Sanyo KHS3082 + CH3082, KHS3682 + CH3682 Operation Functions, Emergency operation

Page 35

7. FUNCTIONS

7-1. Operation Functions

Emergency operation

Emergency operation is available when the remote controller malfunctions, has been lost, or otherwise cannot be used.

To operate the system, press the OPERATION button, which is also used as the receiver, below the unit display. Each time this button is pressed, the OPERATION lamp changes color to indicate the type of operation. Select the desired type of operation.

COOL

 

HEAT

 

STOP

 

 

(GREEN)

 

(RED)

 

(Lamp Off)

The set temperature is 4°F(2°C) below the detected room temperature in the case of cooling operation, and 4°F(2°C) above the room temperature in the case of heating operation. The flap and fan speed settings are AUTO.

AUTO cooling/heating operation

Selecting the operation mode

When AUTO mode is selected, the microprocessor calculates the difference between the set temperature and the room temperature, and automatically switches to Cooling or Heating mode.

Room temp. Set temp. COOL Room temp. Set temp. HEAT

As shown by the example in the figure below, with AUTO cooling/heating operation, the mode changes between Heating and Cooling mode according to changes in the relationship between the current room temperature and the set temperature.

Example

Example of operation in AUTO mode with the set room temperature at 74°F(23°C).

Room temp.

 

 

 

 

 

 

 

Zone A

 

 

 

 

 

 

 

Zone B

 

 

 

 

 

Set temp.

74

Zone C

 

 

 

 

 

Zone C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zone B

 

More than

 

Within

 

 

 

 

 

 

 

 

 

Zone A

 

1 hour

 

1 hour

 

 

 

Compressor

ON

OFF

ON

OFF

ON

 

Operation mode

 

Cooling

 

Heating

Cooling

SENSOR DRY

During DRY operation, the system adjusts the room temperature and fan speed according to the conditions in the room, in order to maintain a comfortable room environment.

SENSOR DRY operation

DRY operation is as shown in the figure below.

Load

COOL zone

Azone

Bzone

Conditions are monitored at all times when the room temperature is below 59°F(15°C).

DRY A

The compressor operation frequency varies.

The indoor fan operates with 1/f fluctuation.

DRY B

The compressor operates at a low operating frequency. The indoor fan operates with 1/f fluctuation.

Monitor

Monitoring operation takes place when the room temperature is below 59°F(15°C), or more than 5°F(3°C) below the set temperature.

When the monitoring range is entered, the compressor stops, and the indoor fan operates with 1/f fluctuation.

NOTE

The Sensor Dry operation during the Low Ambient Cooling Mode (outside air temperature : 59°F(15°C) or lower) is as follows.

DRY A and DRY B

When room temperature rises above the set temperature, the compressor turns ON. When room temperature falls below the set temperature, the compressor turns OFF.

