NOTE: Water column pressure requirements (measured at the pressure tap on the gas valve body):

Natural Gas - 3.5 inches water column (W.C.) - 8.7 mb.

L.P. Gas - 10.5 inches water column (W.C.) - 26.1 mb.

6.If computer program changes are required, refer to the Phase 6 OPL User’s Manual (ADC Part No. 113022) for details.

7.The dryer should be operated through one complete cycle to assure that no further adjustments are necessary and that ALL components are functioning properly.

8.Check the electric service phase sequence. While the dryer is operating, check to see if the blower wheel is rotating in the proper direction. Looking from the front, the blower wheel should spin in the clockwise (CW) direction. If so, the phasing is correct. If the phasing is incorrect, reverse two (2) leads at connections L1, L2, or L3 of power supply to the dryer.

9

Image 13
Contents American Dryer Corporation ML-130Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Content Phase 6 OPL System Diagnostics Important Information Safety PrecautionsStandards Cleaning Routine MaintenanceMATERIALS, GASOLINE, and Their Flammable Vapors Lubrication AdjustmentsENCLOSURE, AIR SUPPLY, and Exhaust Requirements Installation RequirementsElectrical and GAS Requirements Operational Service Check Procedure Page Control BOX Description of PartsDrive Motor HSI HOT Surface Ignition Module Gas Models OnlyIdler Assembly GAS Burner AssemblyBlower Motor and Impellor Tumbler Basket Bearing and Pulley Arrangement Main Door SwitchTumbler Basket Manual Reset Thermostat Sail Switch Gas and Electric Models OnlyHI-LIMIT Gas and Electric Models Only Lint Drawer Lint Drawer SwitchSteam Damper System Introduction ServicingComputer Controls To Replace Computer Control PanelTo Replace Microprocessor Temperature Sensor Probe To Replace Keyboard Touchpad Label AssemblyTo Replace Computer To Remove Hot Surface Ignitor refer to illustration above Ignition ControlsHSI Ignitor Flame Sensor Probe To Remove Flame Sensor ProbeTo Replace Main Burner Orifices To Test and Adjust Gas Water Column PressureTo Convert from Natural Gas to L.P. Gas To Replace HSI Hot Surface Ignition Module To Replace Burner TubesThermostats Page To Replace Sail Switch Sail Switch Assembly Gas and Electric Models OnlyTo Adjust Sail Switch Personal Injury or Fire could ResultTo Install New Main Door Glass To Replace Main Door AssemblyTo Replace Main Door Hinge Block To Replace Front PanelTo Replace Tumbler Basket Pulley PulleysTo Replace Small Idler Pulley To Replace Motor Pulley To Replace Large Idler PulleyTumbler Basket Alignment Vertical Up and Down Adjustment Tumbler Basket AssemblyTo Replace Tumbler Basket or Tumbler Basket Support Tumbler Basket Alignment Lateral Side to Side AdjustmentTo Replace Front Tumbler Basket Support Pillow Block Bearing To Replace Rear Idler Shaft Pillow Block Bearing To Replace Front Idler Shaft Pillow Block BearingBelt Tension Adjustment Motor to Idler Belt Tension Adjustment Tumbler Basket to IdlerBelts To Replace V-BeltsTo Replace Drive Motor MotorsTo Replace Impellor Motor Fan Shaft Drive To Replace Lint Drawer Switch Lint Drawer Assembly To Replace Lint ScreenImpellor No display on computer TroubleshootingComputer will not accept keyboard touchpad entries Dryer operates but is taking too long to dry Dryer will not start, but computer display indicators are onThermal overload for drive motor is tripping Burner hi-limit safety thermostat is trippingOverload for impellor fan motor is tripping There is excessive vibration coming from the tumbler basket Diagnostic L.E.D. light emitting diode Display Failure Codes Phase 6 OPL System DiagnosticsPage E.D. Display Indicator Number E.D. light emitting diode Display IndicatorsE.D. Display Indicator Number AIR AIR JET Output L.E.D. Indicator Optional FAN Blower Output L.E.D. IndicatorHT1 Heat Output L.E.D. Indicator Lint Lint Door Input L.E.D. Indicator Fuse Main Fuse Input L.E.D. IndicatorMain Main Door Input L.E.D. Indicator Power Supply Input L.E.D. Indicator Flame bURNER Control Fail Input L.E.D. IndicatorALL REV E.D. Codes 1. Display CodesGAS/ELECTRIC only BURNER/OVEN Open HI-LIMIT Circuit GAS Models only Power 24 VAC is not Evident AT GAS ValveGAS only Ignition Attempt Failure Computer Logic and Wiring Diagram Page Drive motor reverses but does not forward, blower motor runs No Display ConditionLint Door Condition Blower motor does not operate, drive motor runsMicroprocessor Computer Main Door ConditionFor Phase 6 Models Manual Reset HI-LIMIT InstructionsMotor Plate High and LOW Voltage Technical InformationInformation on the Data Label Data LabelHOW to USE a Manometer Tool List ADC450428 1- 02/22/00-25