HP A6584A, A1354A, A1353A, A1356A, J4373A, J4370A, J4367A manual Alarm text Description

Page 105

Alarm text

Description

 

 

Input Out of Range

Input (Utility) fault: Measured input voltage has exceeded the upper

 

voltage limit specification for normal operation.

 

Input (Utility) fault: Measured input voltage is less than the lower voltage

 

limit specification for normal operation.

 

Input (Utility) fault: Measured input frequency is outside the upper or

 

lower frequency limit specification for normal operation.

 

Rectifier fault: Measured rectifier input current exceeds the upper current

 

limit specification for normal operation.

 

The utility input power is not within predetermined limits. This is possibly

 

caused by over voltage, under voltage, over frequency, under

 

frequency, or over current.

 

The utility input is not present, and detected voltage is zero.

 

 

Internal Failure

An attempt to automatically recalibrate the UPS has failed.

 

Charger fault: The battery charger has failed.

 

DC Link fault: Measured DC link voltage has exceeded the upper

 

voltage limit specification for normal operation.

 

At least one fan in the UPS has failed.

 

At least one fuse in the UPS has failed and must be replaced.

 

Inverter fault: Measured inverter output voltage has exceeded the upper

 

voltage limit specification for normal operation.

 

Inverter fault: Measured inverter output voltage is less than the lower

 

voltage limit specification for normal operation.

 

The inverter module has failed its power up self-test or its continuous self-

 

test.

 

Inverter fault: The inverter has failed.

 

The inverter output has failed and cannot support the load. The reasons

 

for this alarm are, for example, inverter over or under voltage, over or

 

under frequency, distorted waveform, and output out-of window.

 

Inverter fault: The measured inverter output current exceeds the upper

 

current limit specification for normal operation.

 

The inverter output voltage sensor has not been calibrated.

 

For a parallel system, this module has detected that the sync bus is not

 

active.

 

A test of the device EEPROM has detected a checksum failure. The

 

device either has not been programmed or contains suspicious data.

 

A test of the device ROM has detected a checksum or CRC error. The

 

device's operating code is suspicious and should be replaced or

 

reflashed.

 

In a multi-module system or internally to a UPS with multiple controllers,

 

the firmware versions in place are not compatible with each other.

 

 

Loss of Redundant

The agent lost communication to one of the redundant UPSs. This alarm

Communication

appears on the management module that is still in communication with the

 

agent. If both management modules lose communication with the agent, this

 

alarm does not appear.

 

 

Loss of Redundant Power

One of the redundant UPSs is off or on battery power.

 

 

