INSTALLATION MANUAL To Personnel Charged in Installation (Electric) Work and Service

Program Weekly Timer

MODEL : RBC-EXW21E

Accessory parts

Part Name

Q’ty

Program weekly timer

1

 

Connecting cable

1

(Length: 1.2m)

How to install the program weekly timer

NOTE 1 :

Avoid to twist the program weekly timer cable with the power supply cable, etc. or to store them in the same metal pipe, otherwise it causes a malfunction.

NOTE 2 :

Cabling

Connection diagram

(Be sure to use the attached connecting cable.)

Timer terminal Timer terminal

1

1

1

1

System diagram

DC12V

Program

 

 

 

Remote

 

weekly

 

 

 

controller

 

timer

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

wires

 

 

 

 

: Terminal block

 

 

 

 

 

 

 

 

Indoor unit

: Connector

Outdoor unit

69

Screws

2

M4 x 25

 

Wood screws

2

 

Spacer

2

 

Owner’s Manual

1

 

Installation Manual

1

 

Requirement to install

the program weekly timer

Installing dimension for serial installation

When installing the program weekly timer (remote controller/system controller, etc.) to the wall surface, follow the installation procedure in (Fig. 1) and (Fig. 2).

 

92.5mm or more

125mm or more

 

from the wall

 

Spacer

 

Wall

90mm or more

125mm or more

 

from the wall

2.5mm (Gap size)

Pull-out port of lead wire

Fig. 1

*When installing the remote controller and the program weekly timer which are set in parallel at upper side and lower side, in consideration of maintenance, keep a clearance with 25mm or more.

Install the program weekly timer apart from the generation source of noise.

NOTE 3 :

When noise is induced to the power source of the indoor unit, measures such as mounting the noise filter is necessary.

Install the program weekly timer to the box (Procured locally) which has previously inserted in the wall.

Small screws

Spacer

M4 x 25 (2 pcs.)

 

or wood screws

 

Rear case

Program weekly

timer body

Cover

Fig. 2

1.Inserting a minus screwdriver, etc. into the groove at the lower side of the program weekly timer, which appears when opening lid of the program weekly timer body, force open the rear case to remove it.

2.Using the attached M4 screws or wood screws (2 pcs.), fix the rear case of the program weekly timer. Before installation, press to open the screw hole with a screwdriver, etc.

Fix it with the spacer, but not so strongly. If the program weekly timer does not fit closely to the wall, adjust it by cutting off the spacer.

3.Connect the attached connecting cable

(4 cores) to the program weekly timer body.

4.Install the program weekly timer body by matching to hooks on the rear case and putting into the hooks.

Program

2

2

 

 

2

2

Remote

weekly

3

3

 

 

 

3

3

controller

timer

 

 

 

4

4

4

4

 

Connecting cable (Accessory)

Arrangement

The program weekly timer and the remote controller can be arranged to either right or left side.

Cabling procedure

Perform cabling in the following procedure.

1.Connect the attached connecting cable to the timer terminal (4P connector) of the program weekly timer. (Fig. 3)

<Remote controller> <Program weekly timer>

To terminal block

To program

To remote controller

for indoor unit

Attached

Connector

remote controller

weekly timer

connecting cable

section

cabling

 

 

 

 

Fig. 3

2.Pull the attached cable out of lead wire pull- out port on the rear case of the program weekly timer and connect the cable to the timer terminal (4P connector) of the remote controller via inside of the wall. (Fig. 4)

Attached connecting cable

<Program weekly timer> <Remote controller>

Lead wire pull-out port

Fig. 4

Program weekly timer test run setup

After installation, check (OFF to ON) output status using the forced ON switch on the rear side of the program weekly timer P.C. board. Then check the normal operation and certainly turn OFF the forced ON switch.

ON OFF

ON OFF

Forced ON switch

Memory backup function for power failure compensation

This program weekly timer stores in memory the contents set by the operation button during a power failure. Pushing PROGRAM button resumes the operation with the contents before the power failure when the power failure has been reset.

How to use [BACKUP]

After the installation work, check [BACKUP] switch on the rear side of the program weekly timer P.C. board is turned to ON side.

ON OFF

ON OFF

BACKUP switch

Explanation to customers

After the installation work, hand “Owner’s Manual” and “Installation Manual” to the customers.

Explain use and maintenance methods to the customers according to “Owner’s Manual”.

