Sanyo KS1872 installation instructions Basic Functions of the Service Valves, Pump Down

Page 23

Basic Functions of the Service Valves

The basic functions of the service valves are given in Table 8 below.

Table 8

Action

Narrow Tube Service

Wide Tube Service

Valve (2-Way)

Valve (3-Way)

 

 

CLOSED

O-ring

Valve cap

 

 

 

Stem

Shipping

Fully OPEN

Operating and test running

the air conditioner

 

Fully OPEN

 

Measuring pressure

*

 

and gas charging

 

 

 

CLOSED

 

 

*

The service port on the wide tube ser-

Air purging with

*

vice valve uses a Schrader core valve

a vacuum pump

 

to access the refrigerant system.

 

 

Therefore, be sure to use a hose con-

 

 

nector which has a push-pin inside.

 

 

(Fig. 60a)

Service valve

CAUTION

Hose with push-pin

 

 

Close

When opening or clos-

ing the service valve

 

PUSH

Open

 

stem, use the accessory

 

Hex

Fig. 60a

hex wrench. Be sure to

wrench

 

 

 

fully seat the wrench

Fig. 60b

 

before turning the valve.

 

 

Pump Down

Pump down means collecting all refrigerant gas in the system back into the outdoor unit without losing any of the gas. Pump down is used when the unit is to be moved or before servicing the refrigerant circuit.

Pump Down Procedure

Be sure to carry out pump down with the unit in cooling mode.

(1)Connect the Lo side charging hose of the manifold valve to the service port on the wide tube service valve.

(2)Using a hex wrench, turn the narrow tube service valve clockwise all the way to close the service valve. (Be sure to confirm that the wide tube service valve is fully open.)

(3)Press the operation button and start cooling oper- ation.

(4)When the low pressure gauge reading falls to 14.2 to 7.1 psi (1 to 0.5 kg/cm2), fully close the wide tube valve stem. Then quickly stop the unit.

(5)Disconnect all gauges and hoses, and replace the valve caps as they were before.

23

Image 23
Contents Contents Installation Instructions…In Moist or Uneven Locations For safe installation and trouble-free operation, you must…In a Ceiling or Wall …In a RoomOptional Copper Tubing Kit Tools Required for Installation not suppliedAccessories Supplied with Unit Table GeneralIndoor Unit Installation Site SelectionAdditional Materials Required for Installation C2472, CL2472 Outdoor UnitC1872, CL1872 Baffle Plate for the Outdoor Unit CLxx models only Make a Hole How to Install the Indoor UnitTrical wiring or conduits are Remove the Rear Panel from the UnitIf Block, Brick, Concrete or Similar Type Wall Install the Rear Panel on the WallIf Wooden Wall How to replace the grille Remove the Grille to Install the Indoor UnitHow to remove the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringAWG Recommended Wire Length and DiameterWiring Instructions for Inter-unit Connections For stranded wiring How to connect wiring to the terminal For Indoor UnitFor Outdoor Unit For solid core wiring or F-cable Right-side tubing MountingDrain cap Switching drain hose and drain capLeft-side tubing Drain hoseUnit or operate it until all Do not supply power toTubing and wiring to the out To unmount indoor unitWiring Instructions for the Outdoor Unit How to Install the Outdoor UnitUse of the Flaring Method Flaring Procedure with a Flare ToolRefrigerant Tubing Insulation of Refrigerant Tubing Connecting Tubing between Indoor and Outdoor UnitsFinishing the Installation Air Purging Hex wrench before Be sure to completely insertHow to Test Run the Air Conditioner Pump Down Basic Functions of the Service ValvesMounting on a Wall Remote Control Unit Installation PositionTo take out the remote control unit, pull it forward Address Setting of the Remote Control Unit Address Switch