5-4. Connecting Tubing between Indoor and Outdoor Units

a)Tightly connect the indoor side refrigerant tubing exten- ded from the wall with the outdoor side tubing. (Fig. 52)

b)To fasten the flare nuts, apply specified torque as:

Table 6

Tube Dia.

Nut

Tightening Torque

 

 

 

1/4" (6.35 mm)

21/32" (17 mm)

Approx. 120 – 160 lbs·in (140 – 180 kgf·cm)

 

 

 

3/8" (9.52 mm)

7/8" (22 mm)

Approx. 300 – 360 lbs·in (340 – 420 kgf·cm)

 

 

 

1/2" (12.70 mm)

1-1/32" (26 mm)

Approx. 430 – 540 lbs·in (490 – 610 kgf·cm)

 

 

 

5/8" (15.88 mm)

1-5/32" (29 mm)

Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)

 

 

 

5-5. Insulation of Refrigerant Tubing

IMPORTANT

To prevent heat loss and wet floors due to dripping of con-

densation, both tubes must be well insulated with a proper insulation material. (Fig. 53)

The thickness of the insulation should be a minimum 5/16" (8 mm). (Fig. 54)

5-6. Taping the Tubes

Torque wrench

Spanner

Indoor unit

Outdoor unit

Fig. 52

 

Flare

 

insulation

 

Fig. 53

 

Insulation

 

Thickness:

Min.

min. 5/16"

5/16"

(8 mm)

(8 mm)

 

CAUTION

After a tube has been insulat-

 

ed, never try to bend it into a

 

 

narrow curve, as this may

 

cause the tube to break or

 

crack.

(1)At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.

(2)Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 55)

(3)Clamp the tubing bundle to wall, using 1 clamp approx. every 47" (120 cm).

NOTE

Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the con- densation drain hose splits away from the bundle and drips clear of the unit and the tubing.

5-7. Finishing the Installation

After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 56)

