Roberts Gorden DAT100, DAT75 Pressure Switches, Coil Pressure Switch, Filter Pressure Switch

Page 46

DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

16.6Cooling Coil Safety Devices 16.6.1 Cooling Coil Frost Thermostat

The sensing element for this device is inserted into the pocket of the cooling coil situated through the access hole in the coil cover.

The frost thermostat has two settings marked as set point with an arrow head and "diff". The control should be set at 5° C with a 1° C differential.

To replace, remove screw and pull off knob. Remove cover. Disconnect wires.

Pull the sensing element out of the pocket in the coil. Replace in reverse order.

16.6.2 Pressure Switches

The coil and dirty filter pressure switches are preset and different. They are differential pressure switches measuring the pressure loss across the coil or filter.

Coil Pressure Switch

(Normally open contact) used to prove adequate air flow for safe operation of cooling coil.

Filter Pressure Switch

(Normally open contact) used to give indication of filter becoming blocked.

To replace, remove coil compartment cover. Disconnect wires noting their position. Remove the flexible tubing noting the position of the tube connection. Replace in reverse order and check operation.

Figure 18: Cooling Coil Safety Devices.

Red

Coil Frost Thermostat set at 5°C with 1°C diff.

Coil Pressure Switch

set at 0.57 mbar (.23 in wc)

Filter Pressure Switch

set at 1.17 mbar (.47 in wc)

Red

N.O

Connections Negative

Pressure

White

White

Filter

Set

Positive

Pressure

Point

 

Description

Part Number

Coil Pressure Switch

90439801

Filter Pressure Switch

90439804

Coil Frost Thermostat

K018

40

Image 46
Contents DualAir Page 2005 Page Table of Figures Page Product Approval Corrosive Chemicals Clearances to CombustiblesNational Standards and Applicable Codes Electrical Supply Minimum Required Installation ClearancesCritical Considerations 3.1 Basic Information FlueInstallation Clearances and Clearances to Combustibles Specifications 4.1 DAT all models Front View Left VersionGeneral Technical Data Table all models Model 100 115 Fan DataModel 100 115 2 DAT100 and 115 4 kW motor Handling Heater Installation 5.1 GeneralShelf Mounting and Suspension Air Intake Terminal Cover Flue Installation 6.1 Flue InstallationType B22 Appliance Flue ConversionControl Section & Upper Panel Vertical and Horizontal Flue Termination Type B22 Appliance Heaters Installed Within the Heated Space Room Sealed InstallationOpen Flued Installation Building VentilationDepartment for recommendations regarding Optional Heater Configurations 8.1 Distribution Duct14, .1 and to ensure that there is Duct resistance and design. Tel +44 0Gas Connection with Stainless Steel Flex Connector ConnectionsRemote Frost Thermostat Remote ControlSee Page 17, .3 through Page 18, Section Number DAT Wiring Diagram Models See Page 20, SectionSite wiring connections shown DAT Site Connections at Main Circuit Board Louvers Gas Fired HeaterCooling Coils/Condensers Electrical ChecksAutomatic Burner Control Box Sequence Commissioning the Gas Valve Combustion Testing all modelsCommissioning the Gas Valves Set Minimum PressureComplete the Commissioning Pressure SwitchTurning Off the DualAir Unit Instruction to the UserHeater Operation See Page 26, SectionSee Page 25, Section See Page 7, .3 and Page 8, FigureSimple Fault Finding burner faults Burner Lockout Reset ButtonSimple Fault Finding all models Cooling Section OperationHeat Exchanger Maintenance Burner Maintenance13.3 Fan/Motor Assembly Maintenance Servicing 13.1 Servicing InstructionsGas Control Valve Maintenance all models Burner Conversion Conversion Between Gases 14.1 GeneralGas Valves Conduct Commissioning procedure as shown on Page 21, Section Troubleshooting For Automatic Ignition Burner Systems Result in death or electrical shockTroubleshooting for Flame Supervision System StartTroubleshooting for Solenoid Valves Troubleshooting for Main FanTroubleshooting for Fan Contactor Conduct Commissioning procedure as on Page 21, SectionSee Page 5, Section Gas Valve Replacement all modelsBurner Components Gas ValveBurner Compartment Burner InjectorsIgnition Electrode and Flame Probe Remove screws securing outlet flange to the flue adapter Heater Pressure Switch See Page 21, SectionCoil Pressure Switch Pressure SwitchesFilter Pressure Switch 16.7.1 S4563C Models 75 to Ignition ControlFan Motor Removal Fan Removal and Replacement Combination Fan/Limit Thermostat Page Page Some objects can catch fire or explode when placed
Related manuals
Manual 52 pages 54.64 Kb