Sanyo KHS3682 + CH3682, CH3082 Maximum Current Value Change Function, Description of function

Page 38
< CH3082 >

Maximum Current Value Change Function

The maximum current value is changed to 14A (for CH3082) or 17A (for CH3682) to prevent power breaker tripping. (It is set to 24A (in cooling) or 22A (in heating) when the unit is delivered from the factory.)

NOTE 1. When the high load is given (Outside temperature is high in the cooling operation, or outdoor temperature is low in the heating operation), the capacity is reduced.

When the maximum current value change function is to be enabled, make sure to receive the approval of the client.

2.The maximum capacity for cooling or heating operation is about as much as the rated capacity.

Description of function

 

Example of operation for heating

Current

 

Power Point C

 

Point A

 

 

Point B

 

Target

 

frequency

 

Frequency

Frequency

Stops operation

 

 

Approx.3 minutes

Operates at the target frequency at Point A and below.

Stops increases to the frequency between Points A and B.

Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded.

Stops operation, and restarts it appoximately 5 minutes later, if Point C is exceeded.

(May operate when sudden voltage fluctuations occur. Indicates trouble.)

 

 

 

 

In cooling

In heating

 

operation

operation

Current Value on

(25.0)

(25.0)

the Point C

 

 

Current Value

22.0

22.0

on the Point B

 

 

Current Value

21.6

21.6

on the Point A

 

 

< CH3682 >

 

 

 

 

In cooling

In heating

 

operation

operation

Current Value on

(25.0)

(25.0)

the Point C

 

 

Current Value

24.0

23.5

on the Point B

 

 

Current Value

23.6

23.1

on the Point A

 

 

<Maximum Current Value Change Procedure>

(1)Remove the inspection panel.

Refer to Fig. 2 in " Noise Reducing Control" for details.

(2)When the switch No.2 of the dip switch (SW01) on the control P.C.Board is turned ON, the maximum current value change. (Fig. 4)

Dip Switch (SW01)

Max. Current Value

Switch No.2

CH3082

CH3682

 

 

 

ON

14.0A

17.0A

OFF

22.0A

24.0A

Power lamp

SW01

Fig.4 Control P.C.Board

ON

1 2

Dip switch (SW01)

