Sanyo XMHX1252, XMHX1852, CHDZR09053, CHDZR14053, 85464369098000 installation instructions For XM Type

Page 70

For XM Type

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

*

(No. 1)

 

 

 

 

Power supply

 

L

 

 

 

 

 

 

 

1

Outdoor unit

 

208/230V, 1ø, ~60Hz

N

 

2

 

 

INV unit

 

*

 

 

 

 

 

 

3

 

 

 

 

 

Ground

 

 

 

 

 

 

A

 

1

L1

Power supply

 

 

 

 

 

U1

U1

L2

Remote

 

 

 

 

2

208/230V, 3ø, ~60Hz

 

 

 

B

U2

U2

L3

controller

 

 

3

 

 

 

 

 

N

 

WHT

1

1

 

 

1

3

4

 

 

 

 

 

 

 

5

 

 

BLK

2

2

 

 

2

4

Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

*

(No. 2)

Inter-outdoor-unit control wiring

 

Power supply

 

L

D

 

 

 

1

 

 

 

 

208/230V, 1ø, ~60Hz

N

 

2

 

 

 

 

 

 

 

Ground

3

Outdoor unit

 

 

 

 

 

 

Remote

 

 

 

 

U1

INV unit

 

*

 

 

 

 

 

U2

 

 

 

controller

 

 

B

 

 

1

L1

Power supply

 

 

 

 

L2

WHT

1

1

 

 

1

 

2

208/230V, 3ø, ~60Hz

 

 

 

L3

BLK

2

2

 

 

2

3

3

 

 

 

N

 

 

 

 

 

 

 

4

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

5

Ground

 

 

Group control:

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

(No. 3)

 

 

 

 

 

 

 

 

*

 

 

 

* Disconnect switch

Power supply

 

L

1

 

 

 

 

 

 

 

 

(Field Supply)

208/230V, 1ø, ~60Hz

N

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

Ground

3

 

 

 

 

 

 

 

 

* NOTE:

 

 

 

 

 

C

U1

 

 

 

 

 

U2

 

 

Disconnect Switch may be needed by the

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

National/Local code.

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

ALWAYS COMPLY WITH NATIONAL AND

 

 

 

 

 

Indoor unit

 

 

LOCAL CODE REQUIREMENTS.

 

 

 

 

 

 

 

 

 

 

 

 

 

*

(No. n)

 

 

 

 

Power supply

 

L

 

 

 

 

 

 

 

1

 

 

 

 

 

N

 

 

 

 

 

208/230V, 1ø, ~60Hz

 

2

 

 

 

 

 

 

 

Ground

3

 

 

 

 

 

 

 

 

 

 

 

 

Remote

 

 

 

 

U1

 

 

 

 

 

 

 

B

U2

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT

1

1

 

 

1

 

 

 

 

BLK

2

2

 

 

2

 

 

 

 

NOTE

(1)Refer to Section 5-2. “Recommended Wire Length and Wire Diameter for Power Supply System” for the explanation of “A,” “B,” “C,” and “D,” in the above diagram.

(2)The basic connection diagram of the indoor unit shows the 6P (XM type) terminal board, so the ter- minal boards in your equipment may differ from the diagram.

(3)Refrigerant Circuit (R.C.) address should be set before turning the power on.

(4)Regarding R.C. address setting, refer to page 87. Auto address setting can be executed by remote controller automatically. Refer to page 87 – 91.

XM Type

6P terminal board

L

N

U1

U2

R1

R2

POWER

UNIT CONTROL

REMOTE

SUPPLY LINE CONTROL LINE

70

W-3WAY_ECO-i_US.indd 70

2008/02/21 19:01:44

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 70
Contents Outdoor Units Sanyo Commercial SolutionsR410A Models Indoor Units Optional Controllers…In Moist or Uneven Locations For safe installation and trouble-free operation, you must…In a Room …In an Area with High WindsAmount 353 oz Amount 529 oz CountermeasuresDifferent tools required Care regarding tubingBe sure to recharge the refrigerant only in liquid form Manifold gauge Vacuum pumpExisting tubing cannot be used especially R22 Compressor specifications are differentSingle-outlet valve Refrigerating machine oil differs R22Contents AIR Purging Electrical Wiring 5-1. General Precautions on WiringHOW to Process Tubing Test RUN 8-1. Preparing for Test RunOutdoor Unit Part name Tools Required for Installation not suppliedAccessories Supplied Type of Copper Tube and Insulation Material1-Way Air Discharge Semi-Concealed For sealing recessed portion of power supply4-Way Air Discharge Semi-Concealed X-Type Concealed DuctWall-Mounted Concealed Duct High-Static PressureCeiling-Mounted 4-Way Air Discharge Semi-Concealed XM TypeTubing Length H3 C12 Outdoor Unit Tubing Connection Size a D Tubing Size 10 Main Tubing Size LA11 Main Tubing Size After Distribution LB, LC BTU/h 95.500 153.60015 Refrigerant tubing Existing tubing can be used System Limitations 18 System Limitations 17 Refrigerant Charge Amount at Shipment for outdoor unitCommon solenoid valve kit Tube branching methods horizontal use Header joint systemHeader joint system Indoor Suction Tube Tubing size with thermal insulationModel name Cooling capacity after distribution Remarks Size Part B Part C Part D Part E Part F Part G Part H Inch21 Dimensions for connections of each part Discharge Tube Liquid TubeSpecifications Precautions on Installation of Solenoid Valve KitTypes and specifications Optional Solenoid Valve KitUnit Installation of Solenoid Valve Kit Relay kit FrontExample Use the same tools for R22 and for R410A R410A additional charging absolutely mustBe done through liquid charging Main tubing Distribution joint tubingMain tubing RemarkIndoor Unit Ceiling-MountedTypeWall-Mounted Type Front viewOutdoor Unit Precautions When Installing in Heavy Snow Areas Without snow- proof ducting Without platformUnit Ceiling panel Unit installationCeiling panel Air direction Front directionAir direction Suspending the Indoor Unit Placing the Unit Inside the CeilingInstalling the Drain Piping Be careful since the fan will Start when you short the pinOn the indoor control board Removing the corner cover Installing the Ceiling Panel Wiring the Ceiling Panel Attaching the air-intake grilleAdjusting the Auto Flap Checking After InstallationWhen Removing the Ceiling Panel for Servicing Special Remarks DC Fan Tap Change ProcedureSuspending the Indoor Unit Placing the Unit Inside the CeilingThis may cause water to spray Installing the Drain PipingDo not install an air bleeder as From the drain pipe outletChecking the Drainage How to Install the Ceiling Panel Main unitBefore Installing the Ceiling Panel Checking the unit positionInstalling the Ceiling Panel Wiring the Ceiling PanelWhen Removing the Ceiling Panel for Servicing How to Attach the Corner & Air-Intake GrilleChecking After Installation Adjusting the Auto Flap22-3/64 23-5/8Leakage may occur Confirm that the unit isLevel. If it is not level, water Be sure to use a level gaugeInstalling the Drain Piping 3WAYECO-iUS.indd 2008/02/07 M5 ss40 Electrical Power Wiring Wiring connectionsWiring Ss12 or 5/32 ss15/32 For fasteningRemoving the intake grille Removing the side panelAir leakage Others Check after installation Installing the side panel and intake grilleInstalling the intake grille If a wireless remote controller is usedAir outlet duct flange Inspection access27/32 Indoor unit Refrigerant tubingSupporting the indoor unit inside Enough to support the weight of the unitIt is important that you use extreme care Ceiling. Ensure that the ceiling is strongMaximum of 19-11/16. Do not raise it any higher than Section directly after the connection port can be raised a19-11/16, as this could result in water leaks. Fig Short the pin on the indoor control board How to read the diagramBe careful since the fan will start when you Increasing the Fan Speed23-5/8 for checking and servicing the electrical system 17-23/3231/32 Indoor Fan Performance How to Read the Diagram Min -31/32 Inspection plugRefrigerant tubing drain hose position Extreme care in supporting Wall and ceiling side opening positionIt is important that you use Indoor unit from the ceilFixture Double nut Field supply Approx 63/64 Ceiling Surface Washer NutRear cover Duct for Fresh AirShaping the Tubing Downward gradient Min /100Regulations before wir How to carry out power supply wiringCheck local electrical codes Ing. Also, check any specifiedSelecting and Making a Hole Installing the Rear Panel onto the WallIf the Wall is Wooden Removing the grille Removing the Grille to Install the Indoor UnitIf the Wall is Brick, Concrete or Similar Attaching the grilleShaping the Tubing Right-rear tubing Installing the Drain HoseDo not supply power to the unit or operate Left or left-rear tubingKHX0752 / 0952 / 1252 KHX2452Positions where anchor bolts are fastened Installing the Outdoor UnitTransporting Remove the Brackets Used for Transport Routing the TubingRefrigerant tube port Prepare the TubingConnect the Tubing Tubing size mm Outer dia ThicknessTightening torque for each cap Work methodInter-outdoor unit control wiring General Precautions on WiringOutdoor unit Time delay fuse or Circuit capacity Use shielded wiringWiring Controller Wiring System DiagramPower For K, A, X, T, U and D TypesFor XM Type XM TypeOutdoor unit Indoor unit How to connect wiring to the terminal For stranded wiring Important Note When Wiring for Common Type TypeType Important Note When Wiring for XM Type XM TypeUse of the Flaring Method Connecting the Refrigerant TubingFlaring Procedure with a Flare Tool DeburringTube diameter Tightening torque ApproximateThree tubes arranged together Two tubes arranged togetherFour tubes arranged together Finishing the Installation Taping the TubesLeak test Air Purging with a Vacuum Pump for Test Run PreparationManifold gauge Vacuum pump Evacuation 45 min. or more 90 min. or moreUse a cylinder designed for use with R410A Charging additional refrigerantFinishing the job Test RUN Items to Check Before the Test Run Test Run ProcedureUnit with the unit Indoor unit setting S004 Rotary switch, red Address setting of main outdoor unit S007 Unit No. settingMain Outdoor Unit PCB Setting No main unit Settings Auto Address Setting Basic wiring diagram ExampleAutomatic Address Setting from the Outdoor Unit Outdoor main/sub22-9 Automatic Address Setting from Outdoor Unit Automatic Address Setting no compressor operation3 OFF Automatic Address Setting in Heating Mode Automatic Address Setting in Cooling Mode Automatic Address Setting* from the Remote ControllerLED 2 Display during automatic address settingBlink alternately Remote Controller Test Run Settings If 1 indoor unit is connected to 1 remote controllerChecking the indoor unit addresses Possible cause of malfunction LEDMessage Alarm messages displayed on system controller Way Air Discharge Semi-Concealed Type X, XM Types Tips for Energy Saving Should the power fail while the unit is runningSoot Type 1-WAY Way air discharge semi-concealed type aTroubleshooting 100Type high static pressure Concealed Duct High-Static Pressure Type U, D TypesType standard static pressure 101On the wired remote control unit 102CEILING-MOUNTED 103Or soot 104105 Tips for Energy Saving 106