Item |
| Requirements | Result |
| Temperature | 0°C to 45°C (32°F to 113°F). |
|
|
|
|
|
| Relative humidity | 5% to 90% (noncondensing). |
|
|
|
|
|
| Cleanness | • Dust concentration ≤ 3 × 104 particles/m3. (No |
|
| visible dust on desk within three days.) |
| |
|
|
| |
|
|
|
|
|
| • The equipment and floor are correctly grounded. |
|
|
| • The equipment room is |
|
|
| • The humidity and temperature are at a compliant |
|
|
| level. |
|
|
| • Wear an ESD wrist strap and uniform when |
|
| ESD prevention | touching a circuit board. |
|
| • Place the removed interface module on an |
| |
|
|
| |
|
| antistatic workbench, with the face upward, or put |
|
|
| it into an antistatic bag. |
|
|
| • Touch only the edges, instead of electronic |
|
|
| components when observing or moving a removed |
|
|
| interface module. |
|
|
|
|
|
|
| • Take effective measures to reduce interference |
|
|
| from the power grid system. |
|
|
| • Separate the grounding equipment of the router |
|
|
| from the grounding or lightning protection |
|
| EMI prevention | grounding equipment of other devices as far as |
|
| possible. |
| |
|
|
| |
|
| • Keep the router far away from radio stations, radar |
|
|
| and |
|
|
| current. |
|
|
| • Use electromagnetic shielding when necessary. |
|
|
|
|
|
|
| • The grounding cable of the chassis is correctly |
|
|
| grounded. |
|
|
| • The grounding terminal of the AC power |
|
| Lightning | receptacle is correctly grounded. |
|
| • A port lightning arrester is installed. (Optional.) |
| |
| protection |
| |
|
| • A power lightning arrester is installed. (Optional.) |
|
|
| • A signal lightning arrester is installed at the input |
|
|
| end of an external signal cable. (Optional.) |
|
|
|
|
|
|
| • Equip an uninterrupted power supply (UPS). |
|
| Electricity safety | • The emergency power switch in the equipment |
|
|
| room is located. |
|
|
|
|
|
| Workbench | • The workbench is stable enough. |
|
| • The workbench is correctly grounded. |
| |
|
|
| |
|
|
|
|
|
| • The rack has a good ventilation system. |
|
|
| • The rack is sturdy enough to support the weight of |
|
| the router and installation accessories. |
| |
| requirements | • The size of the rack is appropriate for the router. |
|
|
| • The front and rear of the rack are at least 0.8 m |
|
|
| (2.62 ft) away from walls or other devices. |
|
|
|
| |
Safety | • The router is far away from any moist area and heat source. |
| |
precautions | • The emergency power switch in the equipment room is located. |
| |
|
|
|
|
6