SECTION 10: WIRING AND ELECTRICAL INFORMATION
10.3 DAT Main Circuit Board Terminal Identification
Terminal  | Use  | Relay/Function  | Operation  | |
Number | 
  | 
  | 
  | |
  | 
  | 
  | 
  | |
  | 
  | Input for Remote Fan Opera-  | Optional - Main Fan Runs from  | |
1 Input or Output  | External Fan Control  | tion Output for Fan Operation  | ||
External Control  | ||||
  | 
  | Monitor  | ||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
2 Output  | 230 V to external control  | 
  | 230 V 50 Hz supply of external  | |
  | thermostat or control  | |||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
3 Input  | Burner On  | Burner Fires.  | Burner Operates.  | |
R1 energizes with gas valve  | Fan Operates via R1  | |||
  | 
  | |||
  | 
  | 
  | 
  | |
4 Output  | 230 V Burner ON Signal  | 
  | Optional Remote Indication of  | |
  | Burner ON.  | |||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
5 Output  | Neutral for Signals  | 
  | 
  | |
& External Control  | 
  | 
  | ||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
7 Output  | 230 V Burner Lockout Signal  | 
  | Optional Remote Indication of  | |
  | Burner Lockout  | |||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
8 Input  | Burner Lockout Reset from N  | 
  | Optional Remote Burner Lock-  | |
(5)  | 
  | out Reset (must be from N)  | ||
  | 
  | |||
  | 
  | 
  | 
  | |
  | 
  | Site Wiring to Condensers  | DualAir® units contains Coil  | |
  | Volt Free Safety Circuits for  | Frost Thermostat, Coil Pres-  | ||
9 & 10  | Normally Closed Controls  | |||
External Condensers  | sure Switch & Auxiliary Contact  | |||
  | Break on Fault Position  | |||
  | 
  | on Contactor  | ||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
  | 230 V 1st Stage of Cooling  | 
  | Burner OFF  | |
11 Input  | R2 On  | Fan ON from R2  | ||
(Free Cooling)  | ||||
  | 
  | Dampers Output to T16  | ||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
  | 
  | 
  | Burner OFF  | |
  | 230 V 2nd Stage of Cooling  | R2 OFF  | Fan ON from R3  | |
12 Input  | Dampers Output to T15  | |||
Cooling Coil Stage 1  | R3 ON  | |||
  | Output to Condenser 1 at T17  | |||
  | 
  | 
  | ||
  | 
  | 
  | & 18  | |
  | 
  | 
  | 
  | |
  | 230 V 3rd Stage of Cooling  | R3 ON  | All input 12 Operations  | |
13 Input  | Cooling Coil Stage 2  | Output to Condenser 2 at T19  | ||
R4 ON | ||||
  | 
  | & 20  | ||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
  | 230 V Output for Optional  | 
  | 14 = Neutral  | |
14, 15 & 16 Output  | From R2  | 15 = Recirculated Air  | ||
Damper  | ||||
  | 
  | 16 = Fresh Air  | ||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
17 & 18  | Volt Free Control Circuit  | R3 ON  | Normally Open Contact  | |
Condenser 1  | 
  | for Condenser 1  | ||
  | 
  | |||
  | 
  | 
  | 
  | |
  | Volt Free Control Circuit  | R3 ON  | Normally Open Contact  | |
19 & 20  | R4 ON  | |||
Condenser 2  | for Condenser 2  | |||
  | 
  | |||
  | 
  | 
  | 
  | |
21 & 22 Output  | 230 V Output to  | 
  | 21 = L  | |
Remote Dirty Filter Warning  | 
  | 22 = N  | ||
  | 
  | |||
  | 
  | 
  | 
  | |
  | Volt Free Output to  | Alternative Dirty Filter Indica-  | Normally Open Contact  | |
23 & 24  | tion for BMS or DualAir® Con-  | |||
Remote Dirty Filter Warning  | for Dirty Filter Indication  | |||
  | trol  | |||
  | 
  | 
  | ||
  | 
  | 
  | 
  | |
25 & 26 Input  | 0 - 10 V DC Input for  | T3 Must Be Live to Operate  | 0 V = Minimum Fire  | |
Modulating Burner  | Burner  | 10 V = Maximum Fire  | ||
  | ||||
  | 
  | 
  | 
  | 
17