Sanyo KS1872 Refrigerant Tubing, Use of the Flaring Method, Flaring Procedure with a Flare Tool

Page 18

5. Refrigerant Tubing

5-1. Use of the Flaring Method

Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.

5-2. Flaring Procedure with a Flare Tool

(1)Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 12" to 20" (30 to 50 cm) longer than the tubing length you estimate.

(2)Remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare.

(Fig. 47)

NOTE

When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 48)

(3)Remove the flare nut from the unit and be sure to mount it on the copper tube.

(4)Make a flare at the end of copper tube with a flare tool.* (Figs. 49a and 49b)

(*Use “RIGID” or equivalent.)

NOTE

A good flare should have the following characteristics:

inside surface is glossy and smooth.

edge is smooth.

tapered sides are of uniform length.

5-3. Caution before Connecting Tubes Tightly

a)Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used.

b)Be sure to apply refrigerant lubricant to the match- ing surfaces of the flare and union before connect- ing them together. This is effective for reducing gas leaks. (Fig. 50)

c)For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 51)

Deburring

Before

After

Fig. 47

Copper tubing

Reamer

 

 

 

Fig. 48

If the special R410A

If the previous flare tool

flare tool is used:

(clutch-type) is used:

 

 

0 to 0.0196"

 

 

0.0472" (1.2 mm)

 

 

 

 

 

 

(0 to 0.5 mm)

Adjust so that the amount of tube

 

 

 

 

 

 

protrusion is as shown in the figure.

Fig. 49a

Flare nut

Copper tubing

Flare tool

Fig. 49b

Apply refrigerant lubricant here and here

Fig. 50

Union

Flare nut

Fig. 51

18

Image 18
Contents Installation Instructions Contents…In a Room For safe installation and trouble-free operation, you must…In a Ceiling or Wall …In Moist or Uneven LocationsGeneral Tools Required for Installation not suppliedAccessories Supplied with Unit Table Optional Copper Tubing KitInstallation Site Selection Additional Materials Required for InstallationIndoor Unit Outdoor Unit C1872, CL1872C2472, CL2472 Baffle Plate for the Outdoor Unit CLxx models only Remove the Rear Panel from the Unit How to Install the Indoor UnitTrical wiring or conduits are Make a HoleInstall the Rear Panel on the Wall If Wooden WallIf Block, Brick, Concrete or Similar Type Wall Remove the Grille to Install the Indoor Unit How to remove the grilleHow to replace the grille Wiring Instructions General precautions on wiring Shape the Indoor Side TubingRecommended Wire Length and Diameter AWGWiring Instructions for Inter-unit Connections How to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableFor stranded wiring Mounting Right-side tubingDrain hose Switching drain hose and drain capLeft-side tubing Drain capTo unmount indoor unit Do not supply power toTubing and wiring to the out Unit or operate it until allHow to Install the Outdoor Unit Wiring Instructions for the Outdoor UnitFlaring Procedure with a Flare Tool Refrigerant TubingUse of the Flaring Method Connecting Tubing between Indoor and Outdoor Units Finishing the InstallationInsulation of Refrigerant Tubing Air Purging Be sure to completely insert Hex wrench beforeHow to Test Run the Air Conditioner Basic Functions of the Service Valves Pump DownRemote Control Unit Installation Position To take out the remote control unit, pull it forwardMounting on a Wall Address Switch Address Setting of the Remote Control Unit