| Low | Low | |
|
|
| |
Shutdown Settings | The management module initiates | The management module initiates | |
Conserve Battery Power | system shutdowns after the specified | system shutdowns after the specified | |
delay when the UPS begins to | delay when the UPS begins to | ||
| |||
| operate on battery power, unless | operate on battery power. If a low | |
| the UPS issues a low battery alarm | battery alarm occurs during the | |
| before the shutdowns are initiated. | delay countdown, the management | |
| If a low battery alarm occurs during | module ignores the low battery | |
| the delay countdown, the | alarm and continues to observe the | |
| management module ignores the | On Battery shutdown delay setting.¹ | |
| On Battery settings and observes |
| |
| the Low Battery shutdown delay |
| |
| setting. |
| |
|
|
| |
Shutdown Settings | The management module initiates | The management module initiates | |
Maximize Runtime | system shutdowns when the UPS | system shutdowns when the UPS | |
runtime reaches zero, unless the | runtime reaches zero. If a low | ||
| |||
| UPS issues a low battery alarm | battery alarm occurs during the | |
| before the shutdowns are initiated. | runtime countdown, the management | |
| If a low battery alarm occurs during | module ignores the low battery | |
| the runtime countdown, the | alarm and continues to observe the | |
| management module ignores the | runtime countdown.¹ | |
| runtime remaining and observes the |
| |
| Low Battery shutdown delay setting. |
| |
|
|
| |
Shutdown Settings | The management module initiates | The management module does not | |
Do Not Shutdown | system shutdowns when the UPS | initiate any type of system shutdown. | |
issues a low battery alarm. The | Power is maintained until the battery | ||
| |||
| management module observes the | is depleted.² | |
| Low Battery shutdown delay setting. |
| |
|
|
|
¹Selecting this option might result in an ungraceful shutdown. The amount of remaining runtime cannot be accurately predicted after a low battery warning is issued.
² Running batteries to depletion can cause an ungraceful shutdown if a second power failure occurs before the batteries have fully charged.
4.Enter the amount of time to wait before restarting the attached device in the Restart Settings column. This option allows utility power to stabilize and disks in shared storage configurations to spin up before the server restarts.
5.Do one of the following:
o Click Save Settings to save the information.
o Click Refresh Page to cancel changes and restore the page settings to the last saved configuration.
o Click Help to view online help.
Shutdown Events menu
Click Shutdown Events in the left navigation frame to display the Shutdown Events screen. In addition to the typical events (such as power fail events) causing shutdowns, this screen enables administrators to configure other events to trigger a shutdown.
When a shutdown event occurs, the management module gracefully shuts down all attached devices and UPS load segments.
To specify an event for shutdown: