Dell 2700W manual Control Screens Description

Page 40

Control Screens

Table 6 describes the available control screens.

Table 6. Control Screens

Control Screens

Description

 

 

Go to Bypass

Transfers the UPS system to internal Bypass mode.

 

When the Go to Bypass command is issued, the screen immediately shows the

 

message for five seconds: Manual Bypass Command. The option then changes to

 

Go to Normal.

 

When the Go to Normal command is issued, the screen immediately shows the

 

message Normal Mode Command Sent for five seconds. The option then changes

 

to Go to Bypass.

 

 

Battery Test

Schedule Battery Test: yes Cancel Battery test: no

 

Starts a manual battery test.

 

See “Testing Batteries” on page 62.

 

 

Reset Error State

Reset Alarms: yes no

 

Manually clears any latched alarms, such as bad battery detected or DC Bus

 

OV/UV.

 

If a bad battery alarm was also active, reset the battery test status to “Not

 

Tested.”

 

 

Load Segments

Load segment 1: on off

 

Load segment 2: on off

 

These on/off commands override automatic load segment on/off controls made by

 

the Automatic Start Delay and Automatic On Battery Shutdown settings. See

 

“Configuring Load Segments” on page 49.

 

 

Restore Factory Settings

Restore Factory Settings: yes no

 

Available only in Standby mode.

 

Restoring the factory settings:

 

S

Returns all user-configurable EEPROM settings to default factory settings

 

S

Resets all pending on/off commands

 

S

Clears the Event Log and resets all time stamps

 

S

Resets the battery test status

 

S

Initiates the Self Diagnostics test

 

 

 

40 Operation

Image 40
Contents Users Guide July 2013 S 164201788 Table of Contents RS-232 and USB Communication Ports Dell UPS Management SoftwareTesting Batteries UPS Status Menu Event Log MenuIntroduction Dell Online Rack UPSIntroduction Finding Information What are You Looking For? Find It HereSafety Warnings UPS Output PowerSafety Warnings Do not add weight to slide/rail mounted equipment Installation Inspecting the EquipmentUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet Identifying the UPS Rear Panels 120V Rear PanelIdentifying the UPS Front Panel 230V Rear PanelRackmount Setup Opening the Metal Battery CoverIf installing additional UPSs, repeat for each cabinet Positioning the Rails Attaching the Rails to the Rack Installing and Securing the Cabinet Installing the Battery Tray Install the UPS front cover see Figure Installing the EBM Removing the Battery Connector CoverInstalling the Strain Relief Bracket Installing the UPS EBM InstallationInstalling Remote Emergency Power-off Repo Connections Wire FunctionRepo Connector Power Cord Ratings Minimum Upstream Circuit Breaker Rating UPS Output PowerUPS Initial Startup Installation UPS Startup and Shutdown OperationStarting the UPS Starting the UPS on Battery UPS ShutdownControl Panel Functions Control Button Functions Control Button SequenceDisplay Functions Changing the LanguageStartup Screen Screen Locked UPS StatusBattery Mode Bypass ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveStatus Summary Screens Description Battery Test Status Normal ModeHigh Efficiency Mode Converter ModeBattery Status Screens Description Event LogMeasurements Control Screens Control Screens DescriptionSettings Description Available Settings Default Setting SettingsIdentification Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Normal to Bypass Mode Transferring the UPS Between ModesSetting Power Strategy Transferring from Bypass to Normal ModeRetrieving the Event Log Behavior on OverloadConfiguring Load Segments Controlling Load Segments Through the DisplayConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring Battery Settings Configuring the UPS for an EBMRunning Automatic Battery Tests Configuring Automatic RestartConfiguring Automatic Battery Tests Additional UPS Features RS-232 and USB Communication PortsRS-232 Communication Port Pin Assignment GNDDell Network Management Card Optional Dell Network Management CardDell UPS Management Software UPS and Battery Care UPS MaintenanceTransporting the UPS Remove the UPS front cover see Figure Disconnect the internal battery connectors see Figure When to Replace Batteries Storing the UPS and BatteriesTesting Batteries Updating the UPS FirmwareSpecifications Power Levels Rated at nominal inputs Regulation Normal modeRegulation Battery mode Environmental and SafetyBattery Configuration Battery RuntimesVoltage FusesAccessing Alarms and Conditions TroubleshootingUPS Status Menu Typical Alarms and Conditions Event Log MenuAction Troubleshooting Troubleshooting Silencing the Alarm