DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 15: TROUBLESHOOTING 15.1 General

WARNING

Explosion Hazard

Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.

Failure to follow these instructions can result in death, injury or property damage.

Start

Are gas & electrical

supplies on?

Yes

Is Red lockout

warning light on?

No

Does the fan run?

Yes

With external controls on, does the burner continue through the heating cycle?

Yes

Heater Operating

TROUBLESHOOT ENDS.

No

Yes

No

Yes

No

No

Turn on supplies.

Use 15.2 to test burner.

Press the white button on

the combination fan/limit No thermostat. Does the

fan run now?

Yes

See sections 5.3 & 11.3 to

check combination No fan/limit thermostat settings.

Does the fan run?

Has burner “Locked Out”? No

Yes

Use 15.2 to test burner.

If problems persist, contact ROBERTS GORDON® at Tel: +44 (0)1902 498733 or www.rg-inc.com

Use 15.5 to test fan.

Replace combination fan/limit thermostat.

Is combination fan/limit thermostat set correctly? No See sections 5.3 &11.3.

Adjust or replace

as necessary.

For your safety and optimum heater performance use only ROBERTS GORDON® replacement parts.

Conduct Commissioning procedure as shown on Page 21, Section 11

30

Image 36
Contents DualAir Page 2005 Page Table of Figures Page Product Approval Clearances to Combustibles Corrosive ChemicalsNational Standards and Applicable Codes Minimum Required Installation Clearances Critical Considerations 3.1 Basic InformationElectrical Supply FlueInstallation Clearances and Clearances to Combustibles Specifications 4.1 DAT all models Front View Left VersionGeneral Technical Data Table all models Model 100 115 Fan DataModel 100 115 2 DAT100 and 115 4 kW motor Heater Installation 5.1 General HandlingShelf Mounting and Suspension Flue Installation 6.1 Flue Installation Type B22 ApplianceAir Intake Terminal Cover Flue ConversionControl Section & Upper Panel Vertical and Horizontal Flue Termination Type B22 Appliance Room Sealed Installation Open Flued InstallationHeaters Installed Within the Heated Space Building VentilationOptional Heater Configurations 8.1 Distribution Duct 14, .1 and to ensure that there isDepartment for recommendations regarding Duct resistance and design. Tel +44 0Gas Connection with Stainless Steel Flex Connector ConnectionsRemote Control Remote Frost ThermostatSee Page 17, .3 through Page 18, Section Number DAT Wiring Diagram Models See Page 20, SectionSite wiring connections shown DAT Site Connections at Main Circuit Board Gas Fired Heater Cooling Coils/CondensersLouvers Electrical ChecksAutomatic Burner Control Box Sequence Combustion Testing all models Commissioning the Gas ValvesCommissioning the Gas Valve Set Minimum PressurePressure Switch Turning Off the DualAir UnitComplete the Commissioning Instruction to the UserSee Page 26, Section See Page 25, SectionHeater Operation See Page 7, .3 and Page 8, FigureBurner Lockout Reset Button Simple Fault Finding all modelsSimple Fault Finding burner faults Cooling Section OperationBurner Maintenance 13.3 Fan/Motor Assembly MaintenanceHeat Exchanger Maintenance Servicing 13.1 Servicing InstructionsGas Control Valve Maintenance all models Conversion Between Gases 14.1 General Burner ConversionGas Valves Conduct Commissioning procedure as shown on Page 21, Section Troubleshooting For Automatic Ignition Burner Systems Result in death or electrical shockTroubleshooting for Flame Supervision System StartTroubleshooting for Solenoid Valves Troubleshooting for Main FanTroubleshooting for Fan Contactor Conduct Commissioning procedure as on Page 21, SectionGas Valve Replacement all models Burner ComponentsSee Page 5, Section Gas ValveBurner Compartment Burner InjectorsIgnition Electrode and Flame Probe Remove screws securing outlet flange to the flue adapter Heater Pressure Switch See Page 21, SectionPressure Switches Coil Pressure SwitchFilter Pressure Switch Ignition Control 16.7.1 S4563C Models 75 toFan Motor Removal Fan Removal and Replacement Combination Fan/Limit Thermostat Page Page Some objects can catch fire or explode when placed