Table 7. Settings (continued)
Description | Available Settings | Default Setting |
|
|
|
Set Date and Time | Set Month, Day, Year, Hours, Minutes, and Seconds |
|
| Date: mm/dd/yyyy | 01/01/2009 |
| Time: hh:mm:ss | 12:00:00 |
| NOTE: The date format is dependent on the |
|
| language selection. |
|
NOTE: Time is a
Control Commands from Serial Port
[Enabled] [Disabled] | Enabled |
If Enabled, control commands are accepted through the serial port, USB ports, or option card.
If Disabled, configuration and load control commands are restricted to LCD only.
Output Voltage | [200V] [208V] [220V] [230V] [240V] | |
|
| |
|
|
|
Output Frequency | [50Hz] [60Hz] | |
|
|
|
Overload Alarm Level | [10%] [20%] [30%]...[100%] | 100% |
| If 100%, the UPS issues an Output Overload alarm |
|
| at load > 100%. |
|
| NOTE: Output Overload Level 1 by default is set to |
|
| 100% and is configurable from 10% to 100% in 10% |
|
| increments through the LCD setting menu. This |
|
| allows customers to be alerted before the UPS has |
|
| reached its rated capacity limits. |
|
|
|
|
Power Strategy | [Normal] [High Efficiency] [Converter] | High Efficiency |
| See “Setting Power Strategy” on page 47. |
|
|
|
|
Automatic Start Delay | [Off] [0s] [1s] [2s]...[32767s] | 0s |
| See “Configuring Load Segments” on page 49. |
|
|
|
|
Automatic on Battery Shutdown | [Off] [0s] [1s] [2s]...[32767s] | Off |
| See “Configuring Load Segments” on page 49. |
|
|
|
|
Start on Battery | [Enabled] [Disabled] | Enabled |
| NOTE: Battery start is disabled from the factory and |
|
| remains disabled until the UPS has been powered |
|
| from utility and enters Standby mode. After the |
|
| UPS has been started once from utility, the Start on |
|
| Battery feature is automatically enabled. After this is |
|
| set by the user, it remains set. |
|
|
|
|
42 Operation