Roberts Gorden DAT115 Room Sealed Installation, Open Flued Installation, Building Ventilation

Page 19

SECTION 7: AIR SUPPLY

SECTION 7: AIR SUPPLY

7.1 Room Sealed Installation

When installed as a room sealed heater the air for combustion is drawn in from outside the building. It is important to ensure that there is adequate ventilation to provide air for the distribution fan/s.

7.2 Open Flued Installation

Ensure adequate air supply at all times for both combustion and heating requirements in accordance with local and national codes. The air supply to the heater must be fitted with a low resistance terminal to prevent the ingress of debris. See Page 12, Figure 7.

7.2.1 Heaters Installed Within the Heated Space

Where the volume of the heated space is greater than 4.7 m3 per kilowatt of total rated heat input and the air change rate is at least 0.5/h, additional high and low level ventilation will not be required.

For a building having an air change rate less than 0.5/h, ventilation will be necessary in accordance with local and national codes. Ventilation direct to outside must be provided as follows:

Heaters above 70 kW heat input = 350 cm2 + 2.5 cm2 per kW of rated heat input above 70 kW

7.3 Building Ventilation

Where ventilation is required air must be taken from an outside point where it is not likely to be contaminated or obstructed.

Where natural ventilation is used, suitable ventilation with outside air at low level must be provided in accordance with Section 7.2.1 and local and national codes.

Where mechanical ventilation is used, extract rate must be 5% - 10% less than the inlet rate. The mechanical ventilation must be interlocked with the burner on the heater.

7.4 Isolated Equipment Rooms

Ventilation must prevent the isolated equipment room temperature from exceeding 32°C as well as prevent any negative air pressure within the room. See Page 13, Figure 9. Any isolated equipment room containing air heaters will require permanent air vents direct to outside air in compliance with local codes.

Where natural ventilation is used, suitable permanent openings at low and high level, communicating directly with the outside air, must be provided.

Where mechanical ventilation is used, extract rate must be 5% - 10% less than the inlet rate. The mechanical ventilation must be interlocked with the burner on the heater.

Figure 9: DualAir® Units Installed in Isolated Equipment Rooms.

High level ventilation Manifold

Air Intake

Flue

Duct distribution

Return air duct

system or

from heated

discharge to

space or fresh

heated space.

air from outside

Max Temperature 32° C

Room air pressure must not be negative.

Wall

Low level ventilation

Outside

Wall

13

Image 19
Contents DualAir Page 2005 Page Table of Figures Page Product Approval Corrosive Chemicals Clearances to CombustiblesNational Standards and Applicable Codes Flue Minimum Required Installation ClearancesCritical Considerations 3.1 Basic Information Electrical SupplyInstallation Clearances and Clearances to Combustibles Front View Left Version Specifications 4.1 DAT all modelsModel 100 115 Fan Data General Technical Data Table all modelsModel 100 115 2 DAT100 and 115 4 kW motor Handling Heater Installation 5.1 GeneralShelf Mounting and Suspension Flue Conversion Flue Installation 6.1 Flue InstallationType B22 Appliance Air Intake Terminal CoverControl Section & Upper Panel Vertical and Horizontal Flue Termination Type B22 Appliance Building Ventilation Room Sealed InstallationOpen Flued Installation Heaters Installed Within the Heated SpaceDuct resistance and design. Tel +44 0 Optional Heater Configurations 8.1 Distribution Duct14, .1 and to ensure that there is Department for recommendations regardingConnections Gas Connection with Stainless Steel Flex ConnectorRemote Frost Thermostat Remote ControlSee Page 17, .3 through Page 18, Section Number See Page 20, Section DAT Wiring Diagram ModelsSite wiring connections shown DAT Site Connections at Main Circuit Board Electrical Checks Gas Fired HeaterCooling Coils/Condensers LouversAutomatic Burner Control Box Sequence Set Minimum Pressure Combustion Testing all modelsCommissioning the Gas Valves Commissioning the Gas ValveInstruction to the User Pressure SwitchTurning Off the DualAir Unit Complete the CommissioningSee Page 7, .3 and Page 8, Figure See Page 26, SectionSee Page 25, Section Heater OperationCooling Section Operation Burner Lockout Reset ButtonSimple Fault Finding all models Simple Fault Finding burner faultsServicing 13.1 Servicing Instructions Burner Maintenance13.3 Fan/Motor Assembly Maintenance Heat Exchanger MaintenanceGas Control Valve Maintenance all models Burner Conversion Conversion Between Gases 14.1 GeneralGas Valves Conduct Commissioning procedure as shown on Page 21, Section Result in death or electrical shock Troubleshooting For Automatic Ignition Burner SystemsStart Troubleshooting for Flame Supervision SystemTroubleshooting for Main Fan Troubleshooting for Solenoid ValvesConduct Commissioning procedure as on Page 21, Section Troubleshooting for Fan ContactorGas Valve Gas Valve Replacement all modelsBurner Components See Page 5, SectionBurner Injectors Burner CompartmentIgnition Electrode and Flame Probe Remove screws securing outlet flange to the flue adapter See Page 21, Section Heater Pressure SwitchCoil Pressure Switch Pressure SwitchesFilter Pressure Switch 16.7.1 S4563C Models 75 to Ignition ControlFan Motor Removal Fan Removal and Replacement Combination Fan/Limit Thermostat Page Page Some objects can catch fire or explode when placed
Related manuals
Manual 52 pages 54.64 Kb