38

Image 38
Contents Indoor Model No. Product Code No Destination North AmericaSafety Precautions Prohibit Table of Contents Checking Electrical Components Operating Range Indoor Air Intake Temp Outdoor Air Intake TempKHS3082 SpecificationsUnit Specifications CH3082208V KHS3682 CH368221.9 19.9 Major Component Specifications Indoor UnitCB-KHS3682 Microprocessor 250V 3A Board Outdoor UnitOutdoor Unit CH3082 CompressorOutdoor Unit CH3682 Other Component Specifications Dimensional Data Indoor Unit KHS3082Inchmm Refrigerant Flow Diagram Refrigerant Flow DiagramOperating current performance chart Temperature ChartsLow pressure performance chart Indoor discharge air performance chartHigh pressure performance chart Wide Outdoor inlet air D.B. temp. FC Cooling Capacity Indoor OutdoorCooling Capacity Indoor34,000 BTU/h Power Supply 230V Single Phase 60Hz Cooling Capacity IndoorTH Total Heating Capacity BTU/h Power Supply 230V Single Phase 60Hz Heating CapacityHeating Capacity 36,000 BTU/h Room air temp F 26.7C Fan speed High Horizontal distance ft Air Throw Distance ChartsCooling Vertical distance ft Heating Vertical distance ftHeating CH3082 Voltage230V Cooling Electrical CharacteristicsElectrical Data Voltage208V CoolingCH3682 Voltage230V Cooling 8FA2-5250-70400-3 Electric Wiring DiagramsKHS3082 KHS3682 HIC Emergency operation FunctionsOperation Functions Auto cooling/heating operationTimer backup Lamp colorsOperation Sound Switching Procedure to Noise Reducing ControlNoise Reducing Control Outdoor Unit Description of function Maximum Current Value Change ProcedureMaximum Current Value Change Function CH3682Overload prevention during heating Compressor discharge temperature controlProtective Functions Freeze preventionReverse-Cycle Defrosting Defrost detection and releaseCT Peak current cut-off control Method of Self-Diagnostics TroubleshootingPrecautions before Performing Inspection or Repair Self-diagnostics Lamps Replace the circuit board or the fuse NormalReplace the controller Checking the indoor unit Control Check items unit operation Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Off Blinking Illuminated Serial Communication Error Identification ProcedureAlarm Code E05 Before the OperationTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Trouble Diagnosis of Fan Motor Indoor Fan MotorOutdoor Fan Motor Electromagnetic interference Noise Malfunction and Electromagnetic InterferenceNoise malfunction Locations most susceptible to noise Trouble CorrectionMeasurement of Insulation Resistance Power Supply CordChecking Electrical Components Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy What is New Refrigerant R410A? Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A CharacteristicsChecklist before Servicing Tubing Installation Procedures Tools Specifically for R410AProcedure for Replacing Compressor Case of Compressor MalfunctionDamage to the compressor Never charge a large amountUnit. This may cause ExampleRecharging Case Refrigerant is LeakingWelding leaking points Retro-Fitting Existing Systems When Tubes are ExtendedCharging Additional Refrigerant Use of Existing UnitsOI-852-6-4181-149-00-0 Mode D’EMPLOI Pub. OI-85264181149000 SanyoFeatures ContentsSafety Instructions Alert SymbolsInstallation Location Product InformationNames of Parts Unit Display and Operation ButtonRemote Control Unit Display SymbolsRemote Control Unit Mode selector button HR. Timer button 1-HOUR OFF TimerTemperature setting buttons Temp High Power buttonACL button Using the Remote Control UnitAir conditioner Indoor unit Receiver Remote control unit 16 mmOperation with the Remote Control Unit Automatic OperationAutomatic fan speed Cooling and DRY ModeHeating Mode Manual fan speedHigh Power Mode Unoccupied Indication StatusSpecial Remarks Setting the Timer Operation IndicationDo not Using the 1-HOUR OFF TimerTips for Energy Saving 1030 pm 710 am 1100 am Present timeCare and Cleaning Adjusting the Airflow DirectionOperation Without the Remote Control Unit When the air conditioner is not runningHow to clean the air clean filter Air Clean FilterHow to install the air clean filter Cleaning the main unit and remote control unitOperating Range TroubleshootingWired Remote Controller Washing the front panel with waterAppendix B Installation Instructions Installation Instructions ContentsPlease Read Before Starting General Tools Required for Installation not suppliedAccessories Supplied with Unit Table Optional Copper Tubing KitInstallation Site Selection Additional Materials Required for InstallationSolid base must not cover the hole of the bottom plate Precautions for Installation in a Snowy Area Countermeasures against snow and windUnit inch Front and both sides must remain open Installation with intakes facing outletsRequired space around the outdoor unit Unit Obstacle to the front of unit Top is open Single-unit installationMultiple-unit installation 2 or more units Installation in front-rear rows Obstacles to the front and rear of unitRemove the Rear Panel from the Unit How to Install the Indoor UnitTrical wiring or conduits are Make a HoleIf Block, Brick, Concrete or Similar Type Wall Install the Rear Panel on the WallIf Wooden Wall Hole DiaHow to replace the grille Removing and Installing the GrilleHow to remove the grille Wiring Instructions General precautions on wiring Shape the Indoor Side TubingWire Size and Length Wiring Instructions for Inter-unit Connections For stranded wiring How to connect wiring to the terminal For Indoor UnitFor Outdoor Unit For solid core wiring or F-cable Mounting Right-side tubingDrain cap Switching drain hose and drain capLeft-side tubing To unmount indoor unit Do not supply power toTubing and wiring to the out Frame Fastening MethodWiring Instructions for the Outdoor Unit How to Install the Outdoor UnitFirst refer to . Installation Site Selection Routing the Tubing and WiringUse of the Flaring Method Flaring Procedure with a Flare ToolRefrigerant Tubing If the special R410A flare tool is usedInsulation of Refrigerant Tubing Connecting Tubing between Indoor and Outdoor UnitsFinishing the Installation Taping the TubesAir Purging Attempting to turn the valve Be sure to completely insertHex wrench before How to Test Run the Air Conditioner Basic Functions of the Service Valves Pump DownService Valve Connections Remote Control Unit Installation PositionAddress Switch Address Setting of the Remote Control Unit