Relay/Transformer (R/T Box)
Standard Transition
Each MX250 microprocessor based ATS controller requires a relay/transformer box to apply line voltage to the ATS operator via coil control relays. Also required is power for the MX150 printed circuit board and an appli- cation of sensing voltage proportional to line voltage. This is accomplished by the relay transformer box. This method of switching operator voltage and applying power and sensing voltage to the printed circuit board isolates
1
2
(inside)
3
Figure 12
40-225 Amp Molded Power Section
Transformer Usage (see Figure 12)
R/T Box | Primary | 1 VA | 25 VA |
Assembly | Voltage | XFMR | XFMR |
Part No. | at 50/60 Hz | Part No. | Part No. |
|
|
|
|
120V | |||
277V | |||
|
|
|
|
Bill of Material
Item | Part No. | Description | Qty |
|
|
|
|
1 | See Chart | Transformer (1 VA) | 2 |
2 | See Chart | Transformer (25 VA) | 2 |
3 | Relay Flange Mounted | 2 | |
|
|
|
|
the MX250 from the line voltage, further protecting
the controller from harmful line transients. Two versions of the R/T box exist depending on the type of ATS (standard transition or delayed transition).
The following layout drawings of the R/T Box compo- nents (standard and delayed transition) include a bill of materials for replacement parts. Schematics are included to indicate proper wiring.
PRI. | PRI. |
PRI. |
|
SEC. |
| 1 |
SEC. | SEC. |
|
2
3
Figure 13
40-3000 Amp - All Other Standard Types
Transformer Usage (see Figure 13)
R/T Box | Primary | 1 VA | 25 VA |
Assembly | Voltage | XFMR | XFMR |
Part No. | at 50/60 Hz | Part No. | Part No. |
|
|
|
|
120V | |||
277V | |||
|
|
|
|
Bill of Material
Item | Part No. | Description | Qty |
|
|
|
|
1 | See Chart | Transformer (25 VA) | 2 |
2 | See Chart | Transformer (1 VA) | 2 |
3 | Coil Control Relay (24V) | 2 | |
|
|
|
|
■ 26 | GE Zenith Controls ■ |