Roberts Gorden DAT90, DAT75, DAT100, DAT115 service manual Control Section & Upper Panel

Page 17

SECTION 6: FLUE INSTALLATION

5.Refit the air intake spigot to the flexible hose re- using the hose clamp and to the upper panel using the original screws.

6.Align the flues’ inner and outer spigots and attach through the holes in the upper panel re- using the original screws.

7.Refit the lower door.

Figure 5: Control Section & Upper Panel

Air Intake Spigot

Hose Clamp

Inner and Outer

 

Flue Spigots

Flexible Hose

360 mm Lenght

of 130 mm dia Flue

Upper Panel

 

Blanking Plate

 

 

Lower Door

Control Section

Figure 6: Alternate

Flexible Hose

 

Hose Clamp

Upper Panel

90° Bend

 

Spigot "A"

 

90mm Flue

 

Inner Spigot

 

 

Outer Spigots

11

Image 17
Contents DualAir Page 2005 Page Table of Figures Page Product Approval National Standards and Applicable Codes Clearances to CombustiblesCorrosive Chemicals Critical Considerations 3.1 Basic Information Minimum Required Installation ClearancesElectrical Supply FlueInstallation Clearances and Clearances to Combustibles Front View Left Version Specifications 4.1 DAT all modelsModel 100 115 Fan Data General Technical Data Table all modelsModel 100 115 2 DAT100 and 115 4 kW motor Shelf Mounting and Suspension Heater Installation 5.1 GeneralHandling Type B22 Appliance Flue Installation 6.1 Flue InstallationAir Intake Terminal Cover Flue ConversionControl Section & Upper Panel Vertical and Horizontal Flue Termination Type B22 Appliance Open Flued Installation Room Sealed InstallationHeaters Installed Within the Heated Space Building Ventilation14, .1 and to ensure that there is Optional Heater Configurations 8.1 Distribution DuctDepartment for recommendations regarding Duct resistance and design. Tel +44 0Connections Gas Connection with Stainless Steel Flex ConnectorSee Page 17, .3 through Page 18, Section Remote ControlRemote Frost Thermostat Number See Page 20, Section DAT Wiring Diagram ModelsSite wiring connections shown DAT Site Connections at Main Circuit Board Cooling Coils/Condensers Gas Fired HeaterLouvers Electrical ChecksAutomatic Burner Control Box Sequence Commissioning the Gas Valves Combustion Testing all modelsCommissioning the Gas Valve Set Minimum PressureTurning Off the DualAir Unit Pressure SwitchComplete the Commissioning Instruction to the UserSee Page 25, Section See Page 26, SectionHeater Operation See Page 7, .3 and Page 8, FigureSimple Fault Finding all models Burner Lockout Reset ButtonSimple Fault Finding burner faults Cooling Section Operation13.3 Fan/Motor Assembly Maintenance Burner MaintenanceHeat Exchanger Maintenance Servicing 13.1 Servicing InstructionsGas Control Valve Maintenance all models Gas Valves Conversion Between Gases 14.1 GeneralBurner Conversion Conduct Commissioning procedure as shown on Page 21, Section Result in death or electrical shock Troubleshooting For Automatic Ignition Burner SystemsStart Troubleshooting for Flame Supervision SystemTroubleshooting for Main Fan Troubleshooting for Solenoid ValvesConduct Commissioning procedure as on Page 21, Section Troubleshooting for Fan ContactorBurner Components Gas Valve Replacement all modelsSee Page 5, Section Gas ValveBurner Injectors Burner CompartmentIgnition Electrode and Flame Probe Remove screws securing outlet flange to the flue adapter See Page 21, Section Heater Pressure SwitchFilter Pressure Switch Pressure SwitchesCoil Pressure Switch Fan Motor Removal Ignition Control16.7.1 S4563C Models 75 to Fan Removal and Replacement Combination Fan/Limit Thermostat Page Page Some objects can catch fire or explode when placed
Related manuals
Manual 52 pages 54.64 Kb