Toshiba RAV-SM1100UT-E Electrical Work, How to wire, Single phase 50 Hz, Mm2 or more

Page 14

6 ELECTRICAL WORK

For the air conditioner that has no power cable, connect a power cable as mentioned below.

Model

RAV-

SM1100AT-E

SM1400AT-E

 

 

 

 

Power supply

 

220 – 240 V

 

Single phase 50 Hz

 

 

 

 

 

Maximum running current

22.0 A

 

22.8 A

 

 

 

 

Installation fuse rating

25 A (D type

)

 

 

 

Power cable

 

H07 RN-F or 245 IEC 66

 

(2.5 mm2 or more)

 

 

 

 

 

CAUTION

Wrong wiring may cause a burn-out to some electrical parts.

Be sure to use the cord clamps attached to the product.

Do not damage or scratch the conductive core and inner insulator of power and inter-connecting cables when peeling them.

Be sure to comply with local regulations of the cable from outdoor unit to indoor unit.

(wire size and cabling method etc.)

Use the power and Inter-connecting cables with specified thickness, specified type and protective devices required.

How to wire

1.Connect the connecting cable to the terminal as identified with their respective numbers on the terminal block of indoor and outdoor unit.

H07 RN-F or 245 IEC 66 (1.0 mm2 or more)

2.When connecting the connecting cable to the outdoor unit terminal, prevent water coming in the outdoor unit.

3.Insulate the unsheathed cords (conductors) with electrical insulation tape. Process them so that they do not touch any electrical or metal parts.

4.For inter connecting cable, do not use a wire jointed to another on the way.

Use wires long enough to cover the entire length.

Power supply

To Indoor unit

terminal block

terminal block

L N

1

2

3

 

 

 

 

Earth screw

 

 

Power cable

Connecting cable

Stripping length power cord and connecting cable

L N

10

10

1 2 3

10

 

 

10

50

40

40

30

Earth line

Earth line

(mm)

 

 

Power cable

Connecting

 

 

cable

 

CAUTION

The installation fuse (25A D type ) must be used for the power supply line of this air conditioner.

Incorrect/incomplete wiring might cause an electrical fire or smoke.

Prepare the exclusive power supply for the air conditioner.

This product can be connected to the mains. Connection to the fixed wiring :

A switch which disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring.

11

Image 14
Contents Split Type Accessories Adoption of NEW RefrigerantInstallation Manual Way Air Discharge Cassette TypeTo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Connect the connecting cable correctlyInappropriate grounding may cause electric shock Accessory and Installation Parts Accessory and RefrigerantSelection of Installation Before installationObstacle at rear side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at front side Upper side is freeSerial installation at front and rear sides Installation of Outdoor UnitStandard installation Obstacles at both front and rear sidesFor Reference Knockout procedureRefrigerant Piping Connection Piping connectionRefrigerant Piping Pipe Forming/End PositioningTightening of Connecting Part RequirementVacuum pump EvacuatingAir Purge How to open the valve How to close the valveSingle phase 50 Hz How to wireStripping length power cord and connecting cable Electrical WorkSelf-Diagnosis by LED Indication Final Installation ChecksCheck and Test Operation New tools for R410A Applicable to R22 model Changes Changes in the product and componentsNew tools for R410A Accessories Sold Separately Precautions for SafetyRAV-SM1100AT-E RAV-SM1400AT-E Outdoor unit Parts NameIndoor unit Parts Name of Remote Controller Display sectionOperation section Preparation Turn on the main power switch and/or the leakage breakerCorrect Usage StopWhen restarting the operation after stop Mode select button ModeTemperature button StartHow to stop swinging How to set up the wind directionHow to start swinging Heat operationCancel of timer operation Timer OperationTimer operation Get uniform circulation of room air Never open doors and windows more often than necessaryWindow curtains If you do not plan to use the unit for more than 1 month MaintenanceCleaning of remote controller Checks before operationAIR Conditioner Operations and Performance Troubles and Causes RE-INSTALLATIONDo not install the air conditioner in the following places Be careful with noise or vibrationsInoperative Part name ’ty Shape Separate sold partsPart name ’ty Shape Usage Part namePrecautions for Safety Inappropriate grounding may cause electric shock Avoid installing in the following places Selection of Installation PlaceInstallation space Model RAVHeight list of ceiling possible to be installed Selection of installation place Discharge directionAdvice Ceiling heightSM1100UT-E External viewModel RAV SM1400UT-EInstallation of hanging bolt Installation of ceiling opening and hanging boltInstallation of ceiling panel Sold separately Flexible hose Drain Piping WorkPiping/Heat insulating material Adhesive inhibitedDrain up Connection procedureCheck the draining Perform heat insulatingTightening connection Permissible Piping Length and HeatFlaring dia meter size a Unit mm Tightening torque of flare pipe connectionsGas leak check Use a vacuum pumpOpen the valve fully Thermal insulation processPacked valve handling precautions Valve at gas sideBe sure to connect earth wire. Grounding work Remote controller wiringCable connection Cabling on the ceiling panelWiring diagram Remote Controller CablingCabling diagram CablingProcedure How to execute a test runCase of wired remote controller Test RUNConfirmation and check TroubleshootingConfirmation of error history Maintenance Accessories ContentsTCB-AX21U W-E 85464189556000Name and Operation Precautions for SafetyRemote Controller HOW to SET the FAN Speed Signal Receiving PartDisplay Section Operation SectionHOW to Operate the Unit HOW to Operate the TimerHOW to Insert the Batteries HOW to Adjust AIR DirectionSlide Switch Address HOW to Handle the Remote ControllerHOW to USE the Remote Controller Correctly Start HOW to Perform Emergency OperationBefore Asking Repair Work Before asking a repair work, check the following itemsHow to check the program operation time FeaturesTurn on the power supply of the air conditioner RBC-EXW21EName and Operation of Each Part HOW to USE the Timer Correctly When ON/OFF time is set as follows, Error is displayed When push SET Button,Set error Next set up the operation time to the program 2To be checked Clearance of Holiday setupPush DAY button and put the operation Clear of a part of the programResuming of operation Matters to be memorized Power failureOperation of program weekly timer and air conditioner RBC-AS21E Selected mode displays Cooling only type Temperature Setup buttonSelected mode displays Heat pump type Start/Stop button Check button Used in servicingPush either or set to Auto Recommended temperature HOW to Operate AIR ConditionerPower supply Push button Push button to select fan speedInstallation Manual Check after installation Installation of adjust corner capInstallation of suction grille For wireless remote controllerRequirement for installation Multiple remote controllers Accessory partsHow to install remote controller Requirement to install Remote controllerRemote controller test run setup Accessory partsRequirement for installation Multiple remote controllers Installation placeRequirement to install Program weekly timer Accessory parts Part Name ’tyHow to install the program weekly timer Program weekly timer test run setupHow to install the remote sensor Accessory partsRequirement to install the remote sensor Drain-up Kit For Concealed Duct Type Indoor Unit To Personnel Charged in Installation Work and Service Components For Installation ProfessionalsUse for Indoor Unit Only Combination List of Adapter PartsCase of 4-way Ceiling Cassette RAV-SM **0 UT-E Case of Concealed Duct RAV-SM **0 BT-EAddress No. setup table SW01 ProcedureContents Main To Customers

