Sanyo XMHX1252, XMHX1852, CHDZR09053 Header joint system, Tube branching methods horizontal use

Page 15

Always check the gas density WARNING limit for the room in which the

unit is installed.

1-11. Check of Limit Density

When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room. If the density could exceed the limit level, it is necessary to provide an opening between the unit and the adjacent room, or to install mechanical ventilation which is interlocked with a leak detector.

(Total refrigerant charged amount: oz)

(Min. indoor volume where the indoor unit is installed: ft.3)

<Limit density 0.3 (oz/ft.3)

The limit density of refrigerant which is used in this unit is 0.3 oz/ft.3 (ISO 5149).

The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type, so add it to the amount that is charged in the field. (For the refrigerant charge amount at shipment, refer to the unit’s nameplate.)

1-12. Installing Distribution Joint

Pay special attention to any CAUTION location, such as a basement,

etc., where leaking refrigerant can accumulate, since refrig- erant gas is heavier than air.

(1)Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit (APR-CHRZP900BAB, RZP224BAB, RZP680BAB, RZP1350BAB).

(2)When creating a branch using a commercially available T-joint (header joint system), orient the main tubing so that it is either horizontal (level) or vertical. In order to prevent accumulation of refrigerant oil in stopped units, if the main tubing is horizontal then each branch tubing length should be at an angle that is greater than horizon- tal. If the main tubing is vertical, provide a raised starting portion for each branch.

[Header joint system]

Be sure to solidly weld shut the T-joint end (marked by “X” in the figure). In addition, pay attention to the insertion depth of each connected tube so that the flow of refrigerant within the T-joint is not impeded.

When using the header joint system, do not make fur- ther branches in the tubing.

Do not use the header joint system on the outdoor unit side.

(3)If there are height differences between indoor units or if branch tubing that follows a distribution joint is connect- ed to only 1 unit, a trap or ball valve must be added to that distribution joint. (When adding the ball valve, locate it within 15 - 3/4" of the distribution joint.)

If a trap or ball valve is not added, do not operate the system before repairs to a malfunctioning unit are completed. (The refrigerant oil sent through the

15

tubing to the malfunctioning unit will accumulate and may damage the compressor.)

Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the follow- ing table.

 

ft.3

 

 

 

 

 

 

 

 

 

 

 

 

 

ft.2

 

 

 

10000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1136

 

 

indoorMin.volume

9500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1079

indoorMin.floor area

ceilingthe(whenis 8.8 ft. high)

 

 

 

 

 

the density

limit of

 

 

2000

 

 

 

 

 

 

 

227

 

9000

 

Range below

 

 

 

 

 

 

 

 

 

1022

 

 

 

8500

 

the density limit of

 

 

 

 

 

 

 

966

 

 

 

8000

 

0.3 oz/ft.3

 

 

 

 

 

 

 

 

 

909

 

 

 

7500

 

 

 

 

 

 

 

 

 

 

852

 

 

 

7000

 

(countermeasures

 

 

 

 

 

 

 

795

 

 

 

6500

 

not needed)

 

 

 

 

 

 

 

 

 

738

 

 

 

6000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

682

 

 

 

5500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

 

 

 

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

568

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

511

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

454

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

398

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

 

 

 

 

Range above

 

 

 

 

 

341

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

 

 

 

284

 

 

 

 

 

 

 

 

0.3 oz/ft.3

 

 

 

 

 

 

 

 

1500

 

 

 

 

 

 

 

 

 

 

170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

(countermeasures

 

 

114

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

 

 

needed)

 

 

 

 

 

57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

500

1000

1500

2000

2500

3000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

oz

 

 

Total amount of refrigerant

Tube branching methods (horizontal use)

 

 

 

 

 

B

 

 

A

Horizontal

A

 

B

line

View as seen

 

 

 

 

 

 

 

 

 

from arrow

 

 

Arrow view

 

 

Header joint system (Indoor)

 

 

Install at a

 

 

 

 

 

positive angle

 

 

Outdoor

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

Install at a

Indoor

 

 

 

 

positive angle

 

 

 

 

(15 – 30°)

 

 

 

 

 

Horizontal

 

 

 

 

line

 

 

 

 

 

 

 

Indoor

 

 

 

L3

6.56 ft.

