Toshiba MMK-AP0092H Precautions for Safety, New Refrigerant Air Conditioner Installation

Page 5

1 PRECAUTIONS FOR SAFETY

Ensure that all Local, National and International regulations are satisfied.

Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.

The precautions described below include the important items regarding safety. Observe them without fail.

After the installation work, perform a trial operation to check for any problem.

Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.

Turn off the main power supply switch (or breaker) before the unit maintenance.

Ask the customer to keep the Installation Manual together with the Owner’s Manual.

CAUTION

New Refrigerant Air Conditioner Installation

THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.

The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.

To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are charged from those for the conventional refrigerant.

Accordingly the exclusive tools are required for the new refrigerant (R410A).

For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance force and impurity in it.

CAUTION

To Disconnect the Appliance from Main Power Supply

This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.

WARNING

Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.

Inappropriate installation may result in water leakage, electric shock or fire.

Turn off the main power supply switch or breaker before attempting any electrical work.

Make sure all power switches are off. Failure to do so may cause electric shock.

Connect the connecting wire correctly.

If the connecting wire is connected in a wrong way, electric parts may be damaged.

When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.

If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it as a result causes pipe burst and injuries on persons.

Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches.

Exposure of unit to water or other moisture before installation may cause a short-circuit of electrical parts.

Do not store it in a wet basement or expose to rain or water.

After unpacking the unit, examine it carefully if there are possible damage.

Do not install in a place that might increase the vibration of the unit.

To avoid personal injury (with sharp edges), be careful when handling parts.

Perform installation work properly according to the Installation Manual.

Inappropriate installation may result in water leakage, electric shock or fire.

When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.

ENGLISH

2

Image 5
Contents MMK-AP0072H, MMK-AP0092H, MMK-AP0122H Adoption of NEW Refrigerant Contents Refrigerant piping OthersSeparate sold parts To Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Precautions for Safety Selection of Installation PlaceInstallation place Installation spaceInstallation diagram of Indoor and outdoor units Remote controller Installation of Indoor UnitSelection of Installation Place Cutting a hole Mounting the installation plateWhen the installation plate is directly mounted on the wall Piping and drain hose forming Piping and Drain Hose InstallationLeft- hand connection with piping Case of right or left pipingCase of bottom right or bottom left piping Drainage Indoor Unit FixingRefrigerant Piping Piping material and dimensionsPermissible pipe length and permissible height difference Pipe Forming/End PositioningConnection of refrigerant pipe Refrigerant PipingAirtight test/Air purge, etc Open fully valves of the outdoor unit Gas leak checkElectric Work Power supply specificationsElectric Work Wiring connectionHow to connect the wiring of flow selector unit Wiring connection for flow selector unitWiring between indoor and outdoor units Remote controller wiringAddress setup Wiring diagramApplicable Controls Exchange of applicable control setupBasic operation procedure for setup exchange Applicable Controls Adjustment of air directionChange of lighting time of filter sign To secure better effect of heatingCase of wired remote controller How to execute test operationTest RUN Before test operationTest RUN Check wiring/piping of indoor and outdoor unitsCheck transmission of remote controller Confirmation and check TroubleshootingConfirmation of error history Check code list TroubleshootingCheck method TerminologyRemote Indication Auxiliary code Error detected by TCC-LINK central control deviceDifference between the new check code and the current system New check codeCheck of Concentration Limit Indoor unit setup check sheet Confirmation of Indoor Unit Setup