symbol Usage Arc Welding HazardsEngine Hazards Compressed Air Hazards EMF Information Principal Safety StandardsCalifornia Proposition 65 Warnings Radiation can cause interferenceUN Choc Électrique peut tuer Signification des symboles− Consignes DE Sécurité − Lire Avant Utilisation LES Fumées ET LES GAZ peuvent être dangereuxDES Pièces Chaudes peuvent provoquer des brûlures graves LE Soudage peut provoquer un in- cendie ou une explosionDES Particules Volantes peuvent blesser les yeux LE Bruit peut affecter l’ouïeLA Chaleur DU Moteur peut pro- voquer un incendie ’EXPLOSION DE LA Batterie peutDES Organes Mobiles peuvent provoquer des blessures ’AIR Comprimé peut provoque r des blessuresPrincipales normes de sécurité Information sur les champs électromagnétiques− Definitions + − Starting InstructionsCan cause severe burns. Do Are possible hazards asHot muffler and exhaust pipes EngineReturn To Table Of Contents Std Manufacturer’s Rating Labels For CE Products− 50 h Std CC Models CC/CV ModelsSymbols And Definitions Weld, Power, And Engine Specifications − SpecificationsDimensions, Weights, And Operating Angles Volt-Ampere Curves For CC Models TIG Mode Stick ModeMIG Mode Volt-Ampere Curves For CC/CV ModelsFuel Consumption Duty Cycle And Overheating12 kVA/kW Single-Phase AC Output No Weld Load AC Generator Power CurveOptional Three-Phase Generator Curves 15 kVA/kW Three-Phase AC Output No Weld LoadLocation Grounding − InstallationInstalling Welding Generator See Sections 5-2And Airflow ClearanceUsing Lifting Eye Work like a ProMounting Surface Mounting Welding GeneratorSupporting The Unit To Bolt Unit In PlaceInstalling Exhaust Pipe Stop engine and let coolRead and follow all instruc Activating The Dry Charge Battery If ApplicableWhen electrolyte is low, add ChargerReinstall cover after connecting battery Connecting The BatteryConnect Negative − Cable Last Coolant Recovery Tank Engine Prestart ChecksConnecting To Weld Output Terminals Selecting Weld Cable SizesRef 862-A / 048 720-K / 802 Connecting To Remote 14 Receptacle RC14 On CC/CV Models Socket− Operating Welding Generator − CC Models Front Panel Controls For CC Models See SectionDo not switch under load To Start Do not use ether. Using ether voids warrantyEngine Indicator Lights Engine Starting ControlsExample Combination Remote Amperage Control Stick Remote Amperage Control On CC Models OptionalWeld Control/Arc Condition Information Label Set weld controls as shown toReturn To Table Of Contents − Operating Welding Generator − CC/CV Models Front Panel Controls For CC/CV Models See SectionUse switch to select weld amperage range Voltage/Amperage Adjust Switch And Remote 14 ReceptacleProcess/Contactor Switch On CC/CV Models Process/Contactor Switch SettingsRemote Voltage/Amperage Control On CC/CV Models Optional Example Combination Remote Amperage Control TIGAt least once a month, run en − Operating Auxiliary EquipmentVolt And 240 Volt Receptacles Open, contact Factory AuthoRear Of Panel Three-Phase Power ConnectionClose panel opening if no connections are made to generator 240 V 15 a AC South African Receptacle RC1 Optional Generator Power ReceptaclesCircuit Breaker CB2 Circuit Breaker CB3 Maintenance Labels − Maintenance & TroubleshootingFor Non-CE Products Every 50 h Routine MaintenanceEvery 8 h Every 100 hEvery 2000 h Clean/Set InjectorsEvery 1000 h Change FuelTo clean air filter Servicing Air CleanerBy the warranty Do not clean housing with air hoseInspecting And Cleaning Optional Spark Arrestor Muffler Reinstall cleanout plug Tools NeededDo not set engine speed higher than specified Adjusting Engine Speed On Standard ModelsMaximum Close door Tools Needed 10 mmEngine Speed No Load Idle Speed AdjustmentWeld/Power Speed Adjustment Rpm max 61.6 Hz 1250 rpm 41.6 HzServicing Fuel And Lubrication Systems Overload Protection Correct the cause of the shut Diagnosing Causes Of Engine Fault ShutdownsDiagnostic Checks While Running Down before operatingTroubleshooting Welding − CC ModelsWelding − CC/CV Models Optional Three-Phase Generator Power CC/CV Models Only Standard Generator PowerEngine Temperature is too high see Sections 5-7and Wiring harness and componentsShutdown switch is released Out Air in fuel system. See engine manualReturn To Table Of Contents − Electrical Diagrams Circuit Diagram For CC Welding Generator215 296-B Circuit Diagram For CC/CV Welding Generator 215 297-B Wetstacking − RUN-IN ProcedureMent damage may occur Stop engine Do not touch hot exhaust Run-In Procedure Using Load BankProcedure at less than From flammables Do not PerformFrom flammables Run-In Procedure Using Resistance GridBank/grid Do not perform run-inSelecting Equipment − Generator Power GuidelinesHas this symbol Grounding Generator To Truck Or Trailer FrameEarth ground if supplying Grounding When Supplying Building SystemsHow Much Power Does Equipment Require? Use ground device as stated in electrical codesIndustrial Motors Rating Starting Watts Running Watts Approximate Power Requirements For Industrial MotorsApproximate Power Requirements For Farm/Home Equipment Farm/Home Equipment Rating Starting Watts Running WattsApproximate Power Requirements For Contractor Equipment Contractor Rating Starting Watts Running WattsSingle-Phase Induction Motor Starting Requirements Power Required To Start MotorHow Much Power Can Generator Supply? KVA/HP x HP xTypical Connections To Supply Standby Power Selecting Extension Cord Use Shortest Cord Possible Current Load Watts Amperes− Parts List 109 111 -4 or118 85 FigDia Part Mkgs Description Quantity 209 Figures 13-2 Control Box Assembly − CC Models PLG3 Control Box Assembly − CC/CV Models PC7 195 Panel, Front w/Components − CC Models RC13 032 Panel, Front w/Components − CC/CV Models 41 40Panel, Front w/Components − CC/CV Models -1Item PC4, PC5 189 Generator Generator -1Item602 SCREW, .312−18x .75 hexwhd.66d stl pld slffmg tap−rw 601 Main Rectifier Assembly Page Page Your distributor also gives ServiceSupport Your distributor and/or equipment manufacturer’s Miller Electric Mfg. CoFor assistance in filing or settling claims, contact Transportation Department