HP MicroLogix 1761-NET-ENI manual Node 250 TCP/IP Configuration

Page 40

4-12ENI Configuration (Node 248 to 254)

Node 250 - TCP/IP Configuration

This procedure describes configuration for the TCP/IP parameters. The TCP/IP parameters are configured by sending a message instruction to the ENI (or by using the ENI Configuration Utility).

1.Configure a 485CIF write message in the Allen-Bradley controller.

 

Only PLC2 type or 485CIF read/write messages

IMPORTANT

can be used to configure the ENI.

 

 

 

 

2.Set the destination (target) node to 250. Using node address 250 directs this message to the TCP/IP configuration function.

3.The local integer file must be set up for at least 4 integer locations. The first 4 words define the IP address and are required. All remaining variables are optional.

The table below describes the TCP/IP functions that can be configured. The sections following the table describe the functions in more detail.

Table 4.3 TCP/IP Configuration Parameters

Function(1)

Data Type

Length

Notes

IP Address

Integer

4 words

Format aaa.bbb.ccc.ddd. The ENI verifies

 

 

 

the first/highest octet of any IP as follows:

 

 

 

The first octet is between 1 and

 

 

 

223 and not equal to 127 or 169

 

 

 

The first octet is 0, and the entire IP

 

 

 

is 0.0.0.0

 

 

 

otherwise the IP address is treated

 

 

 

as an error

 

 

 

For example, 0.168.0.75 is an error, or

 

 

 

127.0.0.0 is an error.

 

 

 

 

Subnet Mask

Integer

4 words

If not sent, the default mask is derived

 

 

 

from the class of the IP address as shown

 

 

 

in Table 4-13.

 

 

 

 

Gateway

Integer

4 words

Only needed if a Gateway is present on the

 

 

 

Subnet. The default is 000.000.000.000.

 

 

 

 

Security Mask 1

Integer

4 words

If not present, the default is no security

 

 

 

mask 000.000.000.000.

Security Mask 2

 

 

 

 

 

 

 

 

 

(1) The IP address must be configured. All other functions are optional.

Publication 1761-UM006A-EN-P - February 2001

Image 40
Contents MicroLogix Ethernet Interface ENI Cat. No -NET-ENIAllen-Bradley is a trademark of Rockwell Automation Table of Contents Chapter Preface Who Should Use this ManualRelated Documentation For Read this DocumentTechnical Product Assistance Local Product SupportYour Questions or Comments on this Manual Preface P-4 Publication 1761-UM006A-EN-P January Product Overview Ethernet Connection Non-Ethernet DevicesHardware Features LED IndicatorsProduct Drawing Description Function ColorRS-232 Settings Default Other Options Default SettingsDF1 Settings Default Other Options Operating Modes Device CompatibilityMessaging MailEthernet Networks Using a Web Browser with the ENIBasic Ethernet Topology 6Product Overview Publication 1761-UM006A-EN-P February EMC Directive Low Voltage DirectiveSafety Considerations Mounting DIN Rail MountingPanel Mounting RemovalExternal Power Supply Wiring ENI Port IdentificationEthernet Connections Ethernet 8-Pin 10Base-T Connector PortPin Pin Name Ethernet Cables Maintain ENI ConnectionsRS-232 Connector RS-232 Connector Pin AssignmentsRS-232 Cables ENI Connected to Catalog Number Use CableOperation Overview Number of Connections Dedicated toOutgoing messages Incoming messagesRSLinx on Ethernet PC Connected to Ethernet ENI Functional OverviewOperation 4Operation RSLogix 6Operation ENI Configuration Node 248 to ENI Configuration UtilityCOM Port Settings RS-232 Baud Rate and TCP/IP ParametersMail Settings Save to ENI RAM or ENI ROMReset Message RoutingController Messaging Configuring ENI Data Parameters Target Device Parameters Configuring ENI String Parameters Configuring the ENI E-Mail From StringAlways set this to Node Function Data Type Number Options Default Elements Node 248 Save/Reset Function Save/ResetNode 249 From String ValueNode 250 TCP/IP Configuration TCP/IP Configuration Parameters Function Data Type LengthSubnet Mask is in auto-detect Subnet Mask Auto-Detect OperationSubnet Mask is set to Security Mask Behavior Example Condition Node 251 E-Mail Server Node 252 Bootp ConfigurationNode 253 Baud Rate ENI Baud Rate Options Configuration Value Integer Node 254 Ethernet Hardware AddressPeer-to-Peer Messaging Configuration Node TCP/IP address Message Routing ENI receives read orNode Node100 Node Node101100 Route 0 Address 101 Route 1 Address102 Route 2 Address 103 Route 3 AddressFunction ENI Node DF1 Message Routing148 Use any command supported by your controller Data Table Address Use any valid file Size in ElementsPage Mail Messages Node 50 to OverviewConfiguring E-Mail Smtp E-Mail AddressDestination Addresses Message TextMessage Fields to, from, subject Mail Mail Address Description Message ConfigurationNode Sending an E-Mail Message Mail messages System Diagram Example NetworkPurpose Scope RSLOGIX500131.200.50.95 Example Network IP Addresses Device131.200.50.96 Computer’s Ethernet card Configuring 1761-NET-ENI #1 Throttling Message InstructionsENI #1 Configuration ENI IP Addr Screen Configuring 1761-NET-ENI #2 Message Routing Nodes FunctionENI #2 Configuration RSLogix 5000 Ladder Program ENI #2 Configuration Message Instructions Parameters ENI #2 Configuration Rung Descriptions FunctionMessage Message Function Publication 1761-UM006A-EN-P February ENI #2 Configuration Message ConfigurationTab 10 L20 Controller’s Tags 11 File Mapping in RSLogix Configure Rslinx 1769-L2013 Modify DF1 Parameters Using RSLInx 14 SLC 5/05 Controller Ladder Program 15 SLC 5/05 Rung 0 MSG General Tab 17 SLC 5/05 Rung 1 MSG General Tab 19 ControlLogix 5550 Controller Ladder Program 20 ControlLogix 5550 Rung 0 Message Configuration Tab 22 ControlLogix 5550 Rung 1 Message Configuration Tab Configuring an Ethernet Driver in Rslinx 25 Configure Ethernet Driver Using RSLinx On solid for 2 seconds Power-Up SequenceFlashes for 4 seconds Description Color State Indicates Error Codes Generated by the ENI Message Instruction Error CodesError Code Description of Error Condition Pccc Description Remote station problem due to download Pccc Description Cannot execute command due to active IPBsConnection not completed before user-specified timeout Reply not received before user-specified timeoutPccc Description Command cannot be executed Pccc Description No accessPccc Description Data conversion error Pccc Description Overflow histogram overflow6Troubleshooting Publication 1761-UM006A-EN-P February Description ENI Specification Physical SpecificationsMicroLogix Web Site Mounting Dimensions DimensionsProduct Dimensions TCP/IP Parameters Function Format On the subnet maskGateway Optional1 ZeroUsing Bootp Install the Bootp ServerEdit the Bootp Configuration File Device Name IP Address Hardware Address Ethernet TCP/IPFrom See This platform Executable DOS-basedParameters if necessary Windows Windows Program ManagerRunning the Windows-Based Utility Running the DOS-Based UtilityParameter Description Glossary Node Pccc Programmable Controller Communications Commands RS-232 UTP Unshielded Twisted Pair Allocation of Ethernet connections 3-1Ethernet switch IndexMTA TCP Index Publication 1761-UM006A-EN-P February Page Publication 1761-UM006A-EN-P February