Battery Test did not run
Possible Cause: The UPS is On Battery.
Action: The UPS must be in a certain state before the battery test runs. For more information, refer to the section, "Parameters menu option ("Parameters menu" on page 51)."
Browser does not display the web interface for an installed management module
Action:
1.Be sure that the IP address and port number are correct. The default port number for
2.Be sure that the web interface (HTTP/HTTPS) is enabled on the management module.
Browser incorrectly displays English or Japanese characters
Possible Cause: Another user with different language settings logs in to the web interface.
Action: Log out of the web interface, close the browser window, and then sign in to the web interface again.