85464359429000 (EN)

Image 72
Contents Split Type Accessories Adoption of NEW RefrigerantInstallation Manual Way Air Discharge Cassette TypePrecautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Connect the connecting cable correctlyInappropriate grounding may cause electric shock Accessory and Refrigerant Selection of InstallationAccessory and Installation Parts Before installationInstallation Place Necessary Space for InstallationObstacle at rear side Upper side is free Obstacle at front side Upper side is freeInstallation of Outdoor Unit Standard installationSerial installation at front and rear sides Obstacles at both front and rear sidesKnockout procedure Refrigerant Piping ConnectionFor Reference Piping connectionRefrigerant Piping Pipe Forming/End PositioningTightening of Connecting Part RequirementEvacuating Air PurgeVacuum pump How to open the valve How to close the valveHow to wire Stripping length power cord and connecting cableSingle phase 50 Hz Electrical WorkFinal Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410ANew tools for R410A Applicable to R22 model Changes Accessories Sold Separately Precautions for SafetyRAV-SM1100AT-E RAV-SM1400AT-E Parts Name Indoor unitOutdoor unit Parts Name of Remote Controller Display sectionOperation section Turn on the main power switch and/or the leakage breaker Correct UsagePreparation StopMode select button Mode Temperature buttonWhen restarting the operation after stop StartHow to set up the wind direction How to start swingingHow to stop swinging Heat operationTimer Operation Timer operationCancel of timer operation Never open doors and windows more often than necessary Window curtainsGet uniform circulation of room air Maintenance Cleaning of remote controllerIf you do not plan to use the unit for more than 1 month Checks before operationAIR Conditioner Operations and Performance RE-INSTALLATION Do not install the air conditioner in the following placesTroubles and Causes Be careful with noise or vibrationsInoperative Separate sold parts Part name ’ty Shape UsagePart name ’ty Shape Part namePrecautions for Safety Inappropriate grounding may cause electric shock Selection of Installation Place Installation spaceAvoid installing in the following places Model RAVSelection of installation place Discharge direction AdviceHeight list of ceiling possible to be installed Ceiling heightExternal view Model RAVSM1100UT-E SM1400UT-EInstallation of hanging bolt Installation of ceiling opening and hanging boltInstallation of ceiling panel Sold separately Drain Piping Work Piping/Heat insulating materialFlexible hose Adhesive inhibitedConnection procedure Check the drainingDrain up Perform heat insulatingPermissible Piping Length and Heat Flaring dia meter size a Unit mmTightening connection Tightening torque of flare pipe connectionsUse a vacuum pump Open the valve fullyGas leak check Thermal insulation processPacked valve handling precautions Valve at gas sideBe sure to connect earth wire. Grounding work Remote controller wiringCable connection Cabling on the ceiling panelRemote Controller Cabling Cabling diagramWiring diagram CablingHow to execute a test run Case of wired remote controllerProcedure Test RUNTroubleshooting Confirmation of error historyConfirmation and check Maintenance Accessories ContentsTCB-AX21U W-E 85464189556000Precautions for Safety Remote ControllerName and Operation HOW to SET the FAN Speed Signal Receiving PartDisplay Section Operation SectionHOW to Operate the Unit HOW to Operate the TimerHOW to Adjust AIR Direction Slide SwitchHOW to Insert the Batteries HOW to Handle the Remote Controller HOW to USE the Remote Controller CorrectlyAddress HOW to Perform Emergency Operation Before Asking Repair WorkStart Before asking a repair work, check the following itemsFeatures Turn on the power supply of the air conditionerHow to check the program operation time RBC-EXW21EName and Operation of Each Part HOW to USE the Timer Correctly When push SET Button, Set errorWhen ON/OFF time is set as follows, Error is displayed Next set up the operation time to the program 2Clearance of Holiday setup Push DAY button and put the operationTo be checked Clear of a part of the programMatters to be memorized Power failure Operation of program weekly timer and air conditionerResuming of operation RBC-AS21E Temperature Setup button Selected mode displays Heat pump typeSelected mode displays Cooling only type Start/Stop button Check button Used in servicingHOW to Operate AIR Conditioner Power supplyPush either or set to Auto Recommended temperature Push button Push button to select fan speedInstallation Manual Installation of adjust corner cap Installation of suction grille Check after installation For wireless remote controllerAccessory parts How to install remote controllerRequirement for installation Multiple remote controllers Requirement to install Remote controllerAccessory parts Requirement for installation Multiple remote controllersRemote controller test run setup Installation placeAccessory parts Part Name ’ty How to install the program weekly timerRequirement to install Program weekly timer Program weekly timer test run setupAccessory parts Requirement to install the remote sensorHow to install the remote sensor Drain-up Kit For Concealed Duct Type Indoor Unit To Personnel Charged in Installation Work and Service For Installation Professionals Use for Indoor Unit OnlyComponents Combination List of Adapter PartsCase of 4-way Ceiling Cassette RAV-SM **0 UT-E Case of Concealed Duct RAV-SM **0 BT-EAddress No. setup table SW01 ProcedureContents Main To Customers