4On the UPS status summary screen, press the button to check for active alarms or notices. Resolve any active alarms before continuing. See “Troubleshooting” on page 66.

If there are no active alarms, a “No Active Alarms” message appears.

5Verify that the Normal mode icon appears on the UPS status summary screen, indicating that the UPS is operating normally and any loads are powered.

Starting the UPS on Battery

NOTE: Before using this feature, the UPS must have been powered by utility power with output enabled at least once.

NOTE: Utility power cannot be present at startup.

To start the UPS on battery:

1Press the button on the UPS front panel until the UPS beeps.

The UPS front panel display illuminates, and the UPS begins the startup sequence.

The UPS cycles through Standby mode to Battery mode. The Battery mode icon displays on the UPS status summary screen. The UPS supplies power to your equipment.

NOTE: The UPS does not assume the load if you press the button less than three seconds.

2Press the button to check for active alarms or notices.

Ignore the “UPS on Battery” notice and notices that indicate missing utility power. Resolve other active alarms before continuing. See “Troubleshooting” on page 66. After correcting the alarms, restart if necessary.

You can prevent a battery start (requiring utility power at the next startup) by simultaneously pressing the and buttons for three seconds. Battery start can be disabled. See the Start on Battery setting on page 42.

UPS Shutdown

To shut down the UPS:

1Press the button on the front panel for three seconds.

The UPS begins to beep. The UPS transfers to Standby mode.

NOTE: Releasing the button before three seconds returns the UPS to its original operating state.

2Switch off utility power where the UPS is connected.

After utility power is removed, the UPS fully shuts down in ten seconds.

32 Operation

Image 32
Contents Users Guide July 2013 S 164201788 Table of Contents RS-232 and USB Communication Ports Dell UPS Management SoftwareTesting Batteries UPS Status Menu Event Log MenuIntroduction Dell Online Rack UPSIntroduction Finding Information What are You Looking For? Find It HereSafety Warnings UPS Output PowerSafety Warnings Do not add weight to slide/rail mounted equipment Installation Inspecting the EquipmentUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet Identifying the UPS Rear Panels 120V Rear PanelIdentifying the UPS Front Panel 230V Rear PanelRackmount Setup Opening the Metal Battery CoverIf installing additional UPSs, repeat for each cabinet Positioning the Rails Attaching the Rails to the Rack Installing and Securing the Cabinet Installing the Battery Tray Install the UPS front cover see Figure Installing the EBM Removing the Battery Connector CoverInstalling the Strain Relief Bracket Installing the UPS EBM InstallationInstalling Remote Emergency Power-off Repo Connections Wire FunctionRepo Connector UPS Initial Startup Minimum Upstream Circuit Breaker Rating UPS Output PowerPower Cord Ratings Installation Starting the UPS OperationUPS Startup and Shutdown Starting the UPS on Battery UPS ShutdownControl Panel Functions Control Button Functions Control Button SequenceStartup Screen Changing the LanguageDisplay Functions Screen Locked UPS StatusBattery Mode Bypass ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveStatus Summary Screens Description Battery Test Status Normal ModeHigh Efficiency Mode Converter ModeBattery Status Screens Description Event LogMeasurements Control Screens Control Screens DescriptionIdentification SettingsSettings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Normal to Bypass Mode Transferring the UPS Between ModesSetting Power Strategy Transferring from Bypass to Normal ModeRetrieving the Event Log Behavior on OverloadConfiguring Load Segments Controlling Load Segments Through the DisplayConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring Battery Settings Configuring the UPS for an EBMConfiguring Automatic Battery Tests Configuring Automatic RestartRunning Automatic Battery Tests Additional UPS Features RS-232 and USB Communication PortsRS-232 Communication Port Pin Assignment GNDDell Network Management Card Optional Dell Network Management CardDell UPS Management Software Transporting the UPS UPS MaintenanceUPS and Battery Care Remove the UPS front cover see Figure Disconnect the internal battery connectors see Figure When to Replace Batteries Storing the UPS and BatteriesTesting Batteries Updating the UPS FirmwareSpecifications Power Levels Rated at nominal inputs Regulation Normal modeRegulation Battery mode Environmental and SafetyBattery Configuration Battery RuntimesVoltage FusesUPS Status Menu TroubleshootingAccessing Alarms and Conditions Typical Alarms and Conditions Event Log MenuAction Troubleshooting Troubleshooting Silencing the Alarm