Dell 2700W manual Settings Description Available Settings Default Setting

Page 44

Table 7. Settings (continued)

Description

Available Settings

Default Setting

 

 

 

Qualify Bypass

[Always] [Never] [Bypass Disabled]

Always

 

If Always, Bypass operation is allowed when:

 

 

S

Bypass voltages > the value set for Bypass

 

 

 

Voltage Low Limit

 

 

S

Bypass voltages < the value set for Bypass

 

 

 

Voltage High Limit

 

 

S

Bypass frequency > (nominal frequency -3 Hz)

 

 

S

Bypass frequency < (nominal frequency +3 Hz)

 

 

S

Inverter is synchronized with Bypass when

 

 

 

unsynchronized transfers are disabled by the

 

 

 

value set for Unsynchronized Transfers

 

 

If Never, Bypass operation is always allowed; voltage

 

 

and frequency limits are not in use.

 

 

If Bypass Disabled, Bypass operation is prohibited.

 

 

 

 

Synchronization Window

[Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±1.5 Hz]

±3.0 Hz

 

[±2.0 Hz] [±2.5 Hz] [±3.0 Hz]

 

 

If ±3.0 Hz, on inverter operation the inverter tries to

 

 

synchronize with the Bypass when the Bypass

 

 

frequency is not more than 3 Hz from the nominal

 

 

output frequency; otherwise, the inverter goes to

 

 

nominal frequency. On Bypass mode, the sync

 

 

window is always ±3 Hz.

 

 

NOTE: In Sync Disabled state, if the Bypass

 

 

operation is allowed, the UPS synchronizes only

 

 

when it is operating on Bypass mode.

 

 

 

 

Unsynchronized Transfers

[Enabled] [Disabled]

Enabled

 

If Enabled, unsynchronized transfers to the Bypass

 

 

are allowed.

 

 

If Disabled, unsynchronized transfers to the Bypass

 

 

are not allowed.

 

 

NOTE: The Qualify Bypass setting may overrule the

 

 

Unsynchronized Transfers setting.

 

 

 

 

External Battery Module (EBM)

[0] [1]

0

 

See “Configuring the UPS for an EBM” on page 52.

 

 

 

 

 

44 Operation

Image 44
Contents Users Guide July 2013 S 164201788 Table of Contents RS-232 and USB Communication Ports Dell UPS Management SoftwareTesting Batteries UPS Status Menu Event Log MenuIntroduction Dell Online Rack UPSIntroduction Finding Information What are You Looking For? Find It HereSafety Warnings UPS Output PowerSafety Warnings Do not add weight to slide/rail mounted equipment Installation Inspecting the EquipmentUnpacking the Cabinet Unpacking the CabinetLifting the Cabinet Identifying the UPS Rear Panels 120V Rear PanelIdentifying the UPS Front Panel 230V Rear PanelRackmount Setup Opening the Metal Battery CoverIf installing additional UPSs, repeat for each cabinet Positioning the Rails Attaching the Rails to the Rack Installing and Securing the Cabinet Installing the Battery Tray Install the UPS front cover see Figure Installing the EBM Removing the Battery Connector CoverInstalling the Strain Relief Bracket Installing the UPS EBM InstallationInstalling Remote Emergency Power-off Repo Connections Wire FunctionRepo Connector UPS Initial Startup Minimum Upstream Circuit Breaker Rating UPS Output PowerPower Cord Ratings Installation Starting the UPS OperationUPS Startup and Shutdown Starting the UPS on Battery UPS ShutdownControl Panel Functions Control Button Functions Control Button SequenceStartup Screen Changing the LanguageDisplay Functions Screen Locked UPS StatusBattery Mode Bypass ModeBad Battery Detected or Battery Disconnected UPS General Alarms ActiveStatus Summary Screens Description Battery Test Status Normal ModeHigh Efficiency Mode Converter ModeBattery Status Screens Description Event LogMeasurements Control Screens Control Screens DescriptionIdentification SettingsSettings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Settings Description Available Settings Default Setting Transferring from Normal to Bypass Mode Transferring the UPS Between ModesSetting Power Strategy Transferring from Bypass to Normal ModeRetrieving the Event Log Behavior on OverloadConfiguring Load Segments Controlling Load Segments Through the DisplayConfiguring Automatic Start Delay Configuring Automatic on Battery Shutdown Configuring Battery Settings Configuring the UPS for an EBMConfiguring Automatic Battery Tests Configuring Automatic RestartRunning Automatic Battery Tests Additional UPS Features RS-232 and USB Communication PortsRS-232 Communication Port Pin Assignment GNDDell Network Management Card Optional Dell Network Management CardDell UPS Management Software Transporting the UPS UPS MaintenanceUPS and Battery Care Remove the UPS front cover see Figure Disconnect the internal battery connectors see Figure When to Replace Batteries Storing the UPS and BatteriesTesting Batteries Updating the UPS FirmwareSpecifications Power Levels Rated at nominal inputs Regulation Normal modeRegulation Battery mode Environmental and SafetyBattery Configuration Battery RuntimesVoltage FusesUPS Status Menu TroubleshootingAccessing Alarms and Conditions Typical Alarms and Conditions Event Log MenuAction Troubleshooting Troubleshooting Silencing the Alarm