Sanyo KHS3682 + CH3682, KHS3082 + CH3082 service manual Special Remarks

Page 72

A.In Heating Mode: ( )

(1)When the room temperature drops below 46°F, Heating Operation will begin.

(2)When the room temperature rises to above 53°F, Heating Operation will stop.

The above actions will repeat so that the room temperature is maintained at about 50°F.

Room

Temperature (°F)

53

 

 

 

 

 

(2)

 

50

 

 

 

 

 

 

46

 

 

 

 

(1)

 

 

 

 

 

 

 

 

Heating

 

Time

 

Heating

 

starts

stops

B. In Cooling Mode: ( )

(1)When the room temperature rises above 89°F, Cooling Operation will begin.

(2)When the room temperature drops below 82°F, Cooling Operation will stop.

The above actions will repeat so that the room temperature is maintained at about 86°F.

SPECIAL REMARKS

‘‘DRY’’ ( ) Operation

How it works?

Once the room temperature reaches the level that was set, the unit’s operation frequency is changed automatically.

During DRY operation, the fan speed automatically runs at lower speed for providing a comfortable breeze.

‘‘DRY’’ operation is not possible if the indoor temperature is 59 °F or less.

Heating ( ) Operation

Heating performance

When High power operation , Fan speed Automatic operation , HIGH or MEDIUM has been changed to Fan speed

LOW , Quiet operation or Night Setback , the fan speed may not be reduced to the desired setting immediately but rather it may be reduced slowly in steps due to the operating status of the air conditioner. (A maximum of 5 minutes are required for the change to be completed.)

Because this air conditioner heats a room by drawing in the heat of the outside air (heat pump system), the heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be obtained with this air conditioner, use another heating appliance together with it.

Defrosting

Room

Temperature (°F)(1)

89

86

82(2)

Cooling Cooling

starts stops

Time

When the outdoor temperature is low, frost or ice may form on the heat exchanger coil, reducing heating performance. When this happens, a microcomputer defrosting system operates. At the same time, the fan on the indoor unit stops and the OPERATION lamp lights red and orange alternately until defrosting is completed. Heating operation restarts after several minutes. (This interval will vary slightly depending upon the outdoor temperature and the way in which frost forms.)

Cold draft prevention

• For several minutes after the start of heating operation, the indoor

fan runs at a lower speed until the indoor heat exchanger coil has

warmed up sufficiently. However, the fan may remain stopped when

Unoccupied Mode triggers Heating or Cooling Operation in response to the room temperature, but when this happens, the remote control unit will continue to display the Operation mode set by the user.

If the room temperature rapidly changes, the room temperature may get over the upper or lower limit when the unoccupied function is activated.

NOTE

The remote control unit should be used in the location specified in “REMOTE CONTROL UNIT INSTALLATION POSITION” on page 8.

The air conditioner’s stop order (stated in (2) / above) is valid only when the unoccupied function is operated.

the room temperature is low. This is because the COLD DRAFT

PREVENTION SYSTEM is in operation.

Cooling ( ) operation

Sometimes the indoor unit may not get to the set fan speed such as LOW under cool operation at very low outdoor temperatures due to the indoor unit being protected from ice or frost.

Power failure during operation

In the event of power failure, the unit will stop. When the power is resumed, the unit will restart automatically in approximately

5 minutes by the remote control unit.

If the remote control unit is on and left in a location where the unit can receive a signal, then the unit will automatically restart in approximately 5 minutes of power being restored.

Clicking Sound

Clicking sound is heard from the air conditioner

In heating or cooling operation, any plastic parts may expand or shrink due to a sudden temperature change. In this event, a clicking sound may occur. This is normal, and the sound will soon disappear.

Remote Control Unit

The remote control unit sends the setting condition to the air conditioner regularly at five minute intervals.

12

OI-149-12-EG

 

