Agilent Technologies 6050A, 6051A manual Stranded Copper Wire Ampere Capacity Wire Size, Ampacity

Page 44

Table 3-1. Stranded Copper Wire Ampere Capacity

Wire Size

AWG

22

20

18

16

14

12

10

8

6

4

Cross Section Area in mm2

0.75

1

1.5

2.5

4

6

10

Ampacity

5.0

8.33

10

15.4

13.5

19.4

16

31.2

25

40

32

55

40

75

63

100

135

Notes:

1. Ratings for AWG-sized wires derived from MIL-W-5088B. Ratings for metric-sized wires derived from IEC Publication

33-51.

.

2. Ampacity of aluminum wire is approximately 84% of that listed for copper wire.

3. When two or more wires are bundled together, ampacity for each wire must be reduced to the following percentages:

2 conductors 94%

3 conductors 89%

4 conductors 83%

5 conductors 76%

4.Maximum temperatures: Ambient = 50° C Conductor = 105° C

Local Sense Connections

Figure 3-12 illustrates a typical setup with module number 1 connected for constant current or constant resistance operation. Local sensing is used in applications where lead lengths are relatively short, or where load regulation is not critical. The sense switch must be set to LCL. Load leads should be bundled or tie-wrapped together to minimize inductance.

Remote Sense Connections

Figure 3-13 illustrates a typical setup with module number 1 connected for remote sense operation. The remote sense terminals of module 1 are connected to the output of the power supply. Remote sensing compensates for the voltage drop in applications that require long lead lengths. It is only useful when module 1 is operating in CV or CR mode, or when using voltage readback. The sense switch must be set to RMT. Load leads should be bundled or tie wrapped together to minimize inductance.

Parallel Connections

Figure 3-14 illustrates how modules can be paralleled for increased power dissipation. Up to six modules can be directly paralleled in CC or CR mode. Modules cannot be paralleled in CV mode. Each module will dissipate the power it has been programmed for. For example, if two modules are connected in parallel, with module number 1 programmed for 10 A and module number 2 programmed for 20 A, the total current drawn from the source is 30 A.

In Figure 3-14, all lead connections are terminated at the source. Each module is connected to the source using separate wires. Using the source as the current distribution point allows larger wires to be used for each module connection and also reduces the common impedance inherent in daisy-chained configurations.

If because of lead length or other considerations, lead connections cannot be made at the source, a remote distribution terminal may be required. Lead connections can also be daisy-chained across the module binding posts as long as the total current draw is less than the ampere-rating of AWG 8 wire (see Table 3-1). This is because two wires larger than AWG 8 cannot both fit inside an Electronic Load, binding post.

44 Installation

Image 44
Contents Operating Manual Certification Safety Summary Safety Summary Symbol DescriptionHerstellerbescheinigung Manufacturer’s DeclarationPrinting History Page Table of Contents Installation Local OperationCalibration Considerations for Operating in Constant Resistance ModeRemote Operation Page General Information What’s In This ManualOptions Safety Requirements SpecificationsDimensions Page Introduction Operation OverviewRemote Programming Local/Remote ControlFront Panel Description Modes of Operation Extended Power OperationProgrammable Features Triggered Current Level Constant Current CC ModeImmediate Current Level Constant Resistance CR Mode Transient Current LevelSoftware Current Limit Slew RateConstant Voltage CV Mode Immediate Resistance LevelTriggered Resistance Level Transient Resistance LevelTransient Operation Triggered Voltage LevelTransient Voltage Level Pulsed Transient Operation Hpsl Command DescriptionContinuous Transient Operation Sets pulse width to 1 millisecond Selects the external trigger inputSelects pulsed transient operation Triggering a preset level Selects the external trigger input sourceSelects toggled operation Triggering a transient pulseSlew Rate And Minimum Transition Time Risetime Transition LimitationInput Current, Voltage, and Power Measurement Transition Times and Slew Rates Short On/OffInput On/Off Saving and Recalling SettingsReading Remote Programming Errors Status Reporting Protection FeaturesResetting Latched Protection Overcurrent OverpowerOvervoltage Control Connector OvertemperatureReverse Voltage Remote SensingFault External Programming InputPage Installing The Modules InspectionPower Cord Configurations Procedure Installing The Mainframes Channel NumberRack Mounting Turn-On CheckoutCooling Line Voltage Switches Changing Line VoltageGpib Errors Channel Errors DescriptionTurn-On/Selftest Display DescriptionPower Test Controller ConnectionRear Panel Connectors and Switches Wire Size Strip backGpib Address AWG Input Binding Post Control Connector Sense SwitchPins Al and A2 +Sand -SIM and VM Com pin A3Application Connections Trigger ConnectorWiring Considerations Stranded Copper Wire Ampere Capacity Wire Size AmpacityLocal Sense Connections Remote Sense ConnectionsMaximum Wire Lengths to Limit Voltage Drops Zero-Volt Loading Connections12. Local Sensing 14. Parallel Operation Page Local Operation Local OperationControls and Indicators Description Chan Keys Function Keys Local Control Overview Using The Chan Keys Using The Function Keys Selecting the ChannelIdentifying the Selected Channel Turning the Input On/OffRecommended Programming Sequence Setting the Mode of Operation Setting CC ValuesProgramming Ranges ExamplesSetting CR Values Examples Setting CV Values Programming RangeTransient Operation Shorting The Input Displaying Error Codes Using The System KeysSetting The Gpib Address Changing Wake-up Settings Recalling the Factory Default ValuesPage Enter/Output Statements Gpib AddressOutput EnterSending a Remote Command Selecting a ChannelGetting Data Back Output 705 MeascurrRemote Programming Commands CC Mode Example CV Mode ExampleOutput 705INPUT on Output 705MEASCURR? Output 705 Chan 2INPUT OFF Output 705MODEVOLTRemote Programming Flowchart Sheet Remote Programming Flowchart Sheet CR Mode Example Output 705INPUT on Output 705MEASPOW?Continuous Transient Operation Example Output 705CHAN 2INPUT OFF Output 705MODECURROutput 705CHAN 1INPUT OFF Output 705MODEVOLT Pulsed Transient Operation ExampleSynchronous Toggled Transient Operation Example Output 705 Trigsour TIM Page Equipment Required CalibrationCalibration Commands CharacteristicsEquipment Required for Calibration Recommended ModelCalibration Flowcharts Example ProgramsCalibration Flowchart for a Modules Calibration Flowchart for a Modules Calibration Flowchart for a Modules Pause Subend Program Listing for a ModulesPause Print Voltage Calibration Line ElseEND if 610 Set low calibration point Calibration Flowchart for B Modules Calibration Flowchart for B Modules Calibration Flowchart for B Modules Program Listing for B Modules Clear Screen Print TABXY10,10CALIBRATION DoneWait 1260 If Flag then 1270 Output @LdRESReshipt 1280 Considerations For Operating In Constant Resistance Mode Considerations For Operating In Constant Resistance ModeConsiderations For Operating In Constant Resistance Mode Index IndexIndex Index 19, 20, 21 Agilent Sales and Support Offices Agilent Sales and Support OfficesManual Updates