6. Air Purging

Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely.

pressure in the system rises

operating current rises

cooling (or heating) efficiency drops

moisture in the air may freeze and block capillary tubing

water may lead to corrosion of parts in the refrigerant system

Air Purging with a Vacuum Pump (for Test Run)

(1)Check that each tube (both narrow and wide tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.

(2)Using an adjustable wrench or box wrench, remove the valve caps from the service valve on both nar- row and wide tubes.

(3)Connect a vacuum pump and a manifold valve (with pressure gauges) to the service port on the wide tube service valve. (Fig. 57)

 

CAUTION

The service port on the wide tube

 

 

 

service valve uses a Schrader core

 

 

 

 

 

 

valve to access the refrigerant sys-

 

 

 

tem. The valve core is similar to

 

 

 

those used in automobile tires.

 

 

 

Therefore, be sure to use a vacuum

 

 

 

hose connector which has a push-

 

 

 

pin inside.

 

 

 

Be sure to use a manifold valve

 

CAUTION

 

 

for air purging. If it is not avail-

 

 

 

 

 

 

 

 

able, use a stop valve (field sup-

 

 

 

ply) for this purpose. The “Hi”

 

 

 

knob of the manifold valve must

 

 

 

always be kept closed.

(4)With the “Lo” knob of the manifold valve open, run the vacuum pump. The operation time for the vacu- um pump varies with tubing length and the capacity of the pump. The following table shows the amount of time for evacuation:

Table 7

Required time for evacuation when 100 liter/h vacuum pump is used

If tubing length is

If tubing length is

less than 33 ft. (10 m)

more than 33 ft. (10 m)

 

 

10 min. or more

15 min. or more

 

 

Indoor unit

Outdoor unit

Manifold valve (Exclusively for R410A)

Pressure

Lo

Hi

gauge

 

 

Charging hose

(Exclusively for R410A)

Vacuum pump adapter (Exclusively for R410A)

(with reverse flow prevention)

Vacuum pump

Fig. 57

NOTE

To prevent other refrigerants from being mistakenly charged to units which use R410A, the size of the charge port on the service valve is different from the one for other refrigerant types. For servicing such as recharging, the specified charging hose, manifold and vacuum pump adapter (with reverse flow prevention) for R410A must be used.

NOTE

The required time in Table 7 is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs.