Fig. 54

Clamp

Insulated tubes

Fig. 55

Apply putty here

Tubing

Fig. 56

24

Image 102
Contents Indoor Model No. Product Code No Destination North AmericaSafety Precautions Prohibit Table of Contents Checking Electrical Components Operating Range Indoor Air Intake Temp Outdoor Air Intake TempKHS3082 SpecificationsUnit Specifications CH3082208V KHS3682 CH368221.9 19.9 Major Component Specifications Indoor UnitCB-KHS3682 Microprocessor 250V 3A Board Outdoor UnitOutdoor Unit CH3082 CompressorOutdoor Unit CH3682 Other Component Specifications Dimensional Data Indoor Unit KHS3082Inchmm Refrigerant Flow Diagram Refrigerant Flow DiagramOperating current performance chart Temperature ChartsLow pressure performance chart Indoor discharge air performance chartHigh pressure performance chart Wide Outdoor inlet air D.B. temp. FC Cooling Capacity Indoor OutdoorCooling Capacity Indoor34,000 BTU/h Power Supply 230V Single Phase 60Hz Cooling Capacity IndoorPower Supply 230V Single Phase 60Hz Heating Capacity Heating CapacityTH Total Heating Capacity BTU/h 36,000 BTU/h Room air temp F 26.7C Fan speed High Horizontal distance ft Air Throw Distance ChartsCooling Vertical distance ft Heating Vertical distance ftHeating CH3082 Voltage230V Cooling Electrical CharacteristicsElectrical Data Voltage208V CoolingCH3682 Voltage230V Cooling Electric Wiring Diagrams KHS3082 KHS36828FA2-5250-70400-3 HIC Emergency operation FunctionsOperation Functions Auto cooling/heating operationTimer backup Lamp colorsSwitching Procedure to Noise Reducing Control Noise Reducing Control Outdoor UnitOperation Sound Description of function Maximum Current Value Change ProcedureMaximum Current Value Change Function CH3682Overload prevention during heating Compressor discharge temperature controlProtective Functions Freeze preventionDefrost detection and release CT Peak current cut-off controlReverse-Cycle Defrosting Troubleshooting Precautions before Performing Inspection or RepairMethod of Self-Diagnostics Self-diagnostics Lamps Normal Replace the controllerReplace the circuit board or the fuse Using the TEST/T-RUN terminals Checking the Indoor and Outdoor UnitsChecking the indoor unit Control Check items unit operation Off Blinking Illuminated Serial Communication Error Identification ProcedureAlarm Code E05 Before the OperationTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Trouble Diagnosis of Fan Motor Indoor Fan MotorOutdoor Fan Motor Electromagnetic interference Noise Malfunction and Electromagnetic InterferenceNoise malfunction Locations most susceptible to noise Trouble CorrectionMeasurement of Insulation Resistance Power Supply CordChecking Electrical Components Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy What is New Refrigerant R410A? Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A CharacteristicsChecklist before Servicing Tubing Installation Procedures Tools Specifically for R410AProcedure for Replacing Compressor Case of Compressor MalfunctionDamage to the compressor Never charge a large amountUnit. This may cause ExampleCase Refrigerant is Leaking Welding leaking pointsRecharging Retro-Fitting Existing Systems When Tubes are ExtendedCharging Additional Refrigerant Use of Existing UnitsOI-852-6-4181-149-00-0 Mode D’EMPLOI Pub. OI-85264181149000 SanyoFeatures ContentsSafety Instructions Alert SymbolsInstallation Location Product InformationNames of Parts Unit Display and Operation ButtonRemote Control Unit Display SymbolsRemote Control Unit Mode selector button HR. Timer button 1-HOUR OFF TimerTemperature setting buttons Temp High Power buttonACL button Using the Remote Control UnitAir conditioner Indoor unit Receiver Remote control unit 16 mmOperation with the Remote Control Unit Automatic OperationAutomatic fan speed Cooling and DRY ModeHeating Mode Manual fan speedHigh Power Mode Unoccupied Indication StatusSpecial Remarks Setting the Timer Operation IndicationDo not Using the 1-HOUR OFF TimerTips for Energy Saving 1030 pm 710 am 1100 am Present timeCare and Cleaning Adjusting the Airflow DirectionOperation Without the Remote Control Unit When the air conditioner is not runningHow to clean the air clean filter Air Clean FilterHow to install the air clean filter Cleaning the main unit and remote control unitOperating Range TroubleshootingWired Remote Controller Washing the front panel with waterAppendix B Installation Instructions Installation Instructions ContentsPlease Read Before Starting General Tools Required for Installation not suppliedAccessories Supplied with Unit Table Optional Copper Tubing KitInstallation Site Selection Additional Materials Required for InstallationSolid base must not cover the hole of the bottom plate Precautions for Installation in a Snowy Area Countermeasures against snow and windUnit inch Installation with intakes facing outlets Required space around the outdoor unitFront and both sides must remain open Unit Top is open Single-unit installation Multiple-unit installation 2 or more unitsObstacle to the front of unit Installation in front-rear rows Obstacles to the front and rear of unitRemove the Rear Panel from the Unit How to Install the Indoor UnitTrical wiring or conduits are Make a HoleIf Block, Brick, Concrete or Similar Type Wall Install the Rear Panel on the WallIf Wooden Wall Hole DiaRemoving and Installing the Grille How to remove the grilleHow to replace the grille Wiring Instructions General precautions on wiring Shape the Indoor Side TubingWire Size and Length Wiring Instructions for Inter-unit Connections How to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableFor stranded wiring Mounting Right-side tubingSwitching drain hose and drain cap Left-side tubingDrain cap To unmount indoor unit Do not supply power toTubing and wiring to the out Frame Fastening MethodWiring Instructions for the Outdoor Unit How to Install the Outdoor UnitFirst refer to . Installation Site Selection Routing the Tubing and WiringUse of the Flaring Method Flaring Procedure with a Flare ToolRefrigerant Tubing If the special R410A flare tool is usedInsulation of Refrigerant Tubing Connecting Tubing between Indoor and Outdoor UnitsFinishing the Installation Taping the TubesAir Purging Be sure to completely insert Hex wrench beforeAttempting to turn the valve How to Test Run the Air Conditioner Basic Functions of the Service Valves Pump DownService Valve Connections Remote Control Unit Installation PositionAddress Switch Address Setting of the Remote Control Unit