Alert messages 105

Image 105
Contents HP UPS Management Module User Guide Audience assumptions Contents HP UPS Management Module web interface Technical support Alert messages 104 Features OverviewIntroduction HP UPS Power Protection Agent requirements HP UPS Power Protection Agent overviewTypical hardware configurations Configuration B Configuration aConfiguration C Configuration D Configuration E Configuration F Web interface requirements Configuration GSoftware Browser Front panel Component identificationInstalling the HP UPS Management Module Installing the management moduleRequired tools Installing the HP UPS Management Module Connecting the network cable Checking the Error LEDLaunching a terminal emulation program Connecting the configuration cablePress any key in 5 seconds to enter Service menu Configuring the management module for remote accessConnecting devices Installing the HP UPS Management Module Press the Reset button on the management module front panel Installing the HP UPS Power Protection Agent Installation overviewInstalling the agent on Windows operating systems Installing the agent using the GUI method Installing the HP UPS Power Protection Agent Installing the HP UPS Power Protection Agent Installing the HP UPS Power Protection Agent Installing the agent using the silent installation method DevManRA.ini Reconfiguring the agent on Windows operating systemsInstalling the agent using the installation script Installing the agent on Linux operating systemsInstaller launches a separate configuration program Log Installing the agent on SlesReconfiguring the agent on Linux operating systems Installing the agent on HP-UX operating systemsInstalling the agent on an Itanium system SetupRA Installing the agent using the silent installation method Uninstalling components from Windows systems Reconfiguring the agent on HP-UX operating systemsUninstalling components from Linux systems Uninstalling components from HP-UX systemsInstalling the HP UPS Power Protection Agent HP UPS Management Module web interface Accessing the web interfaceHP UPS Management Module web interface overview Web browserSystem tray icon Signing in to the web interfaceBrowser security alert Secure session for Mozilla or SeaMonkey Establishing a secure session for Internet ExplorerEstablishing a secure session for Firefox Navigating the web interfaceOverview menu Home tabNormal Critical HP UPS Management Module web interface Alarms menu Identification menu HP UPS Management Module web interface Parameters menu HP UPS Management Module web interface Manual Control menu Event Log menu Logs tabHP UPS Management Module web interface Application Log menu My Account menu Setup tabUser Accounts menu Network menu Network Management menu System Information tab Snmp Managers tab Trap Receivers tabRemote Access tab Event Notifications menu Events tab Email Setup tab Snmp Traps tab Attached Devices menuUPS Add / Edit Attached Device screen Controlling a load segmentHP UPS Management Module web interface Power Fail menu Advanced power fail settings Shutdown Events menu Low Battery-Selected Low Battery-DeselectedScheduled Shutdowns menu Add/Edit Scheduled Shutdowns screen Help tabAbout menu Info & Updates menu Contents menuHP UPS Management Module Service Menu overview HP UPS Management Module Service MenuAccessing the Service Menu Telnet sessionTerminal emulation session Navigating the menusService Menu HP UPS Management Module Configuration UtilityUPS Monitor submenu Network Configuration submenu Battery submenuPower Protection submenu Web Access submenu Network Settings submenuRemote Console submenu Snmp submenuSnmp Traps submenu Emails submenuSystem Configuration submenu Session Settings submenuDate/Time Configuration submenu Network Time Protocol submenu User Accounts submenuOption number Submenu Description Agent does not install on RH Itanium TroubleshootingAttached device communication errors appear Attached device did not shut down gracefullyBrowser incorrectly displays English or Japanese characters Battery Test did not runCertificate error Error LED illuminates or flashesEmail notifications are not received from an HP-UX server Flash update fails over a serial connection FTP error messages appear when connecting through LinuxEvent notification messages do not appear on console screen Event notifications are not being sentHPFlash does not install image.bin on a Pentium InstallShield error code -6001 appears during setupInput frequency shows zero Manual Load Dumped alarm not working Low battery warning is displayedInvalid IP address Links in traps and emails do not work correctly for LinuxNon-admin users cannot log in through telnet No powerOn battery alarm On boost alarmRedundant UPS status Receiving a security errorSles 10 agent does not autostart after power fail or reboot Silent install did not execute successfullyServers running Windows Server 2003 do not restart Unable to locate the .INI files for a silent install Unable to edit devices using telnetTask Bar menu does not clear Unable to discover a UPSUnable to reboot the machine Unable to set event delays using telnetUnable to start the HP UPS Power Protection Agent for Linux Utility alarm Technical support Before you contact HPHP contact information Regulatory compliance notices Regulatory compliance identification numbersFederal Communications Commission notice Canadian notice Avis Canadien ModificationsEuropean Union regulatory notice Japanese notice Bsmi notice Alert messages UPS alarmsAlarm text Description Nominal level Systems Insight Manager overview Systems Insight Manager integrationDiscovering the management module Configuring HP SIM to receive trapsConfiguring the management module to send traps to HP SIM Security considerations overview Security considerationsSnmp monitoring Optional power monitoring using SnmpUpdating the firmware overview Updating the firmwareConfiguring the software for redundancy Redundant configurationRedundant configuration Using the HP UPS Management Upgrade Utility Mass configurationHttps Acronyms and abbreviationsMII Index Linux, installing the agent Secure sessions, Internet Explorer