Accessory Definitions (cont’d)
M1
Single Phase Amp Meter
M2
Three Phase Amp Meter
M80
3000 Digital Power Monitor
M82
5200 Digital Power Meter
M83A
EPM 5300 Digital Power Meter with Modbus Port
M83B
EPM 5350 Digital Power Meter with Ethernet Port
M84
7430 Digital Power Meter , Wye or Delta
M85A
EPM 9450 Digital Power Meter, Ethernet
M85B
EPM 9450 Digital Power Meter with Internal 56K Mod.
M86A
EPM 9650 Digital Power Meter, Wye or Delta, RS232 or RS485
M86B
EPM 9650 Digital Power Meter, Wye or Delta, RS232 or RS485
N1
Running Time Meter, Door mount
N2
Operation Counter, Door Mount
P1
Time Delay Source 2 Start. Adjustable
Adjust via SET menu (see page 18)
P2
Time Delay S2 Start. Adjustable 1/6 to 300 seconds.
Q2
Remote Peak Shave or Area Protection Circuit. Energize Q2 to simulate Source 1 Line failure causing the Generator to start and transfer the load to Source 2. Should Emergency fail during this operation, Transfer Switch will retransfer back to Source 1.
Q3
Remote inhibit transfer to Source 2 circuit. Energize Q3 input to allow transfer to Source 2. To enable Q3 option, engage Q3 jumper.
Q7
Inhibit transfer to Source 1 circuit. Energize Q7 input to prevent transfer to Source 1.
R1-1/R1-3
Source 1 Over Voltage sensing for single and three phase systems.
Source 1 Over Voltage "Fail" Factory Default: 110%
This adjustment determines the maximum acceptable over voltage. Adjust via the SET menu. Range is 105% to 110% in 1% increments (see page 18).
Once exceeded, the P timer begins timing to signal the Generator to start.
Source 1 Over Voltage "Restore" Factory Default: 105%
This adjustment determines the minimum acceptable over Voltage threshold at which the Transfer Switch is allowed to automatically transfer to Source 1. Adjust via SET menu. Range is 103% to 108% in 1% increments. "Restore" must be a minimum of 2% below "Fail" setting (see page 18).
R15/R15D
Load Shed
Should Source 2 become overloaded, a signal
can be given to switch to the dead or Mid position.
R16
Phase Rotation Sensing
Can be turned on or off via CFG menu (see page 17). Factory Default is on.
This feature prevents Line Source to Line Source trans- fers from occurring between dissimilar phase sequences. This condition is primarily caused by an installation error. Connections from Source 1 and Source 2 need be verified, compared, and corrected to remedy the inconsistent phase rotation between the sources. WARNING: Turning off this feature can cause
severe damage to loads.
R26
Interruptable Power Rate Provisions.
Allow transfer out of Source 1 position to Source 2 or dead Source 2. Alarm and
R50
In Phase Monitor this feature restricts Live to Live Source Transfers to occur unless both Sources are within 7 electrical degrees or less of each other. (live Source to live Source transfers usually occur during transfer back to Source 1 or during Testing). R50 does not change the operation of the Automatic Transfer Switch in a power failure mode. After all timer functions have elapsed, the CHECKING FOR SOURCE SYNCHRO- NISM will be displayed as well as the direction of transfer
■ 12 | GE Zenith Controls ■ |