35

Image 35
Contents Destination North America Indoor Model No. Product Code NoSafety Precautions Prohibit Table of Contents Checking Electrical Components Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeCH3082 SpecificationsUnit Specifications KHS3082208V CH3682 KHS368221.9 19.9 Indoor Unit Major Component SpecificationsCB-KHS3682 Microprocessor 250V 3A Compressor Outdoor UnitOutdoor Unit CH3082 BoardOutdoor Unit CH3682 Other Component Specifications Indoor Unit KHS3082 Dimensional DataInchmm Refrigerant Flow Diagram Refrigerant Flow DiagramIndoor discharge air performance chart Temperature ChartsLow pressure performance chart Operating current performance chartHigh pressure performance chart Wide Outdoor inlet air D.B. temp. FC Indoor Outdoor Cooling CapacityIndoor Cooling Capacity34,000 BTU/h Indoor Power Supply 230V Single Phase 60Hz Cooling CapacityTH Total Heating Capacity BTU/h Power Supply 230V Single Phase 60Hz Heating CapacityHeating Capacity 36,000 BTU/h Heating Vertical distance ft Air Throw Distance ChartsCooling Vertical distance ft Room air temp F 26.7C Fan speed High Horizontal distance ftHeating Voltage208V Cooling Electrical CharacteristicsElectrical Data CH3082 Voltage230V CoolingCH3682 Voltage230V Cooling 8FA2-5250-70400-3 Electric Wiring DiagramsKHS3082 KHS3682 HIC Auto cooling/heating operation FunctionsOperation Functions Emergency operationLamp colors Timer backupOperation Sound Switching Procedure to Noise Reducing ControlNoise Reducing Control Outdoor Unit CH3682 Maximum Current Value Change ProcedureMaximum Current Value Change Function Description of functionFreeze prevention Compressor discharge temperature controlProtective Functions Overload prevention during heatingReverse-Cycle Defrosting Defrost detection and releaseCT Peak current cut-off control Method of Self-Diagnostics TroubleshootingPrecautions before Performing Inspection or Repair Self-diagnostics Lamps Replace the circuit board or the fuse NormalReplace the controller Checking the indoor unit Control Check items unit operation Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Before the Operation Serial Communication Error Identification ProcedureAlarm Code E05 Off Blinking IlluminatedTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Locations most susceptible to noise Trouble Correction Noise Malfunction and Electromagnetic InterferenceNoise malfunction Electromagnetic interferenceMeasurement of Insulation Resistance for Electrical Parts Power Supply CordChecking Electrical Components Measurement of Insulation ResistanceChecking Continuity of Fuse on PCB Assy Characteristics Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A What is New Refrigerant R410A?Checklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorExample Never charge a large amountUnit. This may cause Damage to the compressorRecharging Case Refrigerant is LeakingWelding leaking points Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing SystemsOI-852-6-4181-149-00-0 Pub. OI-85264181149000 Sanyo Mode D’EMPLOIContents FeaturesProduct Information Alert SymbolsInstallation Location Safety InstructionsUnit Display and Operation Button Names of PartsSymbols Remote Control Unit DisplayRemote Control Unit High Power button HR. Timer button 1-HOUR OFF TimerTemperature setting buttons Temp Mode selector button16 mm Using the Remote Control UnitAir conditioner Indoor unit Receiver Remote control unit ACL buttonAutomatic Operation Operation with the Remote Control UnitManual fan speed Cooling and DRY ModeHeating Mode Automatic fan speedUnoccupied Indication Status High Power ModeSpecial Remarks Operation Indication Setting the Timer1030 pm 710 am 1100 am Present time Using the 1-HOUR OFF TimerTips for Energy Saving Do notWhen the air conditioner is not running Adjusting the Airflow DirectionOperation Without the Remote Control Unit Care and CleaningCleaning the main unit and remote control unit Air Clean FilterHow to install the air clean filter How to clean the air clean filterWashing the front panel with water TroubleshootingWired Remote Controller Operating RangeAppendix B Installation Instructions Contents Installation InstructionsPlease Read Before Starting Optional Copper Tubing Kit Tools Required for Installation not suppliedAccessories Supplied with Unit Table GeneralAdditional Materials Required for Installation Installation Site SelectionSolid base must not cover the hole of the bottom plate Countermeasures against snow and wind Precautions for Installation in a Snowy AreaUnit inch Front and both sides must remain open Installation with intakes facing outletsRequired space around the outdoor unit Unit Obstacle to the front of unit Top is open Single-unit installationMultiple-unit installation 2 or more units Obstacles to the front and rear of unit Installation in front-rear rowsMake a Hole How to Install the Indoor UnitTrical wiring or conduits are Remove the Rear Panel from the UnitHole Dia Install the Rear Panel on the WallIf Wooden Wall If Block, Brick, Concrete or Similar Type WallHow to replace the grille Removing and Installing the GrilleHow to remove the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringWire Size and Length Wiring Instructions for Inter-unit Connections For stranded wiring How to connect wiring to the terminal For Indoor UnitFor Outdoor Unit For solid core wiring or F-cable Right-side tubing MountingDrain cap Switching drain hose and drain capLeft-side tubing Frame Fastening Method Do not supply power toTubing and wiring to the out To unmount indoor unitRouting the Tubing and Wiring How to Install the Outdoor UnitFirst refer to . Installation Site Selection Wiring Instructions for the Outdoor UnitIf the special R410A flare tool is used Flaring Procedure with a Flare ToolRefrigerant Tubing Use of the Flaring MethodTaping the Tubes Connecting Tubing between Indoor and Outdoor UnitsFinishing the Installation Insulation of Refrigerant TubingAir Purging Attempting to turn the valve Be sure to completely insertHex wrench before How to Test Run the Air Conditioner Pump Down Basic Functions of the Service ValvesRemote Control Unit Installation Position Service Valve ConnectionsAddress Setting of the Remote Control Unit Address Switch