Toshiba MMK-AP0072H Refrigerant Piping, Permissible pipe length and permissible height difference

Page 13

8 REFRIGERANT PIPING

WARNING

If refrigerant gas has leaked during the installation work, ventilate the room immediately.

If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.

After the installation work, confirm that refrigerant gas does not leak.

If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may generate.

REQUIREMENT

When the refrigerant pipe is long, set the support brackets to fix the pipe with 2.5 to 3m intervals. If the pipe is not fixed, abnormal sound may generate.

Be sure to use the flare nuts attached to the indoor unit or those for R410A.

Permissible pipe length and permissible height difference

They are different according to the used outdoor unit. For details, refer to the Installation Manual attached to the outdoor unit.

Piping material and dimensions

Piping material

Phosphor deoxidization joint-less pipe for air conditioner

 

 

 

Model

MMK-AP0072H to MMK-AP0122H

 

 

 

Pipe size (mm)

Gas side

Ø9.5

 

 

Liquid side

Ø6.4

 

 

 

 

• Use a clean and new pipe, and check that impurity such as dust, oil, moisture, etc. does not adhere in the pipe.

Pipe Forming/End Positioning

Flaring

1. Cut the pipe with a pipe cutter.

OK

NO GOOD

90˚

Obliquity Roughness Warp

2.Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A are recommended.

However, the conventional tools can be used by adjusting projection margin of the copper pipe.

• Flaring diam. meter size :

 

 

 

A

 

A (Unit : mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer diam. of copper pipe

A

-+00.4

 

 

R410A

 

 

 

 

6.4

 

9.1

 

 

 

9.5

 

13.2

 

 

 

12.7

 

16.6

 

 

 

15.9

 

19.7

 

 

 

*In case of flaring for R410A with the conventional flare tool, pull it out approx. 0.5 mm more than that for R22 to adjust to the specified flare size.

The copper pipe gauge is useful for adjusting projection margin size.

10

Image 13
Contents MMK-AP0072H, MMK-AP0092H, MMK-AP0122H Adoption of NEW Refrigerant Contents Separate sold parts OthersRefrigerant piping New Refrigerant Air Conditioner Installation Precautions for SafetyTo Disconnect the Appliance from Main Power Supply Precautions for Safety Selection of Installation PlaceInstallation diagram of Indoor and outdoor units Installation spaceInstallation place Selection of Installation Place Installation of Indoor UnitRemote controller When the installation plate is directly mounted on the wall Mounting the installation plateCutting a hole Piping and drain hose forming Piping and Drain Hose InstallationCase of bottom right or bottom left piping Case of right or left pipingLeft- hand connection with piping Drainage Indoor Unit FixingRefrigerant Piping Piping material and dimensionsPermissible pipe length and permissible height difference Pipe Forming/End PositioningConnection of refrigerant pipe Refrigerant PipingAirtight test/Air purge, etc Open fully valves of the outdoor unit Gas leak checkElectric Work Power supply specificationsElectric Work Wiring connectionHow to connect the wiring of flow selector unit Wiring connection for flow selector unitWiring between indoor and outdoor units Remote controller wiringAddress setup Wiring diagramBasic operation procedure for setup exchange Exchange of applicable control setupApplicable Controls Applicable Controls Adjustment of air directionChange of lighting time of filter sign To secure better effect of heatingCase of wired remote controller How to execute test operationTest RUN Before test operationCheck transmission of remote controller Check wiring/piping of indoor and outdoor unitsTest RUN Confirmation of error history TroubleshootingConfirmation and check Check code list TroubleshootingCheck method TerminologyRemote Indication Auxiliary code Error detected by TCC-LINK central control deviceDifference between the new check code and the current system New check codeCheck of Concentration Limit Indoor unit setup check sheet Confirmation of Indoor Unit Setup