Sanyo CHDZR14053 General Precautions on Wiring, Outdoor unit Time delay fuse or Circuit capacity

Page 68

5. ELECTRICAL WIRING

5-1. General Precautions on Wiring

(1)Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.

(2)Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provid- ed in the exclusive line.

(3)To prevent possible hazards from insulation failure, the unit must be grounded.

(4)Each wiring connection must be done in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.

(5)Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

(6)Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.

(7)Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before beginning. You must ensure that installation complies with all relevant rules and regulations.

(8)To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:

The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.

Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.

(9)If the power supply cord of this appliance is dam- aged, it must be replaced by a repair shop appoint- ed by the manufacture, because special purpose tools are required.

5-2. Recommended Wire Length and Wire Diameter for Power Supply System

Outdoor unit

 

Time delay fuse or

 

circuit capacity

 

 

CHDZ09053

50 A

CHDZR09053

 

 

 

CHDZ14053

70 A

CHDZR14053

 

 

 

Indoor unit

 

Type

Time delay fuse or

circuit capacity

 

 

 

K

10 – 16A

 

 

A, X, XM, T, U

10 – 16A

 

 

D (364, 484)

10 – 16A

 

 

Control wiring

(A) Inter-unit (between outdoor and

(B) Remote control wiring

(C) Control wiring for group control

indoor units) control wiring

 

 

 

 

 

AWG #18 (0.75 mm2)

AWG #18 (0.75 mm2)

AWG #18 (0.75 mm2)

Use shielded wiring*

Use shielded wiring

Use shielded wiring

 

 

 

Max. 3,280 ft.

Max. 1,640 ft.

Max. 1,640 ft. (Total)

 

 

 

NOTE

* With ring-type wire terminal.

(D) Inter-outdoor unit control wiring

AWG #18 (0.75 mm2)

Use shielded wiring

Max. 1,640 ft.