Image 72
Contents Indoor Model No. Product Code No Destination North AmericaSafety Precautions Prohibit Table of Contents Checking Electrical Components Operating Range Indoor Air Intake Temp Outdoor Air Intake TempSpecifications Unit SpecificationsKHS3082 CH3082208V KHS3682 CH368221.9 19.9 Major Component Specifications Indoor UnitCB-KHS3682 Microprocessor 250V 3A Outdoor Unit Outdoor Unit CH3082Board CompressorOutdoor Unit CH3682 Other Component Specifications Dimensional Data Indoor Unit KHS3082Inchmm Refrigerant Flow Diagram Refrigerant Flow DiagramTemperature Charts Low pressure performance chartOperating current performance chart Indoor discharge air performance chartHigh pressure performance chart Wide Outdoor inlet air D.B. temp. FC Cooling Capacity Indoor OutdoorCooling Capacity Indoor34,000 BTU/h Power Supply 230V Single Phase 60Hz Cooling Capacity IndoorPower Supply 230V Single Phase 60Hz Heating Capacity Heating CapacityTH Total Heating Capacity BTU/h 36,000 BTU/h Air Throw Distance Charts Cooling Vertical distance ftRoom air temp F 26.7C Fan speed High Horizontal distance ft Heating Vertical distance ftHeating Electrical Characteristics Electrical DataCH3082 Voltage230V Cooling Voltage208V CoolingCH3682 Voltage230V Cooling Electric Wiring Diagrams KHS3082 KHS36828FA2-5250-70400-3 HIC Functions Operation FunctionsEmergency operation Auto cooling/heating operationTimer backup Lamp colorsSwitching Procedure to Noise Reducing Control Noise Reducing Control Outdoor UnitOperation Sound Maximum Current Value Change Procedure Maximum Current Value Change FunctionDescription of function CH3682Compressor discharge temperature control Protective FunctionsOverload prevention during heating Freeze preventionDefrost detection and release CT Peak current cut-off controlReverse-Cycle Defrosting Troubleshooting Precautions before Performing Inspection or RepairMethod of Self-Diagnostics Self-diagnostics Lamps Normal Replace the controllerReplace the circuit board or the fuse Using the TEST/T-RUN terminals Checking the Indoor and Outdoor UnitsChecking the indoor unit Control Check items unit operation Serial Communication Error Identification Procedure Alarm Code E05Off Blinking Illuminated Before the OperationTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Trouble Diagnosis of Fan Motor Indoor Fan MotorOutdoor Fan Motor Noise Malfunction and Electromagnetic Interference Noise malfunctionElectromagnetic interference Locations most susceptible to noise Trouble CorrectionPower Supply Cord Checking Electrical ComponentsMeasurement of Insulation Resistance Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy Refrigerant R410A Special Precautions When Servicing Unit Characteristics of New Refrigerant R410AWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tubing Installation Procedures Tools Specifically for R410AProcedure for Replacing Compressor Case of Compressor MalfunctionNever charge a large amount Unit. This may causeDamage to the compressor ExampleCase Refrigerant is Leaking Welding leaking pointsRecharging When Tubes are Extended Charging Additional RefrigerantRetro-Fitting Existing Systems Use of Existing UnitsOI-852-6-4181-149-00-0 Mode D’EMPLOI Pub. OI-85264181149000 SanyoFeatures ContentsAlert Symbols Installation LocationSafety Instructions Product InformationNames of Parts Unit Display and Operation ButtonRemote Control Unit Display SymbolsRemote Control Unit HR. Timer button 1-HOUR OFF Timer Temperature setting buttons TempMode selector button High Power buttonUsing the Remote Control Unit Air conditioner Indoor unit Receiver Remote control unitACL button 16 mmOperation with the Remote Control Unit Automatic OperationCooling and DRY Mode Heating ModeAutomatic fan speed Manual fan speedHigh Power Mode Unoccupied Indication StatusSpecial Remarks Setting the Timer Operation IndicationUsing the 1-HOUR OFF Timer Tips for Energy SavingDo not 1030 pm 710 am 1100 am Present timeAdjusting the Airflow Direction Operation Without the Remote Control UnitCare and Cleaning When the air conditioner is not runningAir Clean Filter How to install the air clean filterHow to clean the air clean filter Cleaning the main unit and remote control unitTroubleshooting Wired Remote ControllerOperating Range Washing the front panel with waterAppendix B Installation Instructions Installation Instructions ContentsPlease Read Before Starting Tools Required for Installation not supplied Accessories Supplied with Unit TableGeneral Optional Copper Tubing KitInstallation Site Selection Additional Materials Required for InstallationSolid base must not cover the hole of the bottom plate Precautions for Installation in a Snowy Area Countermeasures against snow and windUnit inch Installation with intakes facing outlets Required space around the outdoor unitFront and both sides must remain open Unit Top is open Single-unit installation Multiple-unit installation 2 or more unitsObstacle to the front of unit Installation in front-rear rows Obstacles to the front and rear of unitHow to Install the Indoor Unit Trical wiring or conduits areRemove the Rear Panel from the Unit Make a HoleInstall the Rear Panel on the Wall If Wooden WallIf Block, Brick, Concrete or Similar Type Wall Hole DiaRemoving and Installing the Grille How to remove the grilleHow to replace the grille Wiring Instructions General precautions on wiring Shape the Indoor Side TubingWire Size and Length Wiring Instructions for Inter-unit Connections How to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableFor stranded wiring Mounting Right-side tubingSwitching drain hose and drain cap Left-side tubingDrain cap Do not supply power to Tubing and wiring to the outTo unmount indoor unit Frame Fastening MethodHow to Install the Outdoor Unit First refer to . Installation Site SelectionWiring Instructions for the Outdoor Unit Routing the Tubing and WiringFlaring Procedure with a Flare Tool Refrigerant TubingUse of the Flaring Method If the special R410A flare tool is usedConnecting Tubing between Indoor and Outdoor Units Finishing the InstallationInsulation of Refrigerant Tubing Taping the TubesAir Purging Be sure to completely insert Hex wrench beforeAttempting to turn the valve How to Test Run the Air Conditioner Basic Functions of the Service Valves Pump DownService Valve Connections Remote Control Unit Installation PositionAddress Switch Address Setting of the Remote Control Unit