8. TEST RUN

8-1. Preparing for Test Run

Before attempting to start the air conditioner, check the following.

(1)The control wiring is correctly connected and all electrical connections are tight.

(2)The transportation pads for the indoor fan have been removed. If not, remove them now.

(3)The power has been connected to the unit for at least 5 hours before starting the compressor. The bottom of the compressor should be warm to the touch and the crankcase heater around the feet of the compressor should be hot to the touch.

(Fig. 8-1)

(4)If only 1 outdoor unit is installed, close the service valve on the balance tubes, and open the service valve on the other 3 tubes (suction, discharge, and liquid tubes). (Fig. 8-2)

If 2 or 3 outdoor units are installed, open the service valves on all 4 tubes (suction, discharge, liquid, and balance tubes). (Fig. 8-2)

(5)Request that the customer be present for the trial run.

Explain the contents of the instruction manual, then have the customer actually operate the system.

(6)Be sure to give the instruction manual and warranty certificate to the customer.

(7)When replacing the control PCB, be sure to make all the same settings on the new PCB as were in use before replacement.

The existing EEP ROM is not changed, and is con- nected to the new control PCB.

83

ON

(Power must be turned ON at least 5 hours before attempting test run)

Power mains switch

Fig. 8-1

Balance tube

Liquid tube

Discharge tube

Suction tube

Fig. 8-2

W-3WAY_ECO-i_US.indd 83

2008/02/07 10:56:11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 83
Contents Optional Controllers Sanyo Commercial SolutionsR410A Models Indoor Units Outdoor Units…In an Area with High Winds For safe installation and trouble-free operation, you must…In a Room …In Moist or Uneven LocationsCountermeasures Amount 353 oz Amount 529 ozManifold gauge Vacuum pump Care regarding tubingBe sure to recharge the refrigerant only in liquid form Different tools requiredRefrigerating machine oil differs R22 Compressor specifications are differentSingle-outlet valve Existing tubing cannot be used especially R22Contents Test RUN 8-1. Preparing for Test Run Electrical Wiring 5-1. General Precautions on WiringHOW to Process Tubing AIR PurgingType of Copper Tube and Insulation Material Tools Required for Installation not suppliedAccessories Supplied Outdoor Unit Part nameConcealed Duct For sealing recessed portion of power supply4-Way Air Discharge Semi-Concealed X-Type 1-Way Air Discharge Semi-Concealed4-Way Air Discharge Semi-Concealed XM Type Concealed Duct High-Static PressureCeiling-Mounted Wall-MountedH3 C Tubing LengthBTU/h 95.500 153.600 Tubing Size 10 Main Tubing Size LA11 Main Tubing Size After Distribution LB, LC 12 Outdoor Unit Tubing Connection Size a D15 Refrigerant tubing Existing tubing can be used Common solenoid valve kit 17 Refrigerant Charge Amount at Shipment for outdoor unitSystem Limitations 18 System Limitations Header joint system Indoor Header joint systemTube branching methods horizontal use Size Part B Part C Part D Part E Part F Part G Part H Inch Tubing size with thermal insulationModel name Cooling capacity after distribution Remarks Suction TubeDischarge Tube Liquid Tube 21 Dimensions for connections of each partOptional Solenoid Valve Kit Precautions on Installation of Solenoid Valve KitTypes and specifications SpecificationsUnit Relay kit Front Installation of Solenoid Valve KitMain tubing Distribution joint tubing R410A additional charging absolutely mustBe done through liquid charging Example Use the same tools for R22 and for R410ARemark Main tubingFront view Ceiling-MountedTypeWall-Mounted Type Indoor UnitOutdoor Unit Without snow- proof ducting Without platform Precautions When Installing in Heavy Snow AreasAir direction Front direction Unit installationCeiling panel Unit Ceiling panelAir direction Placing the Unit Inside the Ceiling Suspending the Indoor UnitInstalling the Drain Piping On the indoor control board Start when you short the pinBe careful since the fan will Removing the corner cover Installing the Ceiling Panel Attaching the air-intake grille Wiring the Ceiling PanelSpecial Remarks DC Fan Tap Change Procedure Checking After InstallationWhen Removing the Ceiling Panel for Servicing Adjusting the Auto FlapPlacing the Unit Inside the Ceiling Suspending the Indoor UnitFrom the drain pipe outlet Installing the Drain PipingDo not install an air bleeder as This may cause water to sprayChecking the unit position How to Install the Ceiling Panel Main unitBefore Installing the Ceiling Panel Checking the DrainageWiring the Ceiling Panel Installing the Ceiling PanelAdjusting the Auto Flap How to Attach the Corner & Air-Intake GrilleChecking After Installation When Removing the Ceiling Panel for Servicing23-5/8 22-3/64Be sure to use a level gauge Confirm that the unit isLevel. If it is not level, water Leakage may occurInstalling the Drain Piping 3WAYECO-iUS.indd 2008/02/07 Ss12 or 5/32 ss15/32 For fastening Electrical Power Wiring Wiring connectionsWiring M5 ss40Removing the side panel Removing the intake grilleAir leakage If a wireless remote controller is used Installing the side panel and intake grilleInstalling the intake grille Others Check after installationRefrigerant tubing Inspection access27/32 Indoor unit Air outlet duct flangeCeiling. Ensure that the ceiling is strong Enough to support the weight of the unitIt is important that you use extreme care Supporting the indoor unit inside19-11/16, as this could result in water leaks. Fig Section directly after the connection port can be raised aMaximum of 19-11/16. Do not raise it any higher than Increasing the Fan Speed How to read the diagramBe careful since the fan will start when you Short the pin on the indoor control board17-23/32 23-5/8 for checking and servicing the electrical system31/32 Min -31/32 Inspection plug Indoor Fan Performance How to Read the DiagramRefrigerant tubing drain hose position Indoor unit from the ceil Wall and ceiling side opening positionIt is important that you use Extreme care in supportingApprox 63/64 Ceiling Surface Washer Nut Fixture Double nut Field supplyDownward gradient Min /100 Duct for Fresh AirShaping the Tubing Rear coverIng. Also, check any specified How to carry out power supply wiringCheck local electrical codes Regulations before wirIf the Wall is Wooden Installing the Rear Panel onto the WallSelecting and Making a Hole Attaching the grille Removing the Grille to Install the Indoor UnitIf the Wall is Brick, Concrete or Similar Removing the grilleLeft or left-rear tubing Installing the Drain HoseDo not supply power to the unit or operate Shaping the Tubing Right-rear tubingKHX2452 KHX0752 / 0952 / 1252Transporting Installing the Outdoor UnitPositions where anchor bolts are fastened Routing the Tubing Remove the Brackets Used for TransportTubing size mm Outer dia Thickness Prepare the TubingConnect the Tubing Refrigerant tube portWork method Tightening torque for each capUse shielded wiring General Precautions on WiringOutdoor unit Time delay fuse or Circuit capacity Inter-outdoor unit control wiringFor K, A, X, T, U and D Types Wiring System DiagramPower Wiring ControllerXM Type For XM TypeOutdoor unit Indoor unit How to connect wiring to the terminal For stranded wiring Type Important Note When Wiring for Common TypeType XM Type Important Note When Wiring for XM TypeDeburring Connecting the Refrigerant TubingFlaring Procedure with a Flare Tool Use of the Flaring MethodApproximate Tube diameter Tightening torqueFour tubes arranged together Two tubes arranged togetherThree tubes arranged together Taping the Tubes Finishing the InstallationManifold gauge Vacuum pump Air Purging with a Vacuum Pump for Test Run PreparationLeak test 45 min. or more 90 min. or more EvacuationFinishing the job Charging additional refrigerantUse a cylinder designed for use with R410A Test RUN Unit with the unit Test Run ProcedureItems to Check Before the Test Run Address setting of main outdoor unit S007 Unit No. setting Indoor unit setting S004 Rotary switch, redMain Outdoor Unit PCB Setting Outdoor main/sub Auto Address Setting Basic wiring diagram ExampleAutomatic Address Setting from the Outdoor Unit No main unit Settings22-9 3 OFF Automatic Address Setting no compressor operationAutomatic Address Setting from Outdoor Unit Automatic Address Setting in Heating Mode Automatic Address Setting* from the Remote Controller Automatic Address Setting in Cooling ModeBlink alternately Display during automatic address settingLED 2 Checking the indoor unit addresses If 1 indoor unit is connected to 1 remote controllerRemote Controller Test Run Settings LED Possible cause of malfunctionMessage Alarm messages displayed on system controller Way Air Discharge Semi-Concealed Type X, XM Types Soot Should the power fail while the unit is runningTips for Energy Saving Way air discharge semi-concealed type a Type 1-WAY100 Troubleshooting101 Concealed Duct High-Static Pressure Type U, D TypesType standard static pressure Type high static pressure102 On the wired remote control unit103 CEILING-MOUNTED104 Or soot105 106 Tips for Energy Saving