5 EVACUATING
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using vacuum pump.
Do not use the refrigerant in the outdoor unit. For details, see the manual of vacuum pump.
Use a vacuum pump
Be sure to use a vacuum pump with
1.Connect the charge hose from the manifold valve to the service port of the gas side packed valve.
2.Connect the charge hose to the port of vacuum pump.
3.Open fully the low pressure side handle of the gauge manifold valve.
4.Operate the vacuum pump to start evacuating.
Perform evacuating for about 35 minutes if the piping length is 30 meters total for model SM560 and 50 meters for model SM800
(assuming a pump capacity of 27 liters per minute.) Then confirm that the compound pressure gauge reading is
5.Close the low pressure side valve handle of gauge manifold.
6.Open fully the valve stem of the packed valves (both sides of Gas and Liquid).
7.Remove the charging hose from the service port.
8.Securely tighten the caps on the packed valves.
REQUIREMENT
For the tools such as charge hose, etc., use those manufactured exclusively for R410A.
REQUIREMENT
•Charging an excessive or too little amount of refrigerant causes a trouble of the compressor. Be sure to charge the refrigerant of specified amount.
•A personnel who charged the refrigerant should write down the pipe length and the added refrigerant amount in the nameplate attached to the service panel of the outdoor unit. It is necessary to troubleshoot the compressor and refrigeration cycle malfunction.
Open the valve fully
Open the valve of the outdoor unit fully. A 4mm- hexagonal wrench is required for opening the valve.
Gas leak check
Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.
REQUIREMENT
Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).
Thermal insulation process
Apply thermal insulation for the pipes separately at liquid side and gas side.
For the thermal insulation to the pipes at gas side, be sure to use the material with
Using the attached thermal insulation material, apply the thermal insulation to the pipe connecting section of the indoor unit securely without gap.
Refrigerant amount to be added
For addition of the refrigerant, add refrigerant “R410A” referring to the attached Installation Manual.
Be sure to use a scale to charge the refrigerant of specified amount.
REQUIREMENT
Apply the thermal insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of the pipe. (The pipe exposed to the outside causes water leak.)
39