25

Image 103
Contents Destination North America Indoor Model No. Product Code NoSafety Precautions Prohibit Table of Contents Checking Electrical Components Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeCH3082 SpecificationsUnit Specifications KHS3082208V CH3682 KHS368221.9 19.9 Indoor Unit Major Component SpecificationsCB-KHS3682 Microprocessor 250V 3A Compressor Outdoor UnitOutdoor Unit CH3082 BoardOutdoor Unit CH3682 Other Component Specifications Indoor Unit KHS3082 Dimensional DataInchmm Refrigerant Flow Diagram Refrigerant Flow DiagramIndoor discharge air performance chart Temperature ChartsLow pressure performance chart Operating current performance chartHigh pressure performance chart Wide Outdoor inlet air D.B. temp. FC Indoor Outdoor Cooling CapacityIndoor Cooling Capacity34,000 BTU/h Indoor Power Supply 230V Single Phase 60Hz Cooling CapacityHeating Capacity Power Supply 230V Single Phase 60Hz Heating CapacityTH Total Heating Capacity BTU/h 36,000 BTU/h Heating Vertical distance ft Air Throw Distance ChartsCooling Vertical distance ft Room air temp F 26.7C Fan speed High Horizontal distance ftHeating Voltage208V Cooling Electrical CharacteristicsElectrical Data CH3082 Voltage230V CoolingCH3682 Voltage230V Cooling KHS3082 KHS3682 Electric Wiring Diagrams8FA2-5250-70400-3 HIC Auto cooling/heating operation FunctionsOperation Functions Emergency operationLamp colors Timer backupNoise Reducing Control Outdoor Unit Switching Procedure to Noise Reducing ControlOperation Sound CH3682 Maximum Current Value Change ProcedureMaximum Current Value Change Function Description of functionFreeze prevention Compressor discharge temperature controlProtective Functions Overload prevention during heatingCT Peak current cut-off control Defrost detection and releaseReverse-Cycle Defrosting Precautions before Performing Inspection or Repair TroubleshootingMethod of Self-Diagnostics Self-diagnostics Lamps Replace the controller NormalReplace the circuit board or the fuse Checking the Indoor and Outdoor Units Using the TEST/T-RUN terminalsChecking the indoor unit Control Check items unit operation Before the Operation Serial Communication Error Identification ProcedureAlarm Code E05 Off Blinking IlluminatedTerminal board Outdoor Unit Alarm Code E07/P04/P05/P20/P27 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Locations most susceptible to noise Trouble Correction Noise Malfunction and Electromagnetic InterferenceNoise malfunction Electromagnetic interferenceMeasurement of Insulation Resistance for Electrical Parts Power Supply CordChecking Electrical Components Measurement of Insulation ResistanceChecking Continuity of Fuse on PCB Assy Characteristics Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A What is New Refrigerant R410A?Checklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorExample Never charge a large amountUnit. This may cause Damage to the compressorWelding leaking points Case Refrigerant is LeakingRecharging Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing SystemsOI-852-6-4181-149-00-0 Pub. OI-85264181149000 Sanyo Mode D’EMPLOIContents FeaturesProduct Information Alert SymbolsInstallation Location Safety InstructionsUnit Display and Operation Button Names of PartsSymbols Remote Control Unit DisplayRemote Control Unit High Power button HR. Timer button 1-HOUR OFF TimerTemperature setting buttons Temp Mode selector button16 mm Using the Remote Control UnitAir conditioner Indoor unit Receiver Remote control unit ACL buttonAutomatic Operation Operation with the Remote Control UnitManual fan speed Cooling and DRY ModeHeating Mode Automatic fan speedUnoccupied Indication Status High Power ModeSpecial Remarks Operation Indication Setting the Timer1030 pm 710 am 1100 am Present time Using the 1-HOUR OFF TimerTips for Energy Saving Do notWhen the air conditioner is not running Adjusting the Airflow DirectionOperation Without the Remote Control Unit Care and CleaningCleaning the main unit and remote control unit Air Clean FilterHow to install the air clean filter How to clean the air clean filterWashing the front panel with water TroubleshootingWired Remote Controller Operating RangeAppendix B Installation Instructions Contents Installation InstructionsPlease Read Before Starting Optional Copper Tubing Kit Tools Required for Installation not suppliedAccessories Supplied with Unit Table GeneralAdditional Materials Required for Installation Installation Site SelectionSolid base must not cover the hole of the bottom plate Countermeasures against snow and wind Precautions for Installation in a Snowy AreaUnit inch Required space around the outdoor unit Installation with intakes facing outletsFront and both sides must remain open Unit Multiple-unit installation 2 or more units Top is open Single-unit installationObstacle to the front of unit Obstacles to the front and rear of unit Installation in front-rear rowsMake a Hole How to Install the Indoor UnitTrical wiring or conduits are Remove the Rear Panel from the UnitHole Dia Install the Rear Panel on the WallIf Wooden Wall If Block, Brick, Concrete or Similar Type WallHow to remove the grille Removing and Installing the GrilleHow to replace the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringWire Size and Length Wiring Instructions for Inter-unit Connections For Outdoor Unit For solid core wiring or F-cable How to connect wiring to the terminal For Indoor UnitFor stranded wiring Right-side tubing MountingLeft-side tubing Switching drain hose and drain capDrain cap Frame Fastening Method Do not supply power toTubing and wiring to the out To unmount indoor unitRouting the Tubing and Wiring How to Install the Outdoor UnitFirst refer to . Installation Site Selection Wiring Instructions for the Outdoor UnitIf the special R410A flare tool is used Flaring Procedure with a Flare ToolRefrigerant Tubing Use of the Flaring MethodTaping the Tubes Connecting Tubing between Indoor and Outdoor UnitsFinishing the Installation Insulation of Refrigerant TubingAir Purging Hex wrench before Be sure to completely insertAttempting to turn the valve How to Test Run the Air Conditioner Pump Down Basic Functions of the Service ValvesRemote Control Unit Installation Position Service Valve ConnectionsAddress Setting of the Remote Control Unit Address Switch