Horizontal

Solidly welded

 

 

line

 

shut (X)

 

 

 

 

Types of vertical trap specifications

(When using ball valve)

 

 

Main tubing

 

 

 

 

Ball valve

Indoor unit (more than 2 units)

(If only 1 unit is connected, a ball valve

(BV: purchased

separately)

is also needed on this side.)

Indoor unit (1)

 

 

 

 

(When not using ball valve)

 

Main tubing

 

Horizontal

 

 

 

 

 

 

 

 

Indoor unit

(Each unit is connected

Branch tubing is

 

to tubing that is either

 

level or is directed

directed upward.

 

 

downward.)

 

More than

 

 

 

 

 

 

7–7/8"

 

 

 

Indoor unit is directed downward

 

 

 

W-3WAY_ECO-i_US.indd 15

2008/02/07 10:55:40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 15
Contents Optional Controllers Sanyo Commercial SolutionsR410A Models Indoor Units Outdoor Units…In an Area with High Winds For safe installation and trouble-free operation, you must…In a Room …In Moist or Uneven LocationsCountermeasures Amount 353 oz Amount 529 ozManifold gauge Vacuum pump Care regarding tubingBe sure to recharge the refrigerant only in liquid form Different tools requiredRefrigerating machine oil differs R22 Compressor specifications are differentSingle-outlet valve Existing tubing cannot be used especially R22Contents Test RUN 8-1. Preparing for Test Run Electrical Wiring 5-1. General Precautions on WiringHOW to Process Tubing AIR PurgingType of Copper Tube and Insulation Material Tools Required for Installation not suppliedAccessories Supplied Outdoor Unit Part nameConcealed Duct For sealing recessed portion of power supply4-Way Air Discharge Semi-Concealed X-Type 1-Way Air Discharge Semi-Concealed4-Way Air Discharge Semi-Concealed XM Type Concealed Duct High-Static PressureCeiling-Mounted Wall-MountedH3 C Tubing Length BTU/h 95.500 153.600 Tubing Size 10 Main Tubing Size LA 11 Main Tubing Size After Distribution LB, LC 12 Outdoor Unit Tubing Connection Size a D15 Refrigerant tubing Existing tubing can be used 17 Refrigerant Charge Amount at Shipment for outdoor unit System Limitations 18 System LimitationsCommon solenoid valve kit Header joint system Tube branching methods horizontal useHeader joint system Indoor Size Part B Part C Part D Part E Part F Part G Part H Inch Tubing size with thermal insulationModel name Cooling capacity after distribution Remarks Suction TubeDischarge Tube Liquid Tube 21 Dimensions for connections of each partOptional Solenoid Valve Kit Precautions on Installation of Solenoid Valve KitTypes and specifications SpecificationsUnit Relay kit Front Installation of Solenoid Valve KitMain tubing Distribution joint tubing R410A additional charging absolutely mustBe done through liquid charging Example Use the same tools for R22 and for R410ARemark Main tubingFront view Ceiling-MountedTypeWall-Mounted Type Indoor UnitOutdoor Unit Without snow- proof ducting Without platform Precautions When Installing in Heavy Snow AreasAir direction Front direction Unit installationCeiling panel Unit Ceiling panelAir direction Placing the Unit Inside the Ceiling Suspending the Indoor UnitInstalling the Drain Piping Start when you short the pin Be careful since the fan willOn the indoor control board Removing the corner cover Installing the Ceiling Panel Attaching the air-intake grille Wiring the Ceiling PanelSpecial Remarks DC Fan Tap Change Procedure Checking After InstallationWhen Removing the Ceiling Panel for Servicing Adjusting the Auto FlapPlacing the Unit Inside the Ceiling Suspending the Indoor UnitFrom the drain pipe outlet Installing the Drain PipingDo not install an air bleeder as This may cause water to sprayChecking the unit position How to Install the Ceiling Panel Main unitBefore Installing the Ceiling Panel Checking the DrainageWiring the Ceiling Panel Installing the Ceiling PanelAdjusting the Auto Flap How to Attach the Corner & Air-Intake GrilleChecking After Installation When Removing the Ceiling Panel for Servicing23-5/8 22-3/64Be sure to use a level gauge Confirm that the unit isLevel. If it is not level, water Leakage may occurInstalling the Drain Piping 3WAYECO-iUS.indd 2008/02/07 Ss12 or 5/32 ss15/32 For