To unmount indoor unit
Press the 2 ▲ marks on the lower part of the indoor unit and unlatch the tabs. Then lift the indoor unit and unmount. (Fig. 42)
3-10. Frame Fastening Method
(1)Remove the screw cover on the bottom surface. (Fig. 43)
(2)Fasten the frame to the rear panel using the 2 sup- plied tapping screws 5/32" x 13/32" (4 x 10 mm). (Fig. 43)
NOTE
Under normal conditions, the installation design calls for a less than 3/32" (2 mm) gap between the air conditioner unit and the wall.
Confirm that the gap is appropriate (less than 2 mm).
a)The drain hose should be slanted downward to the outdoors. (Fig. 44)
b)Never form a trap in the course of the hose.
c)If the drain hose will run in the room, insulate the hose with insulation* so that chilled condensation will not damage furniture or floors. (Fig. 45)
* Foamed polyethylene or its equivalent is recom- mended.
WARNING | Do not supply power to the |
| unit or operate it until all |
| tubing and wiring to the out- |
| side unit are completed. |
Risk of Electric Shock
Push
Fig. 42
Screw cover
Screw
Fig. 43
| Slant | |
Indoor | Drain | |
unit | ||
hose | ||
|
Fig. 44
Condensation
Insulation material (Locally purchased) must be used.
Fig. 45
21