RAV-SM1400UT-E, RAV-SM1100UT-E specifications

Toshiba has consistently been recognized for its commitment to innovation and quality in the HVAC market, and the RAV-SM1100UT-E and RAV-SM1400UT-E models exemplify this dedication. These inverter air conditioners are designed to provide efficient cooling and heating solutions for diverse applications, ensuring comfort in both residential and commercial spaces.

One of the standout features of the RAV-SM1100UT-E and RAV-SM1400UT-E is their advanced inverter technology. This technology allows the units to adjust their cooling and heating capacities based on the real-time conditions, leading to significant energy savings compared to traditional fixed-speed systems. The inverter allows for smooth operation at varying speeds, reducing energy consumption while maintaining a consistent indoor climate.

Both models offer exceptional efficiency ratings. With a high energy efficiency ratio (EER) and seasonal energy efficiency ratio (SEER), these units are designed to operate sustainably while delivering powerful performance. The RAV-SM1100UT-E offers a cooling capacity of 11 kW, while the RAV-SM1400UT-E boasts a more robust 14 kW, making them suitable for a range of spaces from smaller offices to larger commercial properties.

Another significant characteristic is their quiet operation. Toshiba has engineered these units to minimize noise levels, ensuring a tranquil environment. This is particularly beneficial in settings like hotels, restaurants, and workplaces where noise can be disruptive.

The RAV-SM series is also equipped with intelligent control technology. This feature allows users to manage the system from anywhere using a smartphone app, providing convenience and flexibility. Integration with smart home systems further enhances usability, making it easy to program schedules and adjust settings remotely.

Additionally, both models employ a variety of robust filtration systems, ensuring that the circulated air is clean and healthy. With filters that capture dust, allergens, and other particles, these units contribute to improved indoor air quality.

Durability is another hallmark of Toshiba's design philosophy. These air conditioners are built with high-quality materials, ensuring long-lasting performance and reliability even in demanding environments. The RAV-SM models are also designed to work efficiently in low outdoor temperatures, extending their usefulness throughout the year.

In summary, the Toshiba RAV-SM1100UT-E and RAV-SM1400UT-E air conditioners represent a fusion of innovation, efficiency, and user-centric design. With their advanced inverter technology, energy efficiency, quiet operation, intelligent controls, and durable construction, they stand as ideal solutions for those seeking effective climate management in their spaces.