Sanyo KS1872 Connecting Tubing between Indoor and Outdoor Units, Insulation of Refrigerant Tubing

Page 19

5-4. Connecting Tubing between Indoor and Outdoor Units

a)Tightly connect the indoor side refrigerant tubing exten- ded from the wall with the outdoor side tubing. (Fig. 52)

b)To fasten the flare nuts, apply specified torque as:

Table 6

Tube Dia.

Tightening Torque

 

 

1/4" (6.35 mm)

Approx. 120 – 160 lbs·in (140 – 180 kgf·cm)

 

 

3/8" (9.52 mm)

Approx. 300 – 360 lbs·in (340 – 420 kgf·cm)

 

 

1/2" (12.70 mm)

Approx. 430 – 540 lbs·in (490 – 610 kgf·cm)

 

 

5/8" (15.88 mm)

Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)

 

 

5-5. Insulation of Refrigerant Tubing

IMPORTANT

To prevent heat loss and wet floors due to dripping of con-

densation, both tubes must be well insulated with a proper insulation material. (Fig. 53)

The thickness of the insulation should be a minimum 5/16" (8 mm). (Fig. 54)

Torque wrench

Spanner

Indoor unit

Outdoor unit

Fig. 52

 

Insulation

 

Fig. 53

 

Insulation

 

Thickness:

Min.

min. 5/16"

5/16"

(8 mm)

(8 mm)

 

5-6. Taping the Tubes

CAUTION

After a tube has been insulat- ed, never try to bend it into a narrow curve, as this may cause the tube to break or crack.

Fig. 54

(1)At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.

(2)Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 55)

(3)Clamp the tubing bundle to wall, using 1 clamp approx. every 47" (120 cm).

NOTE

Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the con- densation drain hose splits away from the bundle and drips clear of the unit and the tubing.

5-7. Finishing the Installation

After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 56)

Clamp

Insulated tubes

Fig. 55

Apply putty here

Tubing

Fig. 56

19

Image 19
Contents Contents Installation Instructions…In Moist or Uneven Locations For safe installation and trouble-free operation, you must…In a Ceiling or Wall …In a RoomOptional Copper Tubing Kit Tools Required for Installation not suppliedAccessories Supplied with Unit Table GeneralAdditional Materials Required for Installation Installation Site SelectionIndoor Unit C1872, CL1872 Outdoor UnitC2472, CL2472 Baffle Plate for the Outdoor Unit CLxx models only Make a Hole How to Install the Indoor UnitTrical wiring or conduits are Remove the Rear Panel from the UnitIf Wooden Wall Install the Rear Panel on the WallIf Block, Brick, Concrete or Similar Type Wall How to remove the grille Remove the Grille to Install the Indoor UnitHow to replace the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringAWG Recommended Wire Length and DiameterWiring Instructions for Inter-unit Connections For Outdoor Unit For solid core wiring or F-cable How to connect wiring to the terminal For Indoor UnitFor stranded wiring Right-side tubing MountingDrain cap Switching drain hose and drain capLeft-side tubing Drain hoseUnit or operate it until all Do not supply power toTubing and wiring to the out To unmount indoor unitWiring Instructions for the Outdoor Unit How to Install the Outdoor UnitRefrigerant Tubing Flaring Procedure with a Flare ToolUse of the Flaring Method Finishing the Installation Connecting Tubing between Indoor and Outdoor UnitsInsulation of Refrigerant Tubing Air Purging Hex wrench before Be sure to completely insertHow to Test Run the Air Conditioner Pump Down Basic Functions of the Service ValvesTo take out the remote control unit, pull it forward Remote Control Unit Installation PositionMounting on a Wall Address Setting of the Remote Control Unit Address Switch