fastening Electrical Power Wiring Wiring connectionsWiring M5 ss40Removing the side panel Removing the intake grilleAir leakage If a wireless remote controller is used Installing the side panel and intake grilleInstalling the intake grille Others Check after installationRefrigerant tubing Inspection access27/32 Indoor unit Air outlet duct flangeCeiling. Ensure that the ceiling is strong Enough to support the weight of the unitIt is important that you use extreme care Supporting the indoor unit insideSection directly after the connection port can be raised a Maximum of 19-11/16. Do not raise it any higher than19-11/16, as this could result in water leaks. Fig Increasing the Fan Speed How to read the diagramBe careful since the fan will start when you Short the pin on the indoor control board17-23/32 23-5/8 for checking and servicing the electrical system31/32 Min -31/32 Inspection plug Indoor Fan Performance How to Read the DiagramRefrigerant tubing drain hose position Indoor unit from the ceil Wall and ceiling side opening positionIt is important that you use Extreme care in supportingApprox 63/64 Ceiling Surface Washer Nut Fixture Double nut Field supplyDownward gradient Min /100 Duct for Fresh AirShaping the Tubing Rear coverIng. Also, check any specified How to carry out power supply wiringCheck local electrical codes Regulations before wirInstalling the Rear Panel onto the Wall Selecting and Making a HoleIf the Wall is Wooden Attaching the grille Removing the Grille to Install the Indoor UnitIf the Wall is Brick, Concrete or Similar Removing the grilleLeft or left-rear tubing Installing the Drain HoseDo not supply power to the unit or operate Shaping the Tubing Right-rear tubingKHX2452 KHX0752 / 0952 / 1252Installing the Outdoor Unit Positions where anchor bolts are fastenedTransporting Routing the Tubing Remove the Brackets Used for TransportTubing size mm Outer dia Thickness Prepare the TubingConnect the Tubing Refrigerant tube portWork method Tightening torque for each capUse shielded wiring General Precautions on WiringOutdoor unit Time delay fuse or Circuit capacity Inter-outdoor unit control wiringFor K, A, X, T, U and D Types Wiring System DiagramPower Wiring ControllerXM Type For XM TypeOutdoor unit Indoor unit How to connect wiring to the terminal For stranded wiring Type Important Note When Wiring for Common TypeType XM Type Important Note When Wiring for XM TypeDeburring Connecting the Refrigerant TubingFlaring Procedure with a Flare Tool Use of the Flaring MethodApproximate Tube diameter Tightening torqueTwo tubes arranged together Three tubes arranged togetherFour tubes arranged together Taping the Tubes Finishing the InstallationAir Purging with a Vacuum Pump for Test Run Preparation Leak testManifold gauge Vacuum pump 45 min. or more 90 min. or more EvacuationCharging additional refrigerant Use a cylinder designed for use with R410AFinishing the job Test RUN Test Run Procedure Items to Check Before the Test RunUnit with the unit Address setting of main outdoor unit S007 Unit No. setting Indoor unit setting S004 Rotary switch, redMain Outdoor Unit PCB Setting Outdoor main/sub Auto Address Setting Basic wiring diagram ExampleAutomatic Address Setting from the Outdoor Unit No main unit Settings22-9 Automatic Address Setting no compressor operation Automatic Address Setting from Outdoor Unit3 OFF Automatic Address Setting in Heating Mode Automatic Address Setting* from the Remote Controller Automatic Address Setting in Cooling ModeDisplay during automatic address setting LED 2Blink alternately If 1 indoor unit is connected to 1 remote controller Remote Controller Test Run SettingsChecking the indoor unit addresses LED Possible cause of malfunctionMessage Alarm messages displayed on system controller Way Air Discharge Semi-Concealed Type X, XM Types Should the power fail while the unit is running Tips for Energy SavingSoot Way air discharge semi-concealed type a Type 1-WAY100 Troubleshooting101 Concealed Duct High-Static Pressure Type U, D TypesType standard static pressure Type high static pressure102 On the wired remote control unit103 CEILING-MOUNTED104 Or soot105 106 Tips for Energy Saving