Sanyo KS1872 installation instructions Be sure to completely insert, Hex wrench before

Page 21

(5)With the vacuum pump still running, close the “Lo” knob of the manifold valve. Then stop the vacuum pump.

(6)With the accessory hex wrench, turn the valve stem on the narrow tube service valve counter-clockwise by 90 degrees (1/4 turn) for 10 seconds, and then turn the stem clockwise to close it again. (Fig. 58)

CAUTION

Be sure to completely insert

the hex wrench before

 

 

attempting to turn the valve.

(7)Leak test all joints at the tubing (both indoor and out- doors) with soapy water. Bubbles indicate a leak. Tight- en the joint more when leaks, then check if there is no leak. Be sure to wipe off the soap with a clean cloth.

(8)With the hex wrench, turn the wide tube service valve stem counter-clockwise to fully open the valve.

(9)Turn the narrow tube service valve stem counter- clockwise to fully open the valve.

(10)Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure. Then, remove the hose.

CAUTION This may cause the refriger- ant gas to leak. In order to avoid this, take off the hose quickly.

(11)Fasten the valve cap on the wide tube service port securely with an adjustable wrench or box wrench. Next, mount the valve cap on the service valve and tighten it to 170 lbs·in (200 kgf·cm) with a torque wrench. This process is very important to prevent gas from leaking from the system.

(12)Test run the air conditioner. (See next page.)

(13)While the air conditioner is running, apply liquid soap to check for any gas leaks around the service valves or caps.

(14)If there is no leakage, stop the air conditioner.

(15)Wipe off the soap on the tubing.

This completes air purging with a vacuum pump and the air conditioner is ready for actual operation.

90° (1/4 turn)

Narrow tube

Hex wrench

Wide tube

Valve cap

Vacuum hose to manifold valve

Fig. 58

21

Image 21
Contents Contents Installation Instructions…In a Ceiling or Wall For safe installation and trouble-free operation, you must…In a Room …In Moist or Uneven LocationsAccessories Supplied with Unit Table Tools Required for Installation not suppliedGeneral Optional Copper Tubing KitInstallation Site Selection Additional Materials Required for InstallationIndoor Unit Outdoor Unit C1872, CL1872C2472, CL2472 Baffle Plate for the Outdoor Unit CLxx models only Trical wiring or conduits are How to Install the Indoor UnitRemove the Rear Panel from the Unit Make a HoleInstall the Rear Panel on the Wall If Wooden WallIf Block, Brick, Concrete or Similar Type Wall Remove the Grille to Install the Indoor Unit How to remove the grilleHow to replace the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringAWG Recommended Wire Length and DiameterWiring Instructions for Inter-unit Connections How to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableFor stranded wiring Right-side tubing MountingLeft-side tubing Switching drain hose and drain capDrain hose Drain capTubing and wiring to the out Do not supply power toTo unmount indoor unit Unit or operate it until allWiring Instructions for the Outdoor Unit How to Install the Outdoor UnitFlaring Procedure with a Flare Tool Refrigerant TubingUse of the Flaring Method Connecting Tubing between Indoor and Outdoor Units Finishing the InstallationInsulation of Refrigerant Tubing Air Purging Hex wrench before Be sure to completely insertHow to Test Run the Air Conditioner Pump Down Basic Functions of the Service ValvesRemote Control Unit Installation Position To take out the remote control unit, pull it forwardMounting on a Wall Address Setting of the Remote Control Unit Address Switch