68

W-3WAY_ECO-i_US.indd 68

2008/02/20 9:58:52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 68
Contents Sanyo Commercial Solutions R410A Models Indoor UnitsOutdoor Units Optional ControllersFor safe installation and trouble-free operation, you must …In a Room…In Moist or Uneven Locations …In an Area with High WindsAmount 353 oz Amount 529 oz CountermeasuresCare regarding tubing Be sure to recharge the refrigerant only in liquid formDifferent tools required Manifold gauge Vacuum pumpCompressor specifications are different Single-outlet valveExisting tubing cannot be used especially R22 Refrigerating machine oil differs R22Contents Electrical Wiring 5-1. General Precautions on Wiring HOW to Process TubingAIR Purging Test RUN 8-1. Preparing for Test RunTools Required for Installation not supplied Accessories SuppliedOutdoor Unit Part name Type of Copper Tube and Insulation MaterialFor sealing recessed portion of power supply 4-Way Air Discharge Semi-Concealed X-Type1-Way Air Discharge Semi-Concealed Concealed DuctConcealed Duct High-Static Pressure Ceiling-MountedWall-Mounted 4-Way Air Discharge Semi-Concealed XM TypeTubing Length H3 CTubing Size 10 Main Tubing Size LA 11 Main Tubing Size After Distribution LB, LC12 Outdoor Unit Tubing Connection Size a D BTU/h 95.500 153.60015 Refrigerant tubing Existing tubing can be used Common solenoid valve kit 17 Refrigerant Charge Amount at Shipment for outdoor unitSystem Limitations 18 System Limitations Header joint system Indoor Header joint systemTube branching methods horizontal use Tubing size with thermal insulation Model name Cooling capacity after distribution RemarksSuction Tube Size Part B Part C Part D Part E Part F Part G Part H Inch21 Dimensions for connections of each part Discharge Tube Liquid TubePrecautions on Installation of Solenoid Valve Kit Types and specificationsSpecifications Optional Solenoid Valve KitUnit Installation of Solenoid Valve Kit Relay kit FrontR410A additional charging absolutely must Be done through liquid chargingExample Use the same tools for R22 and for R410A Main tubing Distribution joint tubingMain tubing RemarkCeiling-MountedType Wall-Mounted TypeIndoor Unit Front viewOutdoor Unit Precautions When Installing in Heavy Snow Areas Without snow- proof ducting Without platformUnit installation Ceiling panelUnit Ceiling panel Air direction Front directionAir direction Suspending the Indoor Unit Placing the Unit Inside the CeilingInstalling the Drain Piping On the indoor control board Start when you short the pinBe careful since the fan will Removing the corner cover Installing the Ceiling Panel Wiring the Ceiling Panel Attaching the air-intake grilleChecking After Installation When Removing the Ceiling Panel for ServicingAdjusting the Auto Flap Special Remarks DC Fan Tap Change ProcedureSuspending the Indoor Unit Placing the Unit Inside the CeilingInstalling the Drain Piping Do not install an air bleeder asThis may cause water to spray From the drain pipe outletHow to Install the Ceiling Panel Main unit Before Installing the Ceiling PanelChecking the Drainage Checking the unit positionInstalling the Ceiling Panel Wiring the Ceiling PanelHow to Attach the Corner & Air-Intake Grille Checking After InstallationWhen Removing the Ceiling Panel for Servicing Adjusting the Auto Flap22-3/64 23-5/8Confirm that the unit is Level. If it is not level, waterLeakage may occur Be sure to use a level gaugeInstalling the Drain Piping 3WAYECO-iUS.indd 2008/02/07 Electrical Power Wiring Wiring connections WiringM5 ss40 Ss12 or 5/32 ss15/32 For fasteningRemoving the intake grille Removing the side panelAir leakage Installing the side panel and intake grille Installing the intake grilleOthers Check after installation If a wireless remote controller is usedInspection access 27/32 Indoor unitAir outlet duct flange Refrigerant tubingEnough to support the weight of the unit It is important that you use extreme careSupporting the indoor unit inside Ceiling. Ensure that the ceiling is strong19-11/16, as this could result in water leaks. Fig Section directly after the connection port can be raised aMaximum of 19-11/16. Do not raise it any higher than How to read the diagram Be careful since the fan will start when youShort the pin on the indoor control board Increasing the Fan Speed23-5/8 for checking and servicing the electrical system 17-23/3231/32 Indoor Fan Performance How to Read the Diagram Min -31/32 Inspection plugRefrigerant tubing drain hose position Wall and ceiling side opening position It is important that you useExtreme care in supporting Indoor unit from the ceilFixture Double nut Field supply Approx 63/64 Ceiling Surface Washer NutDuct for Fresh Air Shaping the TubingRear cover Downward gradient Min /100How to carry out power supply wiring Check local electrical codesRegulations before wir Ing. Also, check any specifiedIf the Wall is Wooden Installing the Rear Panel onto the WallSelecting and Making a Hole Removing the Grille to Install the Indoor Unit If the Wall is Brick, Concrete or SimilarRemoving the grille Attaching the grilleInstalling the Drain Hose Do not supply power to the unit or operateShaping the Tubing Right-rear tubing Left or left-rear tubingKHX0752 / 0952 / 1252 KHX2452Transporting Installing the Outdoor UnitPositions where anchor bolts are fastened Remove the Brackets Used for Transport Routing the TubingPrepare the Tubing Connect the TubingRefrigerant tube port Tubing size mm Outer dia ThicknessTightening torque for each cap Work methodGeneral Precautions on Wiring Outdoor unit Time delay fuse or Circuit capacityInter-outdoor unit control wiring Use shielded wiringWiring System Diagram PowerWiring Controller For K, A, X, T, U and D TypesFor XM Type XM TypeOutdoor unit Indoor unit How to connect wiring to the terminal For stranded wiring Important Note When Wiring for Common Type TypeType Important Note When Wiring for XM Type XM TypeConnecting the Refrigerant Tubing Flaring Procedure with a Flare ToolUse of the Flaring Method DeburringTube diameter Tightening torque ApproximateFour tubes arranged together Two tubes arranged togetherThree tubes arranged together Finishing the Installation Taping the TubesManifold gauge Vacuum pump Air Purging with a Vacuum Pump for Test Run PreparationLeak test Evacuation 45 min. or more 90 min. or moreFinishing the job Charging additional refrigerantUse a cylinder designed for use with R410A Test RUN Unit with the unit Test Run ProcedureItems to Check Before the Test Run Indoor unit setting S004 Rotary switch, red Address setting of main outdoor unit S007 Unit No. settingMain Outdoor Unit PCB Setting Auto Address Setting Basic wiring diagram Example Automatic Address Setting from the Outdoor UnitNo main unit Settings Outdoor main/sub22-9 3 OFF Automatic Address Setting no compressor operationAutomatic Address Setting from Outdoor Unit Automatic Address Setting in Heating Mode Automatic Address Setting in Cooling Mode Automatic Address Setting* from the Remote ControllerBlink alternately Display during automatic address settingLED 2 Checking the indoor unit addresses If 1 indoor unit is connected to 1 remote controllerRemote Controller Test Run Settings Possible cause of malfunction LEDMessage Alarm messages displayed on system controller Way Air Discharge Semi-Concealed Type X, XM Types Soot Should the power fail while the unit is runningTips for Energy Saving Type 1-WAY Way air discharge semi-concealed type aTroubleshooting 100Concealed Duct High-Static Pressure Type U, D Types Type standard static pressureType high static pressure 101On the wired remote control unit 102CEILING-MOUNTED 103Or soot 104105 Tips